Gude Expert Power Control 8021 Series User manual

Expert Power Control 8021 Series
Expert Power Control 8025 Series
© 2021 GUDE Systems GmbH
Manual Ver. 1.1.0
from Firmware Ver. 1.1
Manual

2
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH

3
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Table of contents
1. Device Description 5
1.1 Security Advice ....................................................................................................... 6
1.2 Content of Delivery ................................................................................................. 6
1.3 Description ............................................................................................................. 6
1.4 Installation ............................................................................................................. 7
1.5 Overvoltage Protection ........................................................................................... 9
1.6 Technical Specifications ........................................................................................ 10
1.6.1 Electrical Measurement ......................................................................................... 10
1.7 Sensor .................................................................................................................. 11
2. Operating 14
2.1 Operating the device directly ................................................................................ 15
2.2 Control Panel ........................................................................................................ 15
2.3 Maintenance ........................................................................................................ 17
2.3.1 Maintenance Page ................................................................................................. 19
2.3.2 Configuration Management .................................................................................. 20
2.3.3 Bootloader Activation ............................................................................................ 21
3. Configuration 24
3.1 Power Ports .......................................................................................................... 25
3.1.1 Watchdog ............................................................................................................... 26
3.2 Ethernet ............................................................................................................... 27
3.2.1 IP Address ............................................................................................................... 28
3.2.2 IP ACL ..................................................................................................................... 29
3.2.3 HTTP ....................................................................................................................... 30
3.3 Protocols .............................................................................................................. 31
3.3.1 Console ................................................................................................................... 32
3.3.2 Syslog ..................................................................................................................... 34
3.3.3 SNMP ...................................................................................................................... 34
3.3.4 Radius ..................................................................................................................... 36
3.3.5 Modbus TCP ........................................................................................................... 37
3.4 Clock ..................................................................................................................... 37
3.4.1 NTP ......................................................................................................................... 38
3.4.2 Timer ...................................................................................................................... 39
3.4.3 Timer Configuration ............................................................................................... 39
3.5 Sensors ................................................................................................................. 46
3.5.1 Port Switching ........................................................................................................ 47
3.6 E-Mail ................................................................................................................... 49
3.7 Front Panel ........................................................................................................... 50
4. Specifications 51

4
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Table of contents
4.1 IP ACL ................................................................................................................... 52
4.2 IPv6 ...................................................................................................................... 52
4.3 Radius ................................................................................................................... 53
4.4 Automated Access ................................................................................................ 53
4.5 SNMP ................................................................................................................... 54
4.5.1 Device MIB 8021 .................................................................................................... 56
4.5.2 Device MIB 8025 .................................................................................................... 58
4.6 SSL ........................................................................................................................ 61
4.7 Console ................................................................................................................. 63
4.7.1 SSH ......................................................................................................................... 66
4.7.2 Push Messages ....................................................................................................... 67
4.7.3 Console Cmd 8021 ................................................................................................. 68
4.7.4 Console Cmd 8025 ................................................................................................. 76
4.7.5 Serial Console ......................................................................................................... 85
4.8 Modbus TCP ......................................................................................................... 86
4.9 Messages .............................................................................................................. 90
5. Support 92
5.1 Data Security ........................................................................................................ 93
5.2 Contact ................................................................................................................. 93
5.3 Declaration of Conformity ..................................................................................... 94
5.4 FAQ ...................................................................................................................... 94
96
Index

Device Description

6
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Device Description
1 Device Description
1.1 Security Advice
·The device must be installed only by qualified personnel according to the following
installation and operating instructions. The manufacturer does not accept responsib-
ility in case of improper use of the device and particularly any use of equipment that
may cause personal injury or material damage.
·The device contains no user-maintainable parts. All maintenance has to be per-
formed by factory trained service personnel.
·This device contains potentially hazardous voltages and should not be opened or
disassembled.
·The device can be connected only to 100 - 240 V AC (50 - 60 Hz) power supply
sockets.
·The used power cords, plugs and sockets have to be in good condition. Always con-
nect the device to properly grounded power sockets.
·To disconnect the appliance quickly and safely from the power supply, the outlet
supplying the appliance with power must be easily accessible.
·This equipment is designed for indoor use only. It must not be used in condensing or
excessively hot environments.
·Please also observe the other instructions in the instructions for proper handling of
the device.
·Because of safety and approval issues it is not allowed to modify the device without
our permission.
·The device is NOT a toy. It has to be used or stored out of range of children.
·Care about packaging material. Plastics has to be stored out of range of children.
Please recycle the packaging materials.
·In case of further questions, about installation, operation or usage of the device,
which are not clear after reading the manual, please do not hesitate to ask our sup-
port team.
·Please, never leave connected equipment unattended, that can cause damage.
·Only connect electrical devices that do not have a limited duty cycle. This means that
in the event of a fault, all connected electrical devices must be able to withstand con-
tinuous activation without causing damage.
1.2 Content of Delivery
The package includes:
·Expert Power Control 8021/8025
·1 x Power Supply cable (IEC C19, max. 16 A)
·Quick Start Guide
1.3 Description
The Expert Power Control 8021/8025 can switch 4 load outputs (IEC C13, max.
10A), that are fed from a mains connection (IEC C20, max. 16A) . The device has the
following features:

7
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Device Description
·Switching of 4load outputs.
·Energy measurement of the mains connection and measurement of voltage, current,
active power, reactive power, apparent power, frequency, phase angle and power
factor.
·2 energy counters, one counter counts continuously, the other counter can be reset
·Residual current measurement type A
·Connection for 2 optional sensors for environmental monitoring (temperature, humid-
ity and air pressure)
·A four-digit 7-segment LED display (for current display or data of external sensors).
·Second four-digit 7-segment LED display (for Revision 2 model)
·Energy measurement and energy counter for each of the 4load outputs and meas-
urement of voltage, current, active power, reactive power, apparent power, fre-
quency, phase angle, power factor per output (see Feature Matrix).
·Separate overvoltage protection of the mains connection.
·Console commands via SSH, Telnet and serial interface
·SSH support with public key and passwords
·Individually parameterisable switch-on delay of all outputs
·Programmable timetables and turn-on/turn-off sequences
·Individually adjustable watchdog for each output, which switches depending on ac-
cessibility (network ping)
·Dual TCP/IP stack with IPv4 and IPv6 support (IPv6-ready)
·Control and monitoring of the device via Ethernet with an integrated web server with
SSL encryption (TLS 1.1, 1.2, 1.3)
·Control and configuration with CGI parameters and JSON messages via HTTP
(REST API)
·SNMP (v1, v2c and v3, traps)
·Modbus TCP support
·Radius support
·Generation of messages (e-mail, syslog and SNMP traps) and switching of relays
depending on sensor measurement limits
·Firmware update during operation via Ethernet possible
·Encrypted e-mails (SSL, STARTTLS)
·Access protection through IP access control
·Low own consumption
·Developed and produced in Germany
Feature Matrix
Product
Ports
Single Port Measurement
GSM
Connector
8021-1
4
IEC
8021-2
4
IEC-Lock
8021-3
4
CEE 7-3
8025-1
4
x
IEC
8025-2
4
x
IEC-Lock
8025-3
4
x
CEE 7-3
1.4 Installation
The Expert Power Control 8021/8025 comes in two variants. Once with the original
display (revision 1).

8
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Device Description
1. 4 plain text displays (on/off) for the state of the outputs
2. LED indicator for Over-Voltage Protection (red - surge protection is inactive)
3. Status LED
4. Current power consumption (7-segment display)
In the Revision 2 model variant with new display
1. 2x 7-segment displays (partly with unit LEDs)
2. 4 plain text indicators (on/off) for the status of the outputs.
3. Status LED
4. LED indicator for Over-Voltage Protection (green - Over-Voltage protection active /
red - inactive)
5. Select button
6. Ok button
7. Ethernet connector (RJ45)
8. External sensor connectors (RJ45)
9. RS232 connector
Expert Power Control 8021/8025 - 1

9
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Device Description
10. Mains supply (IEC C20, max.16 A)
11. 4 x Load outputs (IEC C13, max. 16 A)
Expert Power Control 8021/8025 - 2
12. Mains supply (IEC C20, max.16 A)
13. 4 x Load outputs (IEC C13, max. 16 A, IEC-Lock)
Start-up the device
·Connect the power cord (IEC C19, max. 16A) to the mains supply. The cable con-
nectors are secured as regards their type against unintentional loosening. They must
be inserted up to the stop, otherwise there is no secure connection. The plug must
not wobble in the socket, or there is no tight connection.
·Plug the network cable into the Ethernet socket (RJ45).
·If required, setup a serial connection to the RS232 port.
·Insert the optional external sensors into the sensor connectors.
·Connect the consumers with the load outputs (IEC C13, max. 10A).
1.5 Overvoltage Protection
The device contains an overvoltage protection. The protection is based on input side
varistors with thermal fuse between phase (L) and neutral (N) to protect the internal
electronics and power ports with failure detection (permanently triggered thermal fuse).
The state of the protection is indicated on the front panel by a flash.
·An invisible flash means that the protection is active, a red flash symbolizes that the
overvoltage protection fails. (Revision 1 device)
·An green flash means that the protection is active, a red flash symbolizes that the
overvoltage protection fails. (Revision 2 device)
In addition, the status of the overvoltage protection can be seen on the Webpage
(HTTP) and acquired with SNMP. Each surge protection module is designed that it can
derive a practical unlimited number of voltage pulses in normal installation environ-
ments. In an environment with many energy rich surge pulses it can result in perman-
ent loss of function due to aging of the overvoltage protection element.

10
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Device Description
Recovering of the overvoltage protection function can only be performed by the
manufacturer of the device. In the normal case, the device will continue to work even
after the failure of the protective function.
A signaling via E-Mail, Syslog or SNMP trap occurs only once during operation, ex-
actly at the moment in which the protection fails. In addition, at the start up of the
device a message is generated, when the overvoltage protection is not active.
1.6 Technical Specifications
Interfaces
1 x Mains supply (IEC C20, max.16 A)
1 x Ethernet port (RJ45)
1 x Serial connector (D-SUB, RS232)
2 x RJ45 for external sensor
Load Outputs
8021-1 / 8025-1
4 x Load Outputs (IEC C13, max. 10 A)
Load Outputs
8021-2 / 8025-2
4 x Load Outputs (IEC C13 Lock, max. 10 A)
Network connectivity
10/100 MBit/s 10baseT Ethernet
Protocols
TCP/IP, HTTP/HTTPS, SNMP v1/v2c/v3,
SNMP traps, Syslog, E-Mail (SMTP)
Power Supply
internal power supply (100-240 V AC / -15% /
+10%, 50-60 hz)
Overvoltage Protection: 20mm / 250J varistor disk (300V AC)
·single peak current for 20/80us pulse: 10000 A
·max. clamping voltage 20/80us pulse, Ipk = 100 A: 775 V
Environment
·Operating temperature
·Storage temperature
·Humidity
0°C - 50 °C
-20°C - 70 °C
0% - 95% (non-condensing)
Case
powder coated, galvanized steel sheet
Measurements
19" (inches), 1 Rack Unit, (Depth 195 mm)
Weight
approx. 2.9 kg (8021)
approx. 3.0 kg (8025)
1.6.1 Electrical Measurement
typical fault tolerances for Ta=25°C, I=1Arms...16Arms, Un=90Vrms...265Vrms

11
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Device Description
Electrical Measurement Specification
Category
Range
Unit
Resolu-
tion
Inaccuracy
(typical)
Voltage
90-265
V
0.01
< 1%
Current
0 - 16
A
0.001
< 1.5%
Frequency
45-65
Hz
0.01
< 0.03%
Phase
-180 - +180
°
0.1
< 1%
Active power
0 - 4000
W
1
< 1.5%
Reactive power
0 - 4000
Var
1
< 1.5%
Apparent power
0 - 4000
VA
1
< 1.5%
Power factor
0 - 1
-
0.01
< 3%
Energy Counter
Active Energy
(total)
9.999.999,999
kWh
0.001
< 1.5%
Active Energy
(temporary)
9.999.999,999
kWh
0.001
< 1.5%
1.7 Sensor
Two external sensors can be connected to the Expert Power Control 8021/8025.
The following sensors are currently available
Humidity/Temperature Sensor 7102 (End-of-Life)
Cable length
Connector
RJ45
temperature range
-20°C to +80°C, ±0,5°C (maximum) and ±0,3°C (typical)
air humidity range
(non-condensing))
0-100%, ±3% (maximum) and ±2% (typical)

12
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Device Description
Product Name
7101
7104-1
7105-1
7106-1
Calibrated
Sensor
-
7104-2
7105-2
7106-2
Cable length
Connector
RJ45
RJ45
RJ45
RJ45
temperature range
-20°C to +80°C at
±2°C (maximum)
and ±1°C (typical)
-20°C to +80°C at
±2°C (maximum)
and ±1°C (typical)
-20°C to +80°C at
±2°C (maximum)
and ±1°C (typical)
-20°C to +80°C at
±2°C (maximum)
and ±1°C (typical)
air humidity range
(non-condensing)
-
-
0-100%, ±3%
(maximum) and
±2% (typical)
0-100%, ±3%
(maximum) and
±2% (typical)
air pressure range
(full)
-
-
-
± 1 hPa (typical)
at 300 ... 1100
hPa, 0 ... +40 °C
air pressure range
(ext)
-
-
-
± 1.7 hPa (typical)
at 300 ... 1100
hPa, -20 ... 0 °C
Protection
IP68
-
-
-
Product Name
7201
7202
Cable length
-
-
Connector
RJ45
RJ45
temperature range
-20°C to +80°C at ±2°C (max-
imum) and ±1°C (typical)
-20°C to +80°C at ±2°C (max-
imum) and ±1°C (typical)
air humidity range
(non-condensing)
-
0-100%, ±3% (maximum) and
±2% (typical)

13
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Device Description
The sensors are automatically detected after connect. This is indicated by the green
LED on the sensor port that is lit permanently. The sensor values are displayed at
the "Control Panel" web page:
A click on the link in the "Name" column opens the display of the Min and Max values.
The values in a column can be reset using the "Reset" button. The "Reset" button in
the name column deletes all stored Min and Max values.

Operating

15
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Operating
2 Operating
2.1 Operating the device directly
Port Switching
The current status of the output is indicated by the color of the LED. Red indicates that
the output is off, green shows that the output is on. On the device are the buttons "se-
lect" and "ok". If you press "select", you can select the following modes one by one:
1. At first, all LEDs flash green. If you press the "Ok" button for 4 seconds, all ports
are switched on. (If all ports are switched on, this is skipped).
2. After that, all LEDs flash red. If you hold the "Ok" button for 4 seconds, all ports will
be switched off. (If all ports are switched off, this will be skipped).
3. If you press "Select" again, the LED for the first output starts blinking, i.e. the output
is selected. Press "Select" again to select the next output. If you keep the "Ok" but-
ton pressed for one second, the state of the selected output will be toggled.
You can switch off in the front panel configuration that all ports with the modes
1 and 2 can be switched by pushbutton.
Display Information
If no port is selected manually, repeatedly pressing the "ok" button will show the IP-ad-
dress and the values of the external sensors on the display.
Status-LED
The Status LED shows the different states of the device:
·red: The device is not connected to the Ethernet.
·orange: The device is connected to the Ethernet and waits for data from the DHCP
server.
·green: The device is connected to the Ethernet and the TCP/IP settings are alloc-
ated.
·periodic blinking: The device is in Bootloader mode.
2.2 Control Panel
Access the web interface: http://"IP-address" and log-in.
50

16
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Operating
The web page provides an overview of the switching state, energy measurement val-
ues, as well as the external sensors, provided that they are connected. The number of
ports shown depends on the model. When a single port is clicked at the Expert Power
Control 8021/8025, a panel with buttons to control a single port appear:
The Port icon is green when the relay is closed, or red in the open state. An additional
small clock icon indicates that a timer is active. Timer can be activated by delay, reset
or batch mode.
An activated Watchdog is represented by an eye icon. An "X" means, that the address
that should be observed, could not be resolved. Two circular arrows show a booting
status.
In addition to the panel, the Expert Power Control 8025 shows the measured values
of the selected port:

17
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Operating
The ports can be switched manually with the "On" and "Off" buttons. If the port is
turned on, it can be turned off by pressing the "Reset" button, until after a delay it turns
itself on again. The delay time is determined by the parameter Reset Duration, which is
described in the chapter "Configuration - Power Ports ". The "Close" button dis-
solves the panel again.
Batchmode
Each individual port can be set for a selectable period of time to the state "switch on"
or "switch off". After the selected time they are automatically switched to the second
preselected state.
Optionally the device can be switched via a Perl script or external tools like wget. More
information is available on our support wiki at www.gude.info/wiki.
2.3 Maintenance
The actual device generation with IPv6 and SSL allows all maintenance functions in
the web interface to be carried out on the Maintenance Page .
Maintenance in the web interface
The following functions are available from the maintenance web page:
·Firmware Update
·Change the SSL certificate
·Load and save the configuration
·Restart the device
·Factory Reset
·Jump into the Bootloader
·Delete the DNS cache
Upload Firmware, Certificate or Configuration
On the Maintenance Page , select the required file with "Browse .." in the sections
"Firmware Update", "SSL Certificate Upload" or "Config Import File Upload" and press
"Upload". The file is now transferred to the update area of the device and the contents
are checked. Only now, pressing the "Apply" button will permanently update the data,
or abort with "Cancel".
Only one upload function can be initiated with a reboot, eg. you cannot transmit
firmware and configuration at the same time.
25
19
19

18
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Operating
If after a firmware update, the web page is not displayed correctly anymore, this
may be related to the interaction of Javascript with an outdated browser cache. If a
Ctrl-F5 does not help, it is recommended that you manually delete the cache in the
browser options. Alternatively, you can test start the browser in "private mode".
During a firmware update, old data formats are sometimes converted to new struc-
tures. If an older firmware is newly installed, the configuration data and the energy
meters may be lost! If the device then does not run correctly, please restore the factory
settings (e.g. from the Maintenance Page ).
Actions in Bootloader mode
If the web interface of the device is no longer accessible, the device can be put into
Bootloader mode (see chapter Bootloader activation ). The following functions can
be executed using the GBL_Conf.exe application:
·Set IPv4 address, net-mask and gateway
·Turn HTTP password on and off
·Turn IP-ACL on and off
·Factory Reset
·Jump into the bootloader (can be switched on and off)
·Restart the device
For devices with relays, entering or exiting the bootloader mode does not change
the state of the relays as long as the operating voltage is maintained.
The GBL_Conf.exe program is available free of charge on our website www.gude.info
and can also be found on the enclosed CD-ROM.
Interface GBL_Conf
To check the network settings with GBL_Conf.exe, start the program and choose "All
Devices" in the "Search" menu. From the list select the appropriate device. The lower
part of the left half of the window now shows the current network settings of the device.
If the IP address is displayed with the default settings (192.168.0.2), either no DHCP
server is present on the network, or there could be no free IP address assigned to it.
19
21

19
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Operating
·Activate the Bootloader Mode (see Chapter Bootloader Mode) and choose in menu
"Search" the item "Bootloader-Mode Devices only"
·Enter the desired settings in the edit window and save them with "Save Config".
·Deactivate the boot loader mode for the changes to take effect. Select again "All
Devices" in the "Search" menu of GBL_Conf.exe.
The new network configuration is now displayed.
Factory Reset
The device can be reset to the factory default via the web interface from the Mainten-
ance Page or from the Bootloader mode (see chapter Bootloader activation ). All
TCP/IP settings are reset in this operation.
If a unit is set to factory defaults, an uploaded certificate or updated firmware will
be preserved.
2.3.1 Maintenance Page
This section provides access to important functions such as Firmware Update or Re-
start Device. It is advisable to set an HTTP password for this reason.
Firmware Update: Start a firmware update.
SSL Certificate Upload: Saves your own SSL certificate. See chapter "SSL " for the
generation of a certificate in the right format.
Config Import File Upload: Loads a new configuration from a text file. To apply the new
configuration, a "Restart Device" must be executed after the "Upload".
Config File Export: Saves the current configuration in a text file.
19 21
61

20
Expert Power Control 8021/8025 © 2021 GUDE Systems GmbH
Operating
Saving the configuration should only be carried out in an SSL connection, since it
contains sensitive password information (even if it is encrypted or hashed).
Restart Device: Restarts the device without changing the status of the relays.
Some functions such as a firmware update or changing of the IP-address and
HTTP settings require a restart of the device. A jump to the boot loader or a restart of
the device lead by no means to a change of the relay states.
Restore Fab Settings and Restart Device: Performs a restart and resets the device to
factory default .
Enter Bootloader Mode: Jumps into bootloader mode, where additional settings can be
made with GBL_Conf.exe.
Flush DNS Cache: All entries in the DNS cache are discarded and address resolutions
are requested again.
2.3.2 Configuration Management
The device configuration can be saved and restored in the maintenance area .
The "Config File Export" function can be used to save the current configuration as a
text file. The syntax used in the configuration file corresponds to the commands of the
Telnet console. If the configuration of a device is to be restored from a text file, load
the file with "Upload" and restart the device with "Restart Device".
Saving the configuration should only be carried out in an SSL connection, since it
contains sensitive password information (even if it is encrypted or hashed). For the
same reasons, it is advisable to carefully handle the generated configuration files when
archiving.
Editing the configuration file
It is possible to customize a saved configuration file with a text editor for your own
needs. For example, one scenario would be to use a script language to automate the
creation of many customized versions of a configuration, then equip a large number of
devices with an individualized configuration. Also Upload and restart with CGI com-
mands can be done in scripting languages. With use of the comment sign "#" you can
quickly hide single commands or add personal notes.
If you modify a configuration file manually, it is not always clear which limits are allowed
for parameters. After uploading and restarting, commands with invalid parameters are
ignored. Therefore, the generated configuration includes comments describing the
boundaries of the parameters. Where "range:" refers to a numeric value, and "len:" to a
text parameter. E.g:
email auth set 0 #range: 0..2
22
19
This manual suits for next models
7
Table of contents
Other Gude Switch manuals

Gude
Gude 8801 User manual

Gude
Gude Expert Power Control 8032-1 User manual

Gude
Gude Expert net control 2i2o User manual

Gude
Gude Expert Power Control 8221 Series User manual

Gude
Gude Expert USB User manual

Gude
Gude Expert Power Control 1000 User manual

Gude
Gude Expert Power Control NET 8x 8211 User manual

Gude
Gude Expert Power Control NET 24x User manual

Gude
Gude Expert Bypass Switch 8701 Series User manual