GW Sprinkler Loflow K15 Series User manual

GW LOFLOW K-15 TYPE C, O & S
GW SPRINKLER A/S
Kastanievej 15, DK 5620-Glamsbjerg, Denmark
TEL: +45 64722055 FAX: +45 64722255
Email: sales.dep@gwspinkler.com
Data sheet also available at www.gwsprinkler.com
DATA SHEET No: GW SN030 1001 A
Data Sheet:
Page:
Issue / Date:
GW Loflow K-15 Type C, O
& S
1 of 3
9th July 2007
The right is reserved to vary or modify any specifications without prior notice
Maritime Installation of LOFLOW K15 Sprinklers:
Loflow K15 Sprinklers must be installed in the pendant position. Systems must be designed and installed in
accordance with SOLAS Regulation II-2/12, with the exception of water densities less than 5 litres/min/m2.
Sprinkler systems must be hydraulically calculated with the Hazen-Williams formula, to provide the
recommended minimum water pressure on the last nozzle to operate in the system. SOLAS and NFPA 750
require the systems to have standing charge of fresh water.
Installation and Maintenance:
Loflow K15 Sprinklers have a small orifice when compared with traditional sprinklers. To minimise the risk of
blocked sprinkler nozzles during operation, the sprinkler pipes must be flushed with fresh clean water through
each branch pipe end to avoid dirt in pipes before the sprinklers are installed.
Caution:
After the pipes have been flushed and the pipe plug removed, the internal pipe threads must be cleaned for any
sealing materials, before the sprinklers are installed.
The sprinklers must always be installed in the pendant position using the special purpose spanner from GW
Sprinkler A/S.
Table 1 Sprinkler Pipes and Components:
System Sprinkler material Pipe system material Extinguishing agent
Brass natural
Brass – chrome Galvanized steel pipes
Cu-alloys pipes
Plastic (See note 1)
Fresh water
Galvanised steel pipes
Brass/Cu-alloy pipes
SS303, 304 pipes
Fresh water
Brass – ENP CuNi pipes
SS316, SMO254 etc.
Plastic pipes (see note
1)
Fresh & Seawater
Wet Pipe
Systems
Stainless steel
AISI316
CuNi pipes
SS316, SMO254 etc.
Plastic pipes (see note
1)
Fresh & Seawater
Brass natural
Brass chrome Cu-alloys pipes Fresh water
Brass – ENP Brass/Cu-alloy pipes
SS303, 304 pipes Fresh & Seawater
Dry Pipe
Systems Stainless steel
AISI316 CuNi pipes
Stainless steel pipes Fresh & Seawater
GW LOFLOW K-15 TYPE C, O & S
GW SPRINKLER A/S
Kastanievej 15, DK 5620-Glamsbjerg, Denmark
TEL: +45 64722055 FAX: +45 64722255
Email: sales.dep@gwspinkler.com
Data sheet also available at www.gwsprinkler.com
DATA SHEET No: GW SN030 1001 A
Data Sheet:
Page:
Issue / Date:
GW Loflow K-15 Type C, O
& S
2 of 3
9th July 2007
The right is reserved to vary or modify any specifications without prior notice
Pipe material Component materials Extinguishing Agent
Galv. steel Cast/Ductile iron Fresh Water
Galv.steel
Cu-alloys Brass
Coated iron and steel,
Naval brass
Plastic (Not USCG Installations)
Fresh Water
CuNi
SS316 Coated iron and steel,
Aluminium bronze, SS316,
Brass with ENP/Nedox coating
Fresh & Sea Water
Plastic Cast/ductile iron,
Brass and SS303 etc.
CuNi, SS316, SMO254
Fresh & Sea Water
1) Sprinkler pipes must correspond with hydraulic calculations, internal pressures and authority demands and
recommendations.
Sprinkler material must correspond with materials of pipes and extinguishant, see table 1 above.
2) The materials of sprinkler system components such as valves, flow switches, pumps etc. must correspond
with authority demands, water flow, system pressure, pipe materials and extinguishing agent.
See also Loflow Sprinkler Installation Guidelines Ref no.: 715 for Maritime Installations.
Galvanised Pipes and Fittings:
NFPA 750 does not allow the use of galvanised pipes and fittings downstream the system strainer.
USCG requires a strainer downstream of all fittings that are of materials other than these shown in NFPA
(1996), table 2-3.3.1.
Table 2 Components Material:
Note 1: Plastic pipes are not to be used in maritime installations or ordinary hazard Installations.
GW LOFLOW K-15 TYPE C, O & S
GW SPRINKLER A/S
Kastanievej 15, DK 5620-Glamsbjerg, Denmark
TEL: +45 64722055 FAX: +45 64722255
Email: sales.dep@gwspinkler.com
Data sheet also available at www.gwsprinkler.com
DATA SHEET No: GW SN030 1001 A
Data Sheet:
Page:
Issue / Date:
GW Loflow K-15 Type C, O
& S
3 of 3
9th July 2007
The right is reserved to vary or modify any specifications without prior notice
Table 3: Applications as Classified in SOLAS Regulation II-2/26.2.2:
LOFLOW Sprinkler TypeOccupancy Classification Parameters K15-O K15-C K15-S
(1) Control Stations Sprinkler Spacing:
Distance to Wall:
Water Pressure:
Locations:
Ceiling Height:
max. 3.5m
max. 1.5m
min. 6 bar
all
max. 5m
max. 12m2
max. 2.0m
min. 6 bar
small rooms*
max. 2.5m
(2) Stairways Sprinkler Spacing:
Distance to Wall:
Water Pressure
Stairways Width:
Ceiling Height:
max. 3.5m
max. 1.5m
min. 6 bar
>1.6m
max. 5m
max. 3.5m
max. 0.8m
min. 6 bar
< 1.6m
max. 2.5m
(3) Corridors Sprinkler Spacing:
Distance to Wall:
Water Pressure:
Corridor Width:
Ceiling Height:
max. 3.5m
max. 1.5m
min. 6 bar
> 1.6m
max. 5m
max. 3.5m
max. 0.8m
min. 6 bar
< 1.6m
max. 2.5m
(6) Accommodations Spaces
minor fire risk Sprinkler Spacing:
Distance to Wall:
Water Pressure :
Locations:
Ceiling Height:
max. 3.5m
max. 1.5m
min. 6 bar
all
max. 5m
max. 12m2
max. 2.0m
min. 6 bar
small rooms*
max. 2.5m
(7) Accommodation spaces
moderate fire risk Sprinkler Spacing:
Distance to Wall:
Water Pressure:
Locations:
Ceiling Height:
max. 3.5m
max. 1.5m
min. 6 bar
all
max. 5m
max. 12m2
max. 2.0m
min. 6 bar
small rooms*
max. 2.5m
max. 3.0m
max. 1.5m
min. 6 bar
all
max. 2.5m
(8) Accommodation spaces
greater fire risk Sprinkler Spacing:
Distance to Wall:
Water Pressure
Locations:
Ceiling Height:
max. 3.5m
max. 1.5m
min. 6 bar
all
max. 5m
max. 12m2
max. 2.0m
min. 6 bar
small rooms*
max. 2.5m
max. 3.0m
max. 1.5m
min. 6 bar
all
max. 2.5m
(9) Sanitary & Similar Spaces Sprinkler Spacing:
Distance to Wall:
Water Pressure
Locations:
Ceiling Height:
max. 3.5m
max. 1.5m
min. 6 bar
all
max. 5m
max. 12m2
max. 2.0m
min. 6 bar
small rooms*
max. 2.5m
(13) Storerooms
Workshop, Pantries, Retail
shops, Stores and Laundries,
Galleys and rooms where
goods are piled or shelved
Sprinkler Spacing:
Distance to Wall:
Water Pressure
Locations:
Ceiling Height:
max. 3.0m
max. 1.5m
min. 6 bar
all
max. 2.5m
(14) Storage areas, shops and
other spaces where also
flammable liquids for retail
sales are stored in small
containers
Sprinkler Spacing:
Distance to Wall:
Water Pressure
Locations:
Ceiling Height:
max. 3.0m
max. 1.5m
min. 6 bar
all
max. 2.5m
*Sprinklers to be installed symmetrically
max. 4m x 3m rooms, min. 6 bar pressure Type: O = Open Space
C = Cabins & Corridors
S = Storage Rooms

This manual suits for next models

3

Other GW Sprinkler Irrigation System manuals

GW Sprinkler M5 User manual

GW Sprinkler

GW Sprinkler M5 User manual

GW Sprinkler SSP User manual

GW Sprinkler

GW Sprinkler SSP User manual

Popular Irrigation System manuals by other brands

Gardena T 200 operating instructions

Gardena

Gardena T 200 operating instructions

nvent RAYCHEM XL-Trace Step-by-step design guide

nvent

nvent RAYCHEM XL-Trace Step-by-step design guide

Viking QUICK RESPONSE ELO VK377 Technical data

Viking

Viking QUICK RESPONSE ELO VK377 Technical data

Viking FREEDOM VK486 Technical data

Viking

Viking FREEDOM VK486 Technical data

Tyco WS TY3388 operating instructions

Tyco

Tyco WS TY3388 operating instructions

Johnson Controls tyco TFP700 manual

Johnson Controls

Johnson Controls tyco TFP700 manual

Autopot easy2grow 16 Set-up guidelines

Autopot

Autopot easy2grow 16 Set-up guidelines

Elgo AS2 installation guide

Elgo

Elgo AS2 installation guide

Eden 94122-EDAMZ quick start guide

Eden

Eden 94122-EDAMZ quick start guide

Tyco TY-FRB Series quick start guide

Tyco

Tyco TY-FRB Series quick start guide

Reliable F1 LO manual

Reliable

Reliable F1 LO manual

Tyco DS-1 Series quick start guide

Tyco

Tyco DS-1 Series quick start guide

Reliable LT56 Series manual

Reliable

Reliable LT56 Series manual

Johnson Controls tyco TY-L Series manual

Johnson Controls

Johnson Controls tyco TY-L Series manual

Victaulic VicFlex I-VICFLEX.AQC-U installation instructions

Victaulic

Victaulic VicFlex I-VICFLEX.AQC-U installation instructions

Philips sonicare AirFloss Ultra user manual

Philips

Philips sonicare AirFloss Ultra user manual

Rain Bird Falcon 6504 Installation and operating guide

Rain Bird

Rain Bird Falcon 6504 Installation and operating guide

Hozelock 2550 How to use

Hozelock

Hozelock 2550 How to use

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.