Page 10
GENERAL
Operating Conditions 0 - 50 °C (32 - 122 °F),
0 - 90 %RH non-condensing
Storage Temperature -20 - 60 °C (-4 - 140 °F)
Power Supply 24-30 Vdc / 20-26 Vac
Power Consumption 200 mA max
Wiring Connections Pluggable screw terminal block
(14 to 22 AWG)
Pressure Connections Port for 1/8”ID tubing
Enclosure - Wall Mount: SS304, suitable for wipe-down.
225mm wide x 182.5mm high x 36mm deep.
(8.86”x 7.19”x 1.46”)
Weight 1.3 kg
Certication CE, RoHS
TEMPERATURE
Sensor Type 10KΩ NTC thermistor sensor
Temperature Range 0-50 °C, 32-122 °F
Accuracy ± 0.2 °C (± 0.4 °F) curve matched
RELATIVE HUMIDITY
Sensor Type Thermoset polymer based capacitive sensor
RH Range 0-100 %RH
Accuracy ± 2 %RH
Hysteresis ±1.5%RH
Stability ± 1.2 %RH typical @ 50 %RH in 5 years
DIFFERENTIAL PRESSURE INPUT
CRA, CRB MODELS:
Sensor Type MEMS piezo resistive dierential sensor
Pressure Ranges 01 ± 250 Pa or ± 25 mmWc
02 ± 500 Pa or ± 50 mmWc
Accuracy ± 0.5 %FS
Stability ± 0.5 %FS max (1 year)
Thermal Eect <±1%FS,0-70°C(32-158°F)
Proof Pressure 24.9 kPa (2490 mmWc)
Burst Pressure 74.7 kPa (7470 mmWc)
Media Compatibility Dry air or inert gas
INDICATION
TemperatureDisplay 3digitLEDas0.0-50.0°Cor32.0-122°F
(°C / °F is indicated by an LED)
Relative Humidity Display 3 digit LED as 0.0-99.9 %RH
Dierential Pressure Display
3 1/2 digit LED display as -500-500 Pa
or -50.0-50.0 mmWc (Pa / mmWc is indicated by an LED)
Digit Type 7 segment red LED, 0.80”(20.32 mm) high
Alarm Indication Low/High alarm red LED for each
USER INPUT
Programming Menu/Up/Downfrontpaneltactilekeys
Alarm Silence Silence front panel tactile key
ANALOG OUTPUTS
Signal Type 4-20 mA (sourcing)
and 0-5 Vdc / 0-10 Vdc selectable
Number of Outputs 3 (Temp, RH, DP)
Output Drive 500 Ω max for 4-20 mA,
10 KΩ min for voltage
Output Scales 0-50 °C, 0-100 %RH, ± 500 Pa
ALARM OUTPUTS
Number of Outputs 3 (Temp, RH, DP) can assign
condition as low/high/both
OutputType NO optically isolated solid state FET switch
Contact Rating 100 mA at 28 Vac / 40 Vdc maximum
Trip Point Upper and Lower alarms
adjustable over a range
Alarm Delay 0 to 255 seconds (programmable)
Operation Self-resetting, non-latching
Alarm Buzzer Internal, operates on any alarm condition
Buzzer Delay 0-255 seconds (programmable)
Buzzer DB 70db at 30cm
Operation Self-resetting, can be silenced
via key or disabled remotely
COMMUNICATION
Hardware Isolated 2-wire RS-485 MS/TP
Software Modbus RTU or BACnet®
Baud Rate 9600, 19200, 38400, 57600, 76800 or 115200
Address Range 1-255 for Modbus, 0-127 for BACnet®
DIMENSIONS
225 mm
8.86“
182.5 mm
7.19“
36mm
1.46“
SPECIFICATIONS
IN-GE-CR3AXXNET-01 04/20 Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com