Gamewell ZNS User manual

ZNS
MICROPROCESSOR BASED
CONVENTIONAL FIRE ALARM CONTROL
PANEL
Installation & Operation Manual
The Gamewell Company
60 Pleasant Street Part No. 71774
Ashland, MA 01721 Issue 4 12/4/98
PROPRIETARY MATERIAL
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

ZNS Installation and Operation Manual Issue 4 12/4/98
The information contained in this manual is proprietary to The Gamewell Company. Such
information and technical drawings may not be copied or reproduced in any manner, or disclosed to
organizations that might be competitive to Gamewell, without the express prior written consent of
The Gamewell Company.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

ZNS Installation and Operation Manual Issue 4 12/4/98
GENERAL INFORMATION
The Gamewell Company thanks you for choosing the ZNS Microprocessor based fire alarm control panel.
As with all our products we have taken great care to insure that we have provided a quality product. To
receive maximum benefit and many years of reliable service we would like to make the following
recommendations:
1. Read this manual carefully and in it's entirety before proceeding with the installation of the
ZNS panel.
2. Never make any connections with the power connected.
3. Gamewell spends many hours testing devices that are supplied by Gamewell to be used with
it's control panels to verify compatibility. To maximize system performance, and minimize
risk of damage to the equipment, we suggest using all Gamewell Components.
4. There is no substitute for proper maintenance and testing of this or any life safety
product. Gamewell recommends testing and maintenance of your ZNS in accordance with the
guidelines set forth by the National Fire Protection Association, to be done on a regular basis,
as a minimum.
5. This manual should be stored with the ZNS panel for future reference, and should not be
removed, providing reference to the operation and programming of the installed ZNS
Thank you again for choosing Gamewell. If you have any comments regarding your ZNS panel or other
Gamewell products, please feel free to contact us at:
The Gamewell Company
Product Marketing Department
60 Pleasant Street
Ashland, MA 01721
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

ZNS Installation and Operation Manual Issue 4 12/4/98
TABLE OF CONTENTS
Overview 1
Description 1
INSTALLATION AND WIRING 1
Mechanical 1
Wiring 1
Common Card 2
Indicators 2
Default Operation 2
Auxiliary Power 2
Programming 2
Zone Card 2
Indicators 2
Alarm Disconnect 2
Low /High Current Operation 2
Addressing 2
Zone Programming 2
Programming 3
Power Requirements 3
Appendix A 4
ZNS High Current Compatibility Identifier - 31016 4
Compatible Notification Devices 5
Appendix B 6
Drawings 6
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

ZNS Installation and Operation Manual Issue 4 12/4/98
1
GAMEWELL ZNS
This manual covers the installation, programming and service of the ZNS and its related modules. It
is a supplement to the INS-2 Installation and Programming manuals (P/N’s 70708-05 and 70709-04).
OVERVIEW
Description The ZNS is a microprocessor based conventional Fire Alarm Control Panel. It is
designed to monitor 2 to 32 conventional initiation zones and also allows 2 circuits of
addressable detection or control devices. The main control panel consists of an
addressable INS-2 system. Addition of an ZNS Common Module provides
connection to the conventional zone modules.
INSTALLATION AND WIRING
Mechanical Two cabinet sizes are available for the ZNS the smaller is used to house a 2 to 16
zone system and the larger is used on 2 to 32 zone systems.
21”W x 25.5”H x 4”D (1 to 16 zones)
21”W x 31.5”H x 4”D (2 to 32 zones)
The ZNS Common Module (p/n 31014) mounts in place of the INS-2 expander
module and plugs into the J5 connector. It is connected to the p/n 31015 Zone Mother
Board modules. Each mother board accepts two p/n 31016 two zone Conventional
Input Module. Refer to drawings A-M1104, D-M780 and D-M781 for mechanical
layout.
Wiring
Both high or low current zone should be wired in accordance with NFPA 70, article
760. Maximum loop resistance should not excede 25 ohms. Refer to wiring diagram
A-W544 for terminations.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

ZNS Installation and Operation Manual Issue 4 12/4/98
2
COMMON CARD
Indicators The ZNS common card module has one LED. When first powered it flashes the
version number of the firmware on the ZNS module. Thereafter it will flash
whenever it is responding with zone information to an INS-2 poll.
Default Operation Default operation is a mode that allows alarms to be sensed and automatically routed
to the Signaling Circuits, if for some reason the ZNS controller fails.
Auxiliary Power Auxiliary power is available on the Common Card from terminals A+, A-. Resetable
smoke detector power is available from terminals S+, S-. This power is removed for
four seconds when the system is reset. Combined total current available from both
A+,A- and S+,S- is 0.5 amps.
Programming The ZNS Common Card is enabled by accessing level 4 programming area of the
INS-2 main board. Press the F1 key until the LED above the F1 key is illuminated.
Output controller location C220 must also be enabled and cannot be used by any
other devices. This output controller location allows the ZNS common card to reset
the S+, S- output.
ZONE CARD
Indicators Each 2 zone module has two LED’s per zone, one to indicate alarm and the other to
indicate trouble. The standard zone module has a red and yellow, the supervisory
zone has two yellow LED’s.
Alarm Disconnect Each zone of the 31016 2 zone card has a disconnect switch located next to the
LEDs. When this switch is activated, the zone will not report an Alarm, but it will
show that it is in Trouble
Low /High Current
Operation Each zone of the 31016 2 zone card can be programmed for two modes of operation,
low current and high current. The module is factory set as a high current zone. Low
current mode is selected by removing the following resistors.
Odd Zone Even Zone
Resistors to remove for low current operation. R1,R2,R3 R21,R22,R23
The EOL resistor high current value is 4.7K ohms and the low current value is 15K
ohms.
NOTE:
Low Current zones will not function with 2-wire Smoke Detectors, and
should be used with contact closure devices only.
Addressing The 31016 zone modules must be mounted from left to right. If a slot is empty the
system will not detect modules beyond the first open slot.
Zone Programming Each 31016 2 zone card has jumpers to distinguish between Class A or Class B
initiating circuits. There are also jumpers to program latching and non-latching
zones. All 31016 modules are factory set for Class B latching alarm operation. See
the chart below for programming options. Refer to drawing A-M1105 For resistor
locations.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

ZNS Installation and Operation Manual Issue 4 12/4/98
3
Programming Programming of the 31016 modules is accomplished with the INS-2 laptop software.
Each zone card installed requires 2 addresses regardless of wether both zones are
being used or not. The 31016 requires no programming of its address. It is addressed
automatically, via the ZNS, by its physical location to the addresses of 1 through 32.
Additional addressable modules may be added to the addressable circuits 1 and 2
starting with address 33.
JUMPER PROGRAMMING
Odd Zone Even Zone
Alarms Latched W1L Installed W2L Installed
Alarms Not Latched
(Supervisory Alarms Only) W1L Removed W2L Removed
Class B W1A Installed W2A Installed
Class A W1A Removed W2A Removed
Zone cards are shipped with all jumpers installed (Class B, Alarms Latched).
Power Requirements The ZNS common card draws 2 mA from the +24V supply and 5 mA from the
+5V supply.
The 31015 mother boards do not draw any power from the system.
Each 31016 zone card draws 0.5 mA from the +5V supply plus 6.5 mA for each
trouble or alarm LED on. Note that for one zone, the trouble and alarm LEDs will
never be on at the same time.
The current draw from the +24V supply for each zone on a 31016 zone card
depends upon whether it is configured for hi-current or low current operation.
lo-current -- without detect 2.5 mA max
lo-current -- in alarm 6 mA max
hi-current -- without detectors 6.5 mA max
hi-current -- with detectors 9.1 mA max
hi-current -- in alarm 60 mA max
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

ZNS Installation and Operation Manual Issue 4 12/4/98
4
APPENDIX A
ZNS High Current Compatibility Identifier - 31016
Detectors Bases
Gamewell Model No. Apollo Part No. Qty. Gamewell Model No. Apollo Part No.
71033 55000-350 71036 45681-200
71034 55000-250 71086 45681-220
71035 55000-150 20 71086-LOW 45681-232
71035-160 55000-151 71086-GREEN 45681-231
71035-210 55000-152 71086-RED 45681-230
71393 45681-227
71443 55000-380 10
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

ZNS Installation and Operation Manual Issue 4 12/4/98
5
Appendix A (Cont)
Compatible Notification Devices
Part #Part # Catalog #Catalog # Part #Part # Catalog #Catalog # Part #Part # Catalog #Catalog #
70871 MIZ-24-R 71562 SR-24110-HFR 71717 RSSP-24110W-FR
70873 MIZ-24-W 71569 RSP-241575-VFR 71727 AS-2415C-FW
71138 MT-12/24-R 71573 AMT-12/24-R 71728 AS-2430C-FW
71140 MT-24-WM-VFR 71574 AMT-24-LS-VFR 71729 AS-2475C-FW
71287 MIZ-24-LS-VFR 71575 AMT-24-IS-VFR 71730 RSS-2415C-FW
71288 MIZ-24-LSM-VFR 71576 AMT-24-LSM-VFR 71731 RSS-2430C-FW
71289 MIZ-24-MS-VFR 71614 MT4-12/24-R 71732 RSS-2475C-FW
71290 MIZ-24-IS-VFR 71616 SR-2475-VFR 71733 RSSP-2415W-FR
71292 MT-24 -LS-VFR 71679 AS-2415W-FR 71736 ET70-2415W-FR
71293 MT-24-LSM-VFR 71680 AS-241575W-FR 71737 ET70-241575W-FR
71294 MT-24-MS-VFR 71681 AS-2430W-FR 71738 ET70-2430W-FR
71295 MT-24-IS-VFR 71682 AS-2475W-FR 71739 ET70-2475W-FR
71426 MT-24 -SL-VFR 71683 AS-24110W-FR 71740 ET90-2415C-FW
71427 MT-24-SLM-VFR 71684 AS-24100C-FW 71741 ET90-2430C-FW
71543 AS-2415-VFR 71685 NH-12/24-R 71742 ET90-2475C-FW
71544 AS-241575-VFR 71686 NS-2415W-FR 71743 ET90-24100C-FW
71545 AS-2430-VFR 71687 NS-241575W-FR 71744 E70-2415W-FR
71546 AS-2475-VFR 71688 NS-2430W-FR 71745 E70-241575W-FR
71547 AS-24110-HFR 71689 NS-2475W-FR 71746 E70-2430W-FR
71548 SM-12/24-R 71690 NS-24110W-FR 71747 E70-2475W-FR
71549 DSM-12/24-R 71691 RSS-2415W-FR 71748 E70-24110W-FR
71550 RS-2415-VFR 71692 RSS-241575W-FR 71749 E90-2415C-FW
71551 SR-2415-VFR 71693 RSSP-241575W-FR 71750 E90-2430C-FW
71552 SRP-2415-VFR 71694 RSSP-2430W-FR 71751 E90-2475C-FW
71553 RS-241575-VFR 71695 RSS-2430W-FR 71752 E90-24100C-FW
71554 SRP-241575-VFR 71696 RSSP-2475W-FR 71758 CH90-24-W
71555 SR-241575-VFR 71697 RSS-2475W-FR 71759 CH70-24-R
71556 RS-2430-VFR 71698 RSS-24110W-FR 71760 CH70-2415W-FR
71557 RSP-2430-VFR 71699 RSS-24100C-FW 71761 CH70-241575W-FR
71558 RSP-2475-VFR 71711 AH-24WP-R 71762 CH70-2430W-FR
71559 RS-2475-VFR 71712 RS-2415W-FR 71763 CH70-2475W-FR
71560 RS-24110-HFR 71713 RS-241575W-FR 71764 CH70-24110W-FR
71561 SRP-24110-HFR 71714 W3MT-24-VFR
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

ZNS Installation and Operation Manual Issue 4 12/4/98
6
APPENDIX B
Drawings
D-M781 Ass’y of ZNS 16 Zones
D-M780 Ass’y of ZNS 32 Zones
A-M1104 Mounting Instruction: Card Guide
A-M1105 Configuring of 2 - Zone Card
D-W1171 Wiring ZNS System
A-W544 Wiring ZNS 2 Zone Card