30308433 Issue 1.02
Features
Electronically addressed. Address can bemodified
in field.
Built-in microprocessor processes information
intelligently.
Reusable button can be reset manually.
Providing an independent output contact.
Plug-in structure.
Description
I-9201(T) Addressable Manual Call Point with FT Jack
(MCP) is installed in public places. When there is a fire,
pressing the nearest MCP, alarm signal can be sent to
the fire alarm control panel (FACP). And the FACP will
show the address of the MCP, and give alarm sound.
Person in field can communicate with person at fire
telephone panel by plugging his handset of P-9912(A)
or P-9912(B) into this FT jack.
The MCP is operated by pressing the mechanically
latched button to reduce possibility of accidental alarm.
The built-in microprocessor can execute alarm
checking and communication with the control panel.
The microprocessor contains an EEPROM to store
messages like address and device type.
Connection and Cabling
Fig.1 shows terminals of the MCP.
Fig.1
Connection:
Z1, Z2: Loop connection, polarity-insensitive.
K1, K2: Volt-free normally open output contact. The
closed contact signal shall be output when the MCP is
pressed to directly control external devices.
TL1, TL2, AL, and G: Connecting with I-9304
Emergency Telephone Module or Fire Telephone
Panel.
Recommended Cabling:
1.0 mm2 or above fire cable for all cables. Subject to
local codes.
Installation
Unplug the MCP, thread the cable through the wiring
hole of the base box and connect it to corresponding
terminals, and plug the MCP back. The base of the
MCP can be surface mounted or flush mounted as
shown in Fig.2 and 3.
YM-02C Back Box
Conduit
Back Box
MCP Conduit
MCP
Fig.2 Fig.3
Warning: Before installing the MCP, disconnect the
power from the loop and verify that all bases are
securely installed and that the wiring polarity is
correct at each base.
Application
Connect the terminals Z1 and Z2 to the loop of control
panel directly. If connected with multi-wire fire
telephone panel, only TL1 and TL2 are needed. If
connected with addressable fire telephone panel, TL1,
TL2, AL and G are needed.
Before operation, the MCP should be
programmed by programmer. Please refer to
P-9910B Hand Held Programmer Installation and
Operation Manual for details.
If the connection and wiring are correct, the
control panel should be able to register the MCP.
When fire occurs, pressing the glass on the MCP,
the LED should flash quickly and the control
panel should display fire alarm message.
Please reset the MCP in time when fire alarm is
disposed.
I-9201(T) Addressable
Manual Call Point with FT Jack