GROUP SCS EV-100 User manual

SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Copyright by SIMON PROtec Systems GmbH
Subject to technical changes and errors. All gures are exemplary.
Instruction manual
EV-100
Damper Interface Control Panel
SCS BA EV-100 EN 1.0
The supplementary sheet “Safety instructions and Warranty conditions” contains general
and product-specic warnings and the intended use.
This document is invalid without the supplement!

Contents
SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Page 2
1. Dimensions .................................................................................................................................................. 4
1.1. EV-100 Interface panel................................................................................................................................ 4
1.2. EV-100 Hot box ........................................................................................................................................... 4
1.3. EV-100 Internal arrangement ...................................................................................................................... 5
2. Technical information.................................................................................................................................. 6
2.1. Power supply information............................................................................................................................ 6
2.2. Actuator output............................................................................................................................................ 6
2.3. 230V Module (EV-100-OB) Output.............................................................................................................. 6
2.4. Indications (Feedback)................................................................................................................................ 6
2.5. FAS input for smoke detector EV-SD .......................................................................................................... 6
2.6. Mechanical features .................................................................................................................................... 6
2.7. Mechanical features (Hot Box).................................................................................................................... 6
2.8. Environmental requirements ....................................................................................................................... 6
2.9. Standards and certications........................................................................................................................ 6
3. Product description..................................................................................................................................... 7
3.1. Functional specications ............................................................................................................................. 7
3.2. Power supply............................................................................................................................................... 7
3.2.1. Modulating control .................................................................................................................................... 7
3.3. Transistor switch (on request) ..................................................................................................................... 7
3.4. FAS Fire Alarm Input ................................................................................................................................... 7
3.5. Status indicators.......................................................................................................................................... 7
3.5.1. Control board indicators ........................................................................................................................... 7
3.5.2. Mimic indicators........................................................................................................................................ 7
3.5.3. Function button......................................................................................................................................... 7
3.6. Addressing .................................................................................................................................................. 7
3.7. Conguration switches ................................................................................................................................ 8
4. General Functions ....................................................................................................................................... 8
4.1. Normal mode............................................................................................................................................... 8
4.2. FAS Alarm ................................................................................................................................................... 8
4.3. Alarm override............................................................................................................................................. 8
4.4. Lockout........................................................................................................................................................ 8
4.5. Test.............................................................................................................................................................. 8
4.5.1. Test mode sequence ................................................................................................................................ 8
5. Installation Instructions .............................................................................................................................. 9
5.1. Addressable Damper System – Fire & Smoke Dampers (Spring Close) .................................................... 9
5.2. Addressable Damper System – Smoke Control Dampers (Failsafe in Position) ...................................... 10
5.3. Standalone Damper Control – Fire & Smoke Dampers (Spring Close) .....................................................11
5.4. Standalone Damper Control – Smoke Control Dampers (Failsafe in Position)......................................... 12
6. Commissioning Instructions .................................................................................................................... 13
6.1. Installation and wiring inspection .............................................................................................................. 13
6.2. EV-100 Conguration & Test ..................................................................................................................... 13
7. Troubleshooting......................................................................................................................................... 14

SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Issue: 1.0 / 11.2022 [email protected] Page 3
Contents
8. Appendix .................................................................................................................................................... 14
8.1. Manufacturer‘s declaration EC.................................................................................................................. 14
8.2. EC manufacturer‘s declaration ( distributor)............................................................................................... 14
8.3. Manufacturer‘s declaration UK.................................................................................................................. 14
8.4. UK manufacturer‘s declaration ( distributor)............................................................................................... 14
8.5. Company address ..................................................................................................................................... 14

Dimensions
SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Page 4
1. Dimensions
1.1. EV-100 Interface panel
1.2. EV-100 Hot box

SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Issue: 1.0 / 11.2022 [email protected] Page 5
Dimensions
1.3. EV-100 Internal arrangement
Addressing SW1
Conguration SW2
Reset Button
Status Indication
Mains terminal
Fuses
Terminations
Rotary switch for damper position
230 V AC supply
for EV-100-OB

Technical information
SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Page 6
2. Technical information
2.1. Power supply information
Nominal voltage 230 V AC
Permitted voltage range 85 V AC to 253 V AC
Power consumption (full load) 0.4 A
Min. series fuse (on site) ≥ C 6 A
Connected load 92 VA
Inrush current (cold start) 40 A
Frequency range 47 Hz to 63 Hz
Mains fuse (internal) Fuse characteristic
Type T 1.25 A
Clamp size 0.5 mm² - 2.5 mm²
2.2. Actuator output
Output voltage mains operation
(nominal) 24 V DC
Maximum output current Iout 0.9 A (24 V DC)
Motor output fuse Type T 0.8 A (24 V DC)
Modulating output 0–10 V DC
Modulating input range 0–10 V DC
Modulating input maximum range 0–30 V DC
Ripple of the output voltage Vpp
(0 A < Iout < 0.9 A) ≤ 200 mVpp
Clamp size 0.5 mm² - 2.5 mm²
2.3. 230V Module (EV-100-OB) Output
Output voltage (mains nominal) 230 V AC
Output current Iout 1.25 A
Output fuse for actuators Type T 1.25 A (230 V AC)
2.4. Indications (Feedback)
Output voltage (+) 24 V DC
Input voltage range 15 V DC to 30 V DC
2.5. FAS input for smoke detector EV-SD
Maximum number of EV-SD 8
Output voltage range (B1) 17.5 V DC to 18 V DC
Current carrying capacity (B1) max. 120 mA
Monitoring current (OK range) 100 μA to 5 mA
2.6. Mechanical features
Housing Dimensions 182 × 180 × 90 mm (h × w × d)
Weight (not including batteries) 0.9 kg
Ingress rating IP66
Housing material Polystyrene
Colour Light Grey RAL 7035
Protection class II
2.7. Mechanical features (Hot Box)
Housing Dimensions 284 × 284 × 160 mm (h × w × d)
Weight (not including batteries) 5.60 kg
Ingress rating IP551
Housing Insulating Fab-Bloc
Colour White RAL 9010
Protection class II
(1) Rating when correctly installed and sealed as per instructions
2.8. Environmental requirements
Ambient temperature -5 to 40 °C
Storage temperature -5 to 70 °C
Suitable for outdoor installation No
2.9. Standards and certications
EN compliant As per EMC directive
2014 / 30 / EU and the
low voltage directive
2014 / 35 / EU
UK compliant As per Electromagnetic
Compatibility Regulations
2016 and Electrical Equip-
ment (Safety) Regulations
2016
Additional registrations,
certicates1
prEN 12101-9
BS ISO 21927-9
BS EN 12101-10
Classication as per EN 12101-9 Class D
Classication as per EN 12101-10 Class A
Environmental class as per
EN 12101-10 1

SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Issue: 1.0 / 11.2022 [email protected] Page 7
Product description
3. Product description
3.1. Functional specications
The EV-100 functions as a re damper and smoke control
damper interface panel. The panel provides a power supply
and control functions for most common types of damper ac-
tuators. It can operate as part of an addressable (network)
system or as a standalone unit.
The interface panel is compatible with the following damper
types:
● Spring close re dampers
● Spring open smoke control dampers
● Power open power close smoke control dampers
● Spring close modulating dampers
● Spring open modulating dampers
In network mode the panel functions as an addressable inter-
face panel relaying damper status and accepting operation
commands from a master damper control panel.
In standalone mode the panel can accept a smoke detector
or re alarm interface signal to operate a re damper.
The panel monitors the position and status of the damper and
indicates its condition. A test function operates the damper in
a test sequence and checks and reports any faults.
3.2. Power supply
The interface panel provides a 24 V DC power supply output
for the dierent damper types and congurations. The relay
switched outputs can power the damper in both directions
and a constant output supply is provided for actuator types
that require a permanent supply.
Installation of the AC option module converts the outputs to a
230 V AC actuator supply.
The damper position is monitored by fully open and fully
closed feedback switches rated at 24 V.
3.2.1. Modulating control
A 0-10 V output for proportional position control is provided
for modulating dampers.
The damper position is monitored by a congurable 0-10 V or
2-10 V feedback signal.
3.3. Transistor switch (on request)
A transistor switched 24 V DC output is available for special
applications and is controlled by the master panel.
3.4. FAS Fire Alarm Input
A smoke detector or re alarm interface can be connected
to the FAS input to trigger a FAS alarm condition. An alarm
signal is detected by an open or short circuit across the ter-
minating resistor. The alarm is automatically reset when the
circuit returns healthy by detecting the resistor value within
tolerance.
A reset command switches o the power to the FAS termi-
nals for 3 seconds to reset smoke detectors. An FAS alarm is
retriggered if the smoke detector fails to reset and return the
FAS input to a healthy condition.
3.5. Status indicators
The status of the panel is indicated by coloured LEDs located
on the control board and the front panel mimic.
3.5.1. Control board indicators
LED State Condition
OK
(Green)
O Power supply failure or internal panel fault
On Panel healthy and operating
Flashing Panel in a test sequence
ALARM
(Red)
O No alarms active and in normal mode
On In an alarm condition
Flashing In lockout mode
FAULT
(Amber)
O No fault or warning conditions
On A fault condition is active
Flashing Test failed result active and unacknowl-
edged
3.5.2. Mimic indicators
LED State Condition
OK
(Green)
O Power supply failure or internal panel fault
On Panel healthy and operating
Flashing Panel in a test sequence
ALARM
(Red)
O No alarms active and in normal mode
On In an alarm condition
Flashing In lockout mode
FAULT
(Amber)
O No fault or warning conditions
On A fault condition is active
Flashing Test failed result active and unacknowl-
edged
3.5.3. Function button
A test / reset button is located on the mimic and the control
board and do the same function.
Function Action
Test Press then release the button between 1 - 3 seconds
to start a test sequence.
Reset Press then release the button for > 5 seconds to trig-
ger a reset command.
3.6. Addressing
The panel address can be set between the range of 1 – 255
by switch SW1 in a binary format.
The address is the sum of the values set to ON position.
SW1 ON OFF Function
8 +128 0 Address Value 128
7 +64 0 Address Value 64
6 +32 0 Address Value 32
5 +16 0 Address Value 16
4 +8 0 Address Value 8
3 +4 0 Address Value 4
2 +2 0 Address Value 2
1 +1 0 Address Value 1

General Functions
SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Page 8
3.7. Conguration switches
SW2 OFF On Function
1 2..10V 0..10V Modulating position feedback range
Only applicable when SW2-5 is set to
modulating.
2Network Stand-
alone
Operating mode
Standalone mode operates as an
individual unit.
Network mode connects and receives
commands from a master panel.
3 Open Close Normal damper position / Reset
position
4 Hold Spring Actuator safety drive type
5 Fixed Modu-
lating
Actuator positioning type
6 No Yes Open and close position end switches
installed
4. General Functions
4.1. Normal mode
This is the default mode and normal damper position when
no alarms, overrides, lockout, or test sequences are active. In
normal mode the actuator outputs are switched (energised)
to drive the damper to the normal position set by SW2-3.
If the damper type is set to xed (SW2-5 = OFF) then the
normal position is set by SW2-3. The modulating output will
default to the normal position of 0V for close or 10V for open.
If the damper type is set to modulating (SW2-5 = ON) then
the normal position is set by the setpoint pot.
In a network conguration the position can be overridden by
the override setpoint command and setpoint position value.
The output responds instantly on a change of value with a
lter applied to avoid position hunting with signal noise.
Any position or setpoint change is automatically applied.
4.2. FAS Alarm
On detection of an FAS input alarm the damper switched
outputs automatically switch to the de-energised state. De-
pending on the damper type and conguration the actuator
shall drive or spring to their safety position. This should be
the opposite position to normal mode set by SW2-3.
The modulating output will default to the alarm position of 0V
for close or 10V for open.
An FAS alarm condition in standalone mode (SW2-2 = ON)
is automatically reset when the FAS input returns healthy. In
network mode an FAS alarm can only by a reset command
from a function button or by command from the master panel.
4.3. Alarm override
The alarm position of the damper can be overridden open or
close in a network conguration by commands. Alarm over-
rides take priority over the FAS alarm position and will switch
the actuator output to the last override command received.
The modulating output will switch with the override position of
0V for close or 10V for open.
An alarm override condition is reset by a reset command from
the function button or by command from the master panel.
4.4. Lockout
Lockout only applies when in a network conguration. Con-
nection to the master panel is monitored and when a discon-
nection is detected the panel activates lockout mode.
If the panel was in normal mode when lockout is activated
the damper defaults to the FAS Alarm condition or damper
safety position.
If the panel was in an alarm or override position when lockout
is activated the actuator outputs will remain in its last known
condition or to the last command received.
On power-up the panel will automatically enter lockout mode
until connection to the master panel is alive.
4.5. Test
A test sequence checks the operation of the damper and can
only be performed whilst in normal mode. For a valid test the
damper position feedback signals need to be connected and
congured (SW2-6 = ON) or congured as a modulating type.
The test sequence is started by pressing a function button
between 1-3 seconds or by a test command from the master.
A test is immediately aborted on an alarm, override or lockout
condition or can be cancelled by a reset command.
The correct position feedback signals are checked within the
set travel time.
4.5.1. Test mode sequence
Sequence
Step
Damper
Output
Operation checks
SW2-6 = ON:
Feedback switches
SW2-5 = ON:
Modulating type
1 Open (en-
ergised)
Open feedback in-
put received within
the open time
Modulating position
feedback reached
=>95% within the
open time
2 Close
(de-ener-
gised)
Closed feedback in-
put received within
the close time
Modulating position
feedback reached
=<5% within the
open time
3Normal
position
Normal position
(SW2-3) feedback
input received
within the position
time
Modulating position
feedback reached
within 10% of the
setpoint value wit-
hin the open time
In the event an operation check condition is not met within
the given time, the respective test result failure bit is set and
a fault is indicated.
All results are cleared at the start of each test or by a reset
command.

SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Issue: 1.0 / 11.2022 [email protected] Page 9
Installation Instructions
5. Installation Instructions
DANGER
Risk of electrocution. Works on this equipment should
only be carried out by a qualied and competent electrical
person. Observe all electrical safety regulations and safe
systems of work. Check power supply has been isolated
or disconnected safely before removing equipment covers.
5.1. Addressable Damper System – Fire & Smoke Dampers (Spring Close)
24 V Fire Damper Spring Close 230 V Fire Damper Spring Close
24 V Modulating Fire Damper Spring Close

Installation Instructions
SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Page 10
5.2. Addressable Damper System – Smoke Control Dampers (Failsafe in Position)
24 V Smoke Control Damper
Fail in Position (Non-Spring)
230 V Smoke Control Damper
Fail in Position (Non-Spring)
230 V Smoke Control Damper
Fail in Position (Non-Spring)

SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Issue: 1.0 / 11.2022 [email protected] Page 11
Installation Instructions
5.3. Standalone Damper Control – Fire & Smoke Dampers (Spring Close)
24 V Fire Damper Spring Close 230 V Fire Damper Spring Close
24 V Modulating Fire Damper Spring Close

Installation Instructions
SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Page 12
5.4. Standalone Damper Control – Smoke Control Dampers (Failsafe in Position)
24 V Smoke Control Damper
Fail in Position (Non-Spring)
230 V Smoke Control Damper
Fail in Position (Non-Spring)
230 V Smoke Control Damper
Fail in Position (Non-Spring)

SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Issue: 1.0 / 11.2022 [email protected] Page 13
Commissioning Instructions
6. Commissioning Instructions
DANGER
Disconnect both mains supply poles before connecting
any device to the interface panel.
ATTENTION
The control board is sensitive to electrostatic discharge
causing damage to components. Do not remove or handle
the board, this may invalidate the warranty.
6.1. Installation and wiring inspection
¾Conrm that the correct panels are installed for their
damper actuator types and the wiring is correct against
datasheets.
¾What is the damper actuator voltage? EV-100 panels
have 24 V output as standard, 230 V output require a
conversion module.
¾What is the full load current of the dampers connected?
EV-100 panels have a maximum current output of 0.8 A.
¾Is the damper xed (2 position) or modulating (3 position)
type? Check if the correct wiring for the type of damper
and position feedback signals.
¾What is the correct operation of the damper? Check if the
actuator is mechanically tted to the damper allowing full
OPEN and CLOSE travel and correct fail-safe operation
and normal position.
¾Check if the power supply is available to all control and
interface panels.
6.2. EV-100 Conguration & Test
¾Set the EV-100 panel address (switch SW1) starting from
1 up to 60 for each network (see section 3.6).
¾Set the damper conguration (switch SW2, see section
3.7).
¾To apply any conguration changes press Reset for > 5
seconds.
¾Switch on standalone operation mode (switch SW2-2).
¾Check if the power to the panel and OK indicator is lit.
¾Press the TEST / RESET button for approximately 2 se-
conds to start the automatic test sequence. The OK indi-
cator will ash during test mode and the damper will start
to open and close in sequence.
¾Wait until the end of the test when the OK indicator stops
ashing. If a FAULT occurs correct the position feedback
and actuator wiring. Repeat until the test completes wi-
thout FAULT.
¾Reset standalone operation mode (switch SW2-2) ready
to receive commands from EV-DCP master panel.
¾For modulating dampers adjust the setpoint dial for the
desired balancing position. To apply a setpoint change,
press Reset for > 5 seconds.

Troubleshooting
SCS_BA_EV-100_EN_10 groupscs.co.uk Date: 21.11.2022
Page 14
7. Troubleshooting
ATTENTION
Due to the low loop current, the insulation resist-
ance of the monitored wire (B1) must be checked! The
insulation resistance must be = 20 MΩ/km (wire manu-
facturer specication), otherwise disconnections may be
undetected.
INFORMATION
The EV-100 indications are only visible with mains power
connected.
For more information about the operational status see 3.5.1.:
“Control board indicators” on page 7.
8. Appendix
8.1. Manufacturer‘s declaration EC
We hereby declare that the product complies with
the applicable directives. The declaration of con-
formity can be read at the company‘s premises
and will be sent to you upon request. This declaration certies
that the product complies with the mentioned directives, but
does not represent any guarantee of the product‘s features.
This declaration loses its validity, if the product is modied
without seeking our prior authorisation.
8.2. EC manufacturer‘s declaration
(distributor)
The installer is responsible for the correct assembly or com-
missioning, the preparation of the declaration of conformity in
accordance with EU regulations and for axing the CE mark-
ing. The CE marking must be positioned where it is visible.
8.3. Manufacturer‘s declaration UK
certies that the product complies with the mentioned regula-
tions, but does not represent any guarantee of the product‘s
features. This declaration loses its validity, if the product is
modied without seeking our prior authorisation.
We hereby declare that the product complies with
the applicable regulations. The declaration of con-
formity can be read at the company‘s premises and
will be sent to you upon request. This declaration
8.4. UK manufacturer‘s declaration
(distributor)
The installer is responsible for the correct assembly or com-
missioning, the preparation of the declaration of conformity
in accordance with UK regulations and for axing the UK
marking. The UKCA marking must be positioned where it is
visible.
8.5. Company address
8.5.1. System manufacturer (Germany)
SIMON PROtec Systems GmbH
Medienstraße 8
94036 Passau
Phone: +49 (0) 851 988 70 - 0
Fax: +49 (0) 851 988 70 - 70
E-Mail: [email protected]
Web: www.simon-protec.com
8.5.2. Group SCS
Group SCS
Capital Business Park
Parkway
Cardi CF3 2PZ
Phone: 0300 303 4104
Web: www.groupscs.co.uk
Table of contents
Other GROUP SCS Control Panel manuals
Popular Control Panel manuals by other brands

EST
EST EST3X Installation sheet

fadini
fadini Elpro 15 Plus instructions

Mitsubishi Electric
Mitsubishi Electric E1000 series Service and maintenance manual

Bentel Security
Bentel Security Academy8L manual

EDM
EDM Solution-16 Safecom installation manual

Honeywell
Honeywell IFP-2100 Basic operating instructions