Habitat HTE-01 User manual

Operation Manual
Smarter Control Solutions.

i
About This Manual
This manual uses special attention icons to alert the reader of important
safety concerns, information important to reliable operation of the controls
or helpful installation/setup information.
Safety: Indicates a condition which may cause severe personal
injury, death, or major property damage.
Important Information: Indicates information which requires
special attention for correct operation of the control.
Your Benet: Indicates helpful installation or setup information.
For installation and instructions, refer to the
Installation & Pairing Manual.
For programming instructions, refer to the
Programming Guide.
Documentation

ii
Habitat Technologies
330 East 38th Street, Suite 530
New York, NY 10016-0444
Customer Service
Toll Free: 1-800-717-1682
Web Site: www.habitattechnologies.com
Manual Table of Contents
About This Manual i - ii
System Overview 1-2
Home Screen Display & Controls 3-7
HTE-01 Thermostat Operation 8-14
- Changing Operating Mode 8
- Changing Fan Speed 9
- Alarm Operation 10
- Compressor Short Cycle Protection; Cooling Fan Delay 11
- Frost Mode; Temperature Units 11
- Schedule Setup 12-14
Power Operation 15
Model Specications 16
Designed and Engineered in New York
U.S. registered Trademark, Patents pending
Copyright 2020, All Rights Reserved.
Thermostat
HTE-01
Module
HTM-01

1
System Overview
A single Model HTE-01 thermostat can control up to eight air
conditioning units equipped with Model HTM-01 base modules.
The range between the thermostat and the base modules can be
up to approximately 50 feet through standard building materials.
PTAC - Packaged Terminal AC
WSHP - Water-Source Heat Pump
HWSHP - Hybrid Water-Source Heat Pump
FCU - Fan Coil / Mini-Split Unit
UNI - Unitary AC / Furnace
The The HTE-01 thermostat and
HTM-01 base module are paired
when supplied as a set from
the factory. If base modules are
added or if pairing is required in
the eld, see the Installation &
Pairing Manual for the correct
procedure.

2
For heat pump installations, dip switch #6 must be set to match the
appliance changeover valve. Refer to appliance manufacturers sys-
tem specications for required setting.
- ON = “B” – Cooling is default, switches over to Heat
- OFF = “O” – Heating is default, switches over to Cool
If more than one appliance type (dip switch 1-5) is selected,
error code will be displayed.
System Overview - Dip Switch Congurations
1 – PTAC (Packaged Terminal Unit)
Factory Default
2 – FCU
(Fan Coil Unit / Mini-Split)
3 – WSHP
(Water-Source Heat Pump)
4 – HWSHP
(Hybrid Water Source Heat Pump)
5 – UNTY
(Unitary AC/Furnace)
6 – O/B Terminal Selection
(Heat Pump Only)

3
Home Screen
1
2
3
4
5
6
7
9
10
11
12
13
14
8

4
1
Pairing status indicator:
Connected
Not connected
8Time display1
2
WIFI status indicator (only shown
when WIFI module is used)
Connected
Not Connected
9
Override status indicator1:
Override – Temporary Override
Perm. Override – Permanent
Override
3
Thermostat Battery power indicator
status, only shown when on battery
power used.
Full Half Low Replace
10
Schedule running indicator:
Schedule – Schedule running1
(Blank) No Schedule
4System type 11 Set point
5Room temperature 12 Celsius or Fahrenheit units
6Mode status 13 Emergency heat indication
7Additional system type text 14 Fan speed indication
1 - Schedule must be activated for the time & schedule status to be displayed.
See the Habitat programming guide for information on setting up a schedule.

5
Model HTE-01 Thermostat
1
2
3
4
5
Front
View
Bottom
View

6
LCD Display – See preceding pages for detailed descriptions of the
display icons.
– Increase or Decrease the target temperature set point.
Changing the target set point:
• Press the or button while in Auto, Heat or Cool Modes.
• If a schedule is programmed, “Override” is displayed below the
time indicating that the current target setpoint will be maintained
until the:
- Next schedule period
- Set point is changed to the scheduled value
- Mode button is held for 3 seconds, displaying “Schedule”,
“Perm. Override”
- To change the temperature units between °F and °C, simultaneously
press the and buttons briey.
Mode – Cycle through Operation modes:
Fan – Cycle through desired Fan Speeds.
Manual Reset – Reboots the thermostat system only.
To save energy, the display will turn o after a period of inactivity.
Before making changes, press any button to activate the display,
illuminating the screen.
5
1
2
3
4

7
Model HTM-01 Base Module
Appliance Harness Connector
Water Leak Sensor Connector
Pairing Button
Module Status LED
Module Wi-Fi Connector (remove protective label)
1
2
3
4
5
1
23
4
5

8
HTE-01 Thermostat Operation
To save energy, the display will turn o after a period of inactivity.
Before making changes, press any button to activate the display,
illuminating the screen.
Changing Operating Mode:
• Press the Mode button to change between:
Thermostat will not generate heating or cooling
demands.
If the equipment supports automatic changeover, the
thermostat will switch between heating and cooling
based on the room temperature.
Thermostat will maintain the target set point
temperature with cooling.
Thermostat will maintain the target set point
temperature with heating.
Thermostat will operate the fan for circulation.

9
Changing Fan Speed:
• Press the Fan button to scroll through fan speed options as shown
in the following chart.
• When a schedule is running, the default fan speed for PTAC, WSHP,
HWSHP or FCU, while heating or cooling is “AUTO”
• If the Thermostat is in Fan Only mode, the default fan speed is “LO”
System Type Mode Fan Sequence
PTAC (Packaged Terminal AC)
WSHP (Water-Source Heat Pump)
HWSHP (Hybrid Water-Source
Heat Pump)
Cool
Heat
Auto
Fan
Only
FCU (Fan Coil Unit / Mini-Split)
Cool
Heat
Auto
Fan
Only
UNI (Unitary Furnace / AC)
Cool
Heat
Auto

10
Alarm Operation:
• When any base module detects water
leakage, it will be reported to the thermostat
which will display the following message:
• Note: The number shown after
indicates the base module which has
detected a water leak from the Water Leak
Sensor Cable.
• To reset the alarm, press all buttons
( , , Mode and Fan). The
thermostat will re-check the base modules
and, if no leaks are detected, resume normal
operation.
• If alarms from multiple base modules are
reported, only one alarm will be shown
until a button is pushed and the backlight
illuminates. Then, the display will scroll
through the alarms detected.

11
Compressor Short Cycle Delay Protection:
The HTE-01 Thermostat has a built in short cycle delay to protect the
compressor. The Programming Guide describes how to change this delay
from its default value of 5 minutes to as low as 1 minute.
When this function is active, the or will ash but the output will
not turn on.
Cooling Fan Delay:
For PTAC, WSHP or HWSHP systems in mode, the fan will remain
running for 1 minute after the cooling demand is satised.
Frost Mode:
If Emergency Heat is enabled and Frost Protect Setpoint parameter is
active in Administrative Settings, the thermostat will call for heat when
the room temperature falls below the Frost Setpoint (default 45°F/7°C)
unless the system mode is not Fan Only.
Temperature Units:
To change the temperature units between °F and °C, simultaneously
press the and buttons briey.

12
Schedule Setup:
Press & hold “Mode” & “Fan”
until a sound is played (3 seconds),
then release.
The display shows the number
of base modules currently paired.
Press “Mode” to scroll back to the
Schedule Parameter and use the
button to toggle schedule
to “Y”. Press “Fan” to conrm.
When prompted to ,
Use the buttons
to toggle to “y”. Press “Fan”
to continue.

13
Use the buttons
to set the hour that the rst period
begins. Press “Fan” to continue.
Display Description Action when “Fan” pressed
Weekday (MF) or
Weekend (SS)
MF – Set periods*
SS – Set periods*
Same schedule
throughout the week Set periods*
Dierent schedule
each day
MO, TU, WE, TH, FR, SA, SU
– Set periods*
• Choose Schedule Type
* Periods SS, WK, MO, TU, WE, TH, FR, SA, SU are set up in the same way as listed below MF.
• Period Setup
Use buttons to set
minutes for the rst period. Press
“Fan” to continue.

14
Use but-
tons to set the target set
point for Heating. Press
“Fan” to continue.
Set time and tempera-
ture set points for each
desired period.
To disable a period, press
the button until
is displayed.
Up to 6 periods per day
or group of days can be
programmed.
After the 6th period is
programmed, the HTE-01
Thermostat will move to
the next day or group,
depending on the
schedule type.
Once all periods and day
groups have been pro-
grammed, a prompt to
Update will be displayed.
Press “n” to accept the
current schedule or “y”
to make further changes.
Use buttons
to set the target set point
for Cooling. Press “Fan” to
advance to the next period.

15
Power Operation
Battery Installation
Please insert 2 AA Alkaline
batteries (included.) High
performance lithium batteries may
be used and are recommended on
commercial applications.
Hardwired Installation
Battery installation is optional if
Thermostat is hardwired, “R” and
“C” terminal connected to 24 volt
only power.
When the battery icon starts ashing and it shows the
Low or Replace icons, the batteries should be
replaced immediately to prevent system shutdown.

16
Model Specications
Model HTE-01 Thermostat
Temperature Units °C or °F
Operating Temperature 32°F - 99°F / 0°C - 40°C
Indoor Temperature
Measurement Range 32°F - 113°F / 0°C - 45°C
Power Source
Hardwired: 18 to 30 VAC, NEC Class II,
50/60 Hz, 65 mA @ 24 VAC
Battery: 3.0 VDC, (2) AA batteries
Operating Ambient 32°F - 122°F / 0°C - 50°C
Operating Humidity <95% Non-condensing RH
Program 5 + 2 / 7 days
Dimension 3.93” W x 3.93” H x 1.1” D
Frequency ISM Band 915MHZ
Model HTM-01 Module
Load Rating 1 amp per terminal, 1.5 amp maximum all
terminals combined.
Power Source 18 to 30 VAC, NEC Class II, 50/60 Hz
44 mA min./1.7 A max. at 24 VAC
Operating Ambient 32°F - 122°F / 0°C - 50°C
Operating Humidity <95% Non-condensing RH

Model HTE-01 Thermostat
Temperature Units °C or °F
Operating Temperature 32°F - 99°F / 0°C - 40°C
Indoor Temperature
Measurement Range 32°F - 113°F / 0°C - 45°C
Power Source
Hardwired: 18 to 30 VAC, NEC Class II,
50/60 Hz, 65 mA @ 24 VAC
Battery: 3.0 VDC, (2) AA batteries
Operating Ambient 32°F - 122°F / 0°C - 50°C
Operating Humidity <95% Non-condensing RH
Program 5 + 2 / 7 days
Dimension 3.93” W x 3.93” H x 1.1” D
Frequency ISM Band 915MHZ
Model HTM-01 Module
Load Rating 1 amp per terminal, 1.5 amp maximum all
terminals combined.
Power Source 18 to 30 VAC, NEC Class II, 50/60 Hz
44 mA min./1.7 A max. at 24 VAC
Operating Ambient 32°F - 122°F / 0°C - 50°C
Operating Humidity <95% Non-condensing RH
Designed and Engineered in New York.
U.S. Registered Trademark. Patents pending
www.habitattechnologies.com
HC-UM-HTE-01-HTM-01-2020.05 v2