manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Haga
  6. •
  7. Controllers
  8. •
  9. Haga KD48P User manual

Haga KD48P User manual

Exit
¤¤
Proc. -1999...4000
Dev. -1000...1000
Band 0...1000
2. level
3. level
Setting the PID operating properties.
Adjusting input filter.of
SPLo SPHi<
SPHi SPLo>
YLo YHi≤
Yhi Ylo≥
Operating time counter.
It measures the state time in hoursOn
A
B
C
H
F
H
F
G
G
E
E
*=2,3,4,5
*=2,3,4,5
0....6
0....13
D
B
A
D
¤
¤
¤
¤¤¤
Current output: 35(+) and 36 terminals
Voltage output: 36(+) and 37 terminals
C
1. level
Enter Present set-point (read only)
Present control output % (in auto mode read only)
The ordinals of patterns see model
identification
The hysteresis of the ALARM*
in unit of SP
Limits
Symmetric 0...1000
Asymmetric -1000...1000
B. Table [3]=0
The value of the ALARM*
in unit of SP
Limits
G. Table [7]=1
Deleting of the maximum difference (PV-SP) from memory
Set the value from 0 up to 100 and exit with key
The minimal control deviation since the last delete. Read only.
The maximal control deviation since the last delete. Read only.
Under the SP
Above the SP
Exits from configuration mode
Enters in the 2. level at GAin menu item
keys in configuration
when a menu item is
flashing, returns here
pressing the
Gain in %-ban (The attribute: p. Limits 0.0-100.0%)
The proportional band of the control loop in the unit of SP: P=100/p%
For ON-OFF control: GAin=0.0
¤¤ Setting the a ON-OFF controlsymmetrical hysteresis for
Reset time [s]
Limits 0 to 1000 s
Derivative time [s]
Limits 0 to 1000 s
Manual reset to eliminate the PD control (int=0) offset
For PD control int=0
For Asymmetric hysteresis
int=1 GAin=0 dZon=0 ¤¤
Limits : ±1000
Return Returns to the 1. level at menu item SP
Dead zone for valve positioning motor, or symmetrical
hysteresis for ON-OFF control (in SP unit)
Limits:
0...1000
Enters in the 3. level at inP menu item
Types of input. Setting the decimal point and filter.
The offset of PV, in the unit of SP
(For lead resistant compensation and calibration) Limits: ±1000
Scale low
(A. table *****11* inputs only)
Setpoint low
See A. Table
Setpoint adjust disable. E-HL error disable. User input selecting.
The properties of output actuators. See B. Table
Limits: -1999...4000
Limits: -1999...4000
Scale high
(A. table *****11* inputs only) Limits: -1999...4000
Setpoint high
Limits: -1999...4000
Cycle time of control output (Y) in seconds.
Valve travel time from open to close.
Below Yd’ the motor does not start to rotate (recommended: 1-5)
Limits: 0...255 s
The maximal value of Y (%) if EPid[2]=1
Yt=1 for SSR
Below YLo the Y=0. Limitation of the control output
Limits: 0...100 (1. level/Y shows the unlimited value!)
Over YHi the Y=100. Limitation of the control output
Limits: 0...100 (1. level/Y shows the unlimited value!)
The properties of the analogue output
The low value of linear output
(E.g. for 0 mA » 0 °C)
The high value of linear output
(E.g. for 20 mA » 1000 °C)
Reset the factory settings.
There is not a linear output if LiLo=LiHi
Current output: 35(+) and 36 terminals
Voltage output: 36(+) and 37 terminals
The properties of ALARM ( relay, or *OPC ).
See
**
E. Table
Communication
See G. Table Detailed in Communication Manual
Logical OR or AND of ALAM2 and ALARM3 to
ALARM4 and ALARM5. See F. Table
MODBUS address 0...255
Master address : 255
Properties of patterns
See H. Table
Return Returns to the 2. level at menu item GAin
1. page ME160-5
Notation Refers to a menu item or setting: e.g. 1.p/3.level/LiLo first page, 3.level, LiLo menu item®
Refers to a table: e.g. 1.p/out[54]=01 ®1. page, B. table, 5 and 4 switches are in 01 state
*is instead of a number
and refers to the coherent menu items and settings
The EDS notations : = 00110011 (1=ON, 0=OFF)
• How to tune. Make an impulse on the 8-9 terminals. The controller tunes the parameters at the SP.
If the overshot may damage the process limit the output (Y) in 1.p/3.level/Yd’ and set 1.p/EPid[2]=1.
Let ALARM3 1.p/A3d[****3210]=****1010 and let the value of 1.p/1.level/A3 a little higher than the expect-
able biggest overshot.
There are two tuning method for motorized valve control. If 1.p/3.level/Yt<15 the tuning do not use the
travel time. If the controller uses the travel time written in1.p/3.level/Yt>15 1.p/3.level/Yt.
¤
Shows the maximal and minimal values of the control deviation. Its useful for very long pro-
cesses like as cold-store, brooder house etc.
¤¤¤There is a modulated sound at place of the relay or loudspeaker which can be acknowledged
and stoped by pushing the START botton.
¤
•
Cascade control. See C. Table
See D. Table
Cascade types.
dLin
LiLo
LiHi
SP
inP
GAin
Y
PrFL
SHFt
int
dEr
nrES
SPLo
dZon
SPHi
CnF
out
EPid
Yt
A*
Yd
Ah*
YLo
Pid -
YHi
-End
Ad*
A23L
con
Adr
-rEt
dE-r
dE L
dE H
rEt
PuHi
PuLo
dPrG
Ontc
Advance in profile with push-button
Reverse ALARM action
76543210H. Table EDSdPrG
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
1
1
1
1
1
1
0
0
0
0
0
0
1
1
1
1
1
1
0
0
0
1
1
1
0
0
0
1
1
1
0
0
0
1
1
1
0
0
0
1
1
1
ALARM (relay) is active in soak and may be: PROC, DEV, BAND
Asymmetrical ALARM hysteresis: + upper, - lower symmetrical(0 )
ALARM is active in (±) RAMP
1. ( RAMP±)
2. (±) RAMP
3. (±) RAMP
4. (±) RAMP
ALARM is active in waiting for SOAK (hidden FrEE)
1. waiting for SOAK (hidden FrEE)
2. waiting for SOAK (hidden FrEE)
3. waiting for SOAK (hidden FrEE)
4. waiting for SOAK (hidden FrEE)
ALARM is active in SOAK
1. SOAK
2. SOAK
3. SOAK
4. (±) RAMP
0
0
1
1
1
1
1
1
1
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
Active in state onlyOn
Operational
feature
of the ALARM
Instrument
events
Events
by the
type of
profile
step
The events (activated relay) are valid in
the program steps named on the left.
1
1
ALARM is active at the End command for 1s
ALARM is active when the controller is (control mode) stateOn
ALARM is active when the controller is or START delay stateOn
ALARM is active when the controller is in START delay state
Profile with 4 program-steps
The START delay value will be erased at its end.
Shows the remaining time when polling. (0 elapsed)®
Changing the data of profile is prohibited in stateOn
Time base HH:MM (hour:minute), measured in unit/hour
Increasing (+) RAMP enable only
1
00
1
0
0
1
ALARM is valid in profile (in profiles 0 and even also)I
IIIand
R2 »2 relay R3 »3 relay
AL ALARM
**»
1
Model identification: 0***
Model
identification:
1***
Model
identification:
2***
0
00
0
1
111
00
01
011
76543210C. Table EPid EDS
0
1
1
1
1
PID-A D is formed from control deviation (x = PV - SP)
e
PID-B (PV)D is formed from process value
PID PI automatic switching at small control deviation®
Output is limited by 3.level/A3d. Value in 3.level/Yd’
The effect in the 3.level/inp[3] selected filter decreases.
R2 = AL2 without function R3 = AL3 without function
R2 = AL2 or AL4 or AL5 R3 = AL3 or AL4 or AL5
R2 = AL2 or AL4 R3 = AL3 or AL4
R2 = AL2 or AL5 R3 = AL3 or AL5
R2 = AL2 and AL4 R3 = AL3 and AL4
R2 = AL2 and AL5 R3 = AL3 and AL5
R2 = AL2 or (AL4 and AL5) R3 = AL3 or (AL4 and AL5)
R2 = AL2 and (AL4 or AL5)
R2 = Sign, may stop by START
R3 = AL3 and (AL4 or AL5)
77
66
55
44
33
22
11
00
E. Table ALARM2Bool functions of
00
00
00
00
00
11
00
11
00
00
11
11
11
00
00
11
00
11
11
11
00
11
11
11
E. Table ALARM3Bool functions of
11R3 = Sign, may stop by START
Default input filter 14s if EPid[7]=1 than 0s
Strong input filter 24s if EPid[7]=1 than 7s
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
11
0
0
0
0
1
1
1
1
0
0
0
0
0
1
1
1
1
1
6543210A. Table inp EDS
PV without rounding
PV rounding to 5
1
0Temperature unit CELSIUS
Temperature unit FAHRENHEIT
Decimal Point Positioning: none
Decimal Point Positioningt ***.*
Decimal Point Positioning **.**
Decimal Point Positioning *.***
T
J
K
S
Pt100/385 (DIN)
KTY thermistor (accessory)
0-20 mA 0-2000 Ohm 0-200 mV
4-20 mA
7
(Cu-CuNi)
(Fe-CuNi)
(NiCr-Ni)
(PtRh10-Pt)
-50......850
-40......200
0....2000
0....2000
-50......900
-50....1000
-50....1300
-50....1760
for temperature inputs only
scaleable
1Shaded sensors are valid
-50.... 840
-40.... 150
-50......400
-50......900
-50....1300
-50....1600
(NiCr-CuNi)
(Fe-CuNi)
(NiCr-Ni)
(PtRh13-Pt)
JPt100/392
Ni100
PV rounding to 10
PV rounding to 50
for scaleable inputs only
L
N
R
E
Thermocouples
0
0
1
1
0
1
0
1
76543210B. Table out EDS
1
1
1
0
1
Changing the data of profile is prohibited
E-HL error message enabled when SPLo-5% PV SPHi+5%≥≥
Starts the Auto-tune see foot-note•
The A and A h do not appear in the 1. level, but their values are valid**
Reverse action (for heating)
Direct action (for cooling)
1
1
1
1
0
0
0
0
Changing control relays 1 3 (for SSR recommended)»
Control with relay
Valve positioning control 1. type Described on the 2. page
User inputs
Valve positioning control 2. type
Program START with push-button
Program START and STOP with push-button
0
1
01
10
11
1101
76543210D. Table dLin EDS
4-20 mA (1-5 V, 2-10 V) analogue output range
0-20 mA (0-5 V, 0-10 V) analogue output range
Process value (PV) on the analogue output
Control output value (Y) on the analogue output
Set-point value (SP) on the analogue output
Factory default settings reset
All of profile data erasing
1Indefinite soak enabled (S=On)
The resets and restores 0000
101
0(They operates in OFF state only)
76543210E. Table A d EDS
*
PROCESS type ALARM action
DEVIATION type ALARM action
BAND type ALARM action
ALARM is active when an error message is on
ALARM is active during the tune
ALARM is valid in profile (in profiles 1 and odd also)II
ALARM is valid in profile and (in all profiles also)III
76543210G. Table EDS (con 543210 in Communication Manual)
dE-r dE L dE H menu items are enabled (see in 1. level)
Waiting for SOAK (hidden FrEE) disabled
1 pc profile
1 pc profile
2 pc profiles
Profile with 4 program-steps
Profile with 8 program-steps
Profile with 4 program-steps
1 pc profile
Profile with 8 program-steps 2 pc profiles
Profile with 16 program-steps 1 pc profile (joined + )III
Profile with 4 program-steps 14 pc profiles
Profile with 8 program-steps 7 pc profiles
Profile with 16 program-steps (joined + )III3 pc profiles
Time base MM:SS (minute:second), measured in unit/minute
Increasing (+) RAMP and decreasing enable(-) RAMP
Normal broadcast communication for multichannel master
Cascade control-master device
Delta cascade-control deviceTmaster
0
10
11
Cascade control MASTER
00
Thermocouples
I
H
G
AR
2. page ME160-5
Warranty
Model: KD48P
Serial number: Date of purchase: Validation by the supplier:
The cost of transport (out and home) is borne by the customer. .
The HAGA Automation LTD’s KD48 series warranted to be free of defects in material, and fabrication. The warranty is valid
for 3 years after delivery to the first purchaser for use. The second period of the warranty is 2 years long in which the
manufacturer repairs the defective controller without fee, except the cost of materials. .
Since the HAGA Automation LTD can not influence the usage of the controllers, so the warranty is not valid for the
damages cased by them in the connected devices. ..
. .
The HAGA Automation LTD examines in its electrical laboratory the defective controller and detects the cause of breakdown.
The warranty does not apply to damage resulting from transportation, alteration, misuse or abuse. .
EMC installation guidelines
The KD48P controller generally is not sensible for electrical noise. The controller does not disturb the other instruments in
its environment as well. The extreme circumstances such as long leads, inductances without filters, etc. may reduce the
control qualities. In such cases you ought to prevent the spreading of the electric noise. The noises must be eliminated the
closest to its source. The filters and snubbers at the controller's inputs and outputs generally have not enough effects.
There are some thumb rules for improving the control properties. .
Connect to the every inductive coil a special filter as close as possible.
Give power from the operating circuit in a cabinet. If there is not, use separating transformer.
In very noisy environment install the controller in metal case which is properly connected to protective earth. If you have
more protective net use the best by trial. .
In very extreme environment (inductive heating, radio transmitter, X-ray appliances etc.) call an expert.
CAUTION: In any critical application where failure could cause expensive product loss or endanger personal safety, a
redundant limit controller or monitor is required. We recommend the KD48Bx controller. .
Never run the signal and control cables together the AC power lines. Use shielded cables and connect the shields (pigtails)
to the PE. .
All these sensible cables run as far the noise sources as possible.
and
For automatic lead compensation
Cascade control
KD48P PID Profile Controller. User’s Manual.
The KD48P type profile controller can solve all of your
heating tasks, where the temperature must be
controlled precisely by the time. .
Due to the robust PID algorithm the KD48P controls
the temperature along the programmed profile with
minimal oscillation. .
Please configure the controller before starting up. It is
necessary to read up this manual. Some skill in
knowledge of control may be useful. .
Danger warnings
Programming
It is very easy programming a profile by the graph.
Press the delayed START green lamp blinks and
the time appears in form on the display.
You can decrease with or inrease with
the delay.
Save the value pressing the again. The lamp of the 1. RAMP (heating velocity) will blink in form .
After pressing the controller saves the previous value and steps to the SOAK temperature setting.
The green lamp blinks and value displayed in form .
Set the SOAK temperature with .
Caution! The point at the and is the
signal of SOAK temperature.
Press and repeat the setting process for the SOAK time .
The time units of START delay, RAMP and SOAK are in hour or in minute according to configuration 1.p/dPrG[6].
Continue the programming to the and of the profile in the same way. The graph shows you what to do.
keys decrease or increase the displayed value with one unit at a press, but will run down or up
accelerated for holding them down. After the last program step the controller exits from programming. .
Press and hold for 5 seconds to start the control. The display changes from OFF to On. The controller
runs the programmed profile to the command or to the profile end. You can stop the program pressingEnd
and hold for 5 seconds. The lamps light red and the actual blinks. So the graph demonstrates the state
of process. .
The Difference display shows the control deviation. You can inquire about the actual time or temperature
pressing .
The lamp from among which is set blinks green. The actual running program step lamp is red and blinks.
The lamps of executed steps are continuously red. The lamp which is set in state blinks red-green.On .
For making the handling clear we name the profile construction and the set of the properties
of controller . To program a profile go through the graph and write the values in display and save.
Some useful facilities can you find below:
programming
configuring
When you enter a RAMP in the graph appears. At his command the program jumps across the
velocity segment and heat without any restrictions to the next temperature.SOAK
The temperature limits are configured in 1.p/3.level/ and .SOAK SPlo SPHi
Step one before with there is the which finishes the profile, turns out the controller.FrEE
At SOAK time value the controller jumps to the next RAMP, so it is possible to use two RAMPS
continuously. SOAK time is guaranteed so there is an automatic FrEE before SOAK temperature. This may
disabled by 1.p/3.level/con[6]=1.
The SOAK time may be timeless if 1.p/3.level/dLin[4]=1. The display shows in such a case .
The programming may be enabled or disabled by the 1.p/3.level/out[7] and 1.p/3.level/dPrG[5] in or
state. In state the controller acts by the changed value immediately..
On
OFF On
All of the ALARM (4 pc) can work as event in each program segment. Configure the properties in the places:
the properties first in 1p./3.level/A*d and A23L, the values after it in 1.p/1.level/A* and A*h.
Using the ON-OFF mode the system oscillates, the PV swings around the SP. The PID control mode gives
the efficiency performance. The H-TUNE determines the parameters after starting. Enter the set point
in the place of first soak temperature by this sketch. Configure 1.p/3.level/out[54]=00. Give a
short circuit on 8 9 terminals for 1-3 seconds. The display shows holding down . The controller
makes 3 on-off oscillations around the selected set point and writes the parameters in the 1.p/1.level. After
it returns to the normal mode. The PID parameters can be altered for modifying of control properties.
tunE
.
Operation of H-TUNE function
The auto tune may be started in or state. The controller goes state finishing the tune.
For special tune see foot-note on 1. page.
On OFF OFF
.
There is a modulated (intermittent signal on the 2. relay if) 1.p/A23L[7]=1 and on the 3. relay if A23L[3]=1
when the relay is active. Acknowledge and turn off the signal with pressing .
There is a buzzer instead of relay by order.
In the controller containing 16 program steps
you may change by pressing for 5
seconds. The profil names are:
profiles
and .P-- I P--II
The controller containing 56 program steps you
profile inmay choose a 1.p/1.level/PrFL.
The Fig.2. shows an annealing program. The
explanations are as follows:
The range of the first part of the program is
effective to the line 7. The next part runs to
the line 13 and the symbol is lighting. At
the line 11 the controller turns off the process.
+
If two profile is connected 1.p/3.level/dPrG[2]=1
during the running of the second profile the II
symbol is lighting. .
Take it into account that the profiles may be connected by the 1.p/3.level/dPrG[012]= configuration. Write
the connected programs by itself in OFF state. The editing of connected programs in On state are disable.
***
Cation! If there is a START delay before a connected program than it appears before each profile, but it
will be effective after the start only. .
START
START
START
Set the RAMP value with the keys. The value for programmed cooling is negative. The
upper point in the RAMP value is not a decimal point but shows the difference between the RAMP and
SOAK values.
Caution!
START
START
START
START
START
MAINS
All the necessary fasteners and
connectors are in the accessory bag
Fig. 4
1
2
3
4
5
6
7
8
31
32
33
34
35
36
37
38
21
22
23
24
25
26
27
28
MODE
INPUT
+
-
24Vdc
Tx
A
Rx
B
R1
R2
R3
+
-
User input.
1.p/3.level/out[54]
-2
-6
-10
-15 26
10 15
Lights
Blinks
Does not light
Key for SP difference displayPV-
The deviation display gives fast
information about the state of the
control loop. The control deviation
can be seen by cast a glance at it.
SP
PV-SP
Programming example
12345678910 12 13
4+
Start delay: 17:30
RAMP: 450°C/h
RAMP: 500°C/h
RAMP: 650°C/h
RAMP: End
SOAK temperaturet: 300°C
SOAK temperature: 630°C
SOAK temperature: 980°C
SOAK time: 00:30
SOAK time: 00:20
SOAK time: 00:15
11
Fig. 2.
Fig. 3.
4+
START
321
45
Relays
Relays
The program
runs or is set
II
The program runs
on 4+ area (next 4
steps) or is set
SOAK
temperature
Heating velocity
START delay
Steps in graphic
Deacrease value
Increase value SOAK time
Difference display
Fig. 1.
Y
Actuator
Power supply
Voltage: 85-265VAC, 48-400Hz, 120-375VDC
Power: 3 VA
Fuses: for supply: T315mA.
for relays: 3A
Dielectric strength: EN 61010, 2/II
All the inputs and outputs are galvanic isolated
(except Ssd)
n controller: 51xn+6
Installation
Cut out
45+0,3
45+0,3
Placing in a row
30
Placing in a row
(before the controller)
Relais: 3A, 230V, Ac1. Lifetime min.: 100000 cycle
26
27
28
KTY
+
-
PT100
10 W
Thermo couple
0-20 mA
4-20 mA
0-200 mV
KTY
Wiring of sensors and transmitters which
was set in: 1.p/3.level/ inp [4 210]*
Wiring
56 7
67 8
23
3
22 21
5
Closes
Opens
L
N
NL
KTY measures the temperature of the cold junction.
Short-circuit on 26-27 turns the cold junction compensation off.
Wiring the valve positioning
motor. 1.p/out: 10.
Closes at mains fall off and OFF state
******
1. type
Opens
Closes
Wiring the valve positioning
motor 1.p/out: 11.
It remains in actual position
at mains fall off,
closes in OFF state
******
2. type
4
Types of ALARMs
ALARM value
ALARM value
ALARM value
ALARM value ALARM value
ALARM value
SP
SP
SP
SP
DEVIATION
BAND
PROCESS
NORMAL ALARM REVERSE ALARM
Relay active
Relay inactive
Relay active
Relay inactive
Relay active
Relay inactive
Hysteresis
Relay active
Relay active
Relay active
Relay inactive
Relay inactive
Relay inactive
Hysteresis
Hysteresis
Hysteresis
SP
Lower
asymmetrical
Symmetrical
Upper
asymmetrical
The ALARMs are a logical functions which act the relays. In the 1.p/3.level/A*d defined properties
determine the value of this function in the process. If the result is 0 the relay inactive (default state).
If it is 1 than active (reverse to the default). The relay is open in the case of reverse
configuration in active state. Some bool functions are in 1.p/3.level/A23L. These functions can connect
ALARMs together e.g.: in case of A23L[210]=100 R3 is active if AL3 AL4 are active.
Caution!
and .
When the heat source is far from the workpiece, the controller can not regulate it properly. The controlI
is slow and unstable. Such process is the heating in a retort. Because of the big delay time a fair-sized
temperature overshot may occur.
To eliminate the the waste in material and energy, use 2 controllers in one cascade group. The inside
controller will be the MASTER and the outside the SLAVE.
The HAGA controllers are able to control in cascade method. You can configure the MASTER and connect
to the SLAVE thorough the communication port.
.
.
.
.
.
.
Enter into the configuration and how to do it
Configuring
The configuration specifies the properties of the controller. The configuration pages accept the data by
the model identification only. There is a map on the 1. page containing all of the menu items and the
moving possibilities among them. There are a lot of security items in the menu. The adequate
configuration helps you to select a very good operation. Using the security code to the necessary grade
the handling will be very easy. So the operator can not enter false data into the process. .
Press and hold and after it for about 3 seconds. The blinking appears. This is the first level of
configuration (see map on 1.page). Browse about the menu items with . At menu item you
can go on the second level and at menu item on the third level.
SP
Pid-
CnF- .
Enter the menu item with and set it with . Each set goes in the memory by pressing again.
The memory stores the data for an indefinite period.
0%
Y(SP)
SP
dZon
Yt
Yd’
Yd’
Open Close
100%
Yt valve update time, the period of one full opening from
closed state with Y=100 % actuation
Y(SP) Y at the stable range
dZon dead zone.
Yd’ is the smallest changing of Y, which can turn the motor.
Below this value the controller does not move the motor.
Valve positioning data
START
START
Start and stop program (5 s)
Inquire for output (Y) in %
Changing and program (5 s)P-- I P--II
Value of program step while stateOn
Special actuations with keys
Enter to security code (30 s)
Enter into configuration (3 s) Thetimewrittenin
brackets are periods
of pressing Start
pressing from right.
.
Accept (ENTER)
Setting: Exit:
Security
The protect function is for preventing unwanted modification of settings. The protected levels are hidden
by a 6 bit code. Press the keys for 30 seconds. An EDS appears on the display with the
following actions:
Protect code
e.g.: 001011
Security
levels
00 without protection
01 3. level is hidden
10 2.
11 everything
level is hidden
is hidden
Please memorise the protect code. You can not change the security levels without the protect code!
The service can erase it, if you have forgotten the code.
START
Error messages.
A/D converter error. Service can repair it. .
Setting error SPLo SPHi
≤
in state out [6]=1, if SPLo-5% PV SPHi+5%≥≥
Overflow
Underflow
The error message disappears after a reset, if the fault was repaired..
Outside
PV range
Repairing
When the self test after the start repeats continuously the controller has
got out of order. The controller may be repaired by the manufacturer.
____
ALARM3 code
Relay
0
1
None
2
3
4
5
6
Current output 0/4-20 mA
Voltage output 0/1-5 V
Voltage output 0/2-10 V
Buzzer
OPC
KD48P
Model identification
The controller is made of separate parts.
So you can extend it later.
Code
1
2
0
4 steps
56 steps
16 steps
Program
Communication Code
RS-232
0
1
None
2
RS-485
Other Code
0
1
None
Voltage
for transmitter
2
3
ALARM 4,5
Both
UT
Addition to the KD48P Manual
The addition can be found in the 3. page at the d.FrE menu item.
This supplement contains some useful properties..
The light intensity can be set from half to whole. The half intensity is enough in normal circumstances and the instrument does not
warm over. The whole intensity has to use by daylight.
The band of switching from ramp to Soak may be widened. When the PID parameters are not precisely tuned or the power is very few
then the controller can not reach the Soak temperature and it is switching some degrees under it. This option eliminates the
phenomena, but would be better to use a correct PID parameter set.
76543210d.FrE
0 The display lights with half intensity
1 The display lights with whole intensity
00 ±2
±4
±6
±8
Free operation
a. figure
Ramp operation b. figure
Ramp operation c. figure
01
10
11
0
1
0When setting the ramp value (°C/h, or °C/min) you can see the upper point. ***·*.
1When setting the ramp value (°C/h, or °C/min) you can not see the upper point ****.
1 The actuator can be scaled at YLo and YHi for Solid State Relay Driver (Ssd).
Settings of the actuator.Ifd.FrE[0]=0 the actuator operates by the Manual. If d.FrE [0]=1 and out[1]=0 (using relay or, Ssd for the
control) the actuator (Y) can be alterable and scalable. The relation between the Yvalue counted by the PID algorithm and value
which appears at the output is the next:
Y=0% the output is (e.g. Ssd) YLo.
Y=100% the output is (e.g. Ssd) YLHi. But YLo <YHi relation must be true!
YLo and YHi are set by the Manual and are the endpoints of the actuator scaling..
The controller counts the value for actuator between these two values linearly.
What is this function for? In some system occurs that its power is to much. This option can improve the control properties.
E.g. set YHi=50. By this value the actuator gets 50% when the counted value is 100%. It seems if the power had been halved. The
system has changed of course so it must be tuned again.
Important! Please tune the system after every actuator scaling!
Pay attention to the value of YLo! Because of the lowest value of the YLo is the least value for the actuator, it will operate
the system eve it is in OFF state. Be careful when use it! It my be useful for saving a system against frost.
+6
-6
SP for
soak
switching
to soak
Free
a. fi
g
ure
SP for
soak switching
to soak
°C/hour
b. fi
g
ure
+6
-6
SP for
soak
switching
to soak
°C/hour
c. fi
g
ure

Popular Controllers manuals by other brands

West Penn Wire AV-IP-NC811 Operation manual

West Penn Wire

West Penn Wire AV-IP-NC811 Operation manual

Reflex Reflexomat RS 90/1 operating manual

Reflex

Reflex Reflexomat RS 90/1 operating manual

Ametek Magnetrol Tuffy Installation and operating manual

Ametek

Ametek Magnetrol Tuffy Installation and operating manual

M-system PSP10 instruction manual

M-system

M-system PSP10 instruction manual

Honeywell LCBS Connect Applications manual

Honeywell

Honeywell LCBS Connect Applications manual

WEG AVR-A-OPT-16 Installation, operation and maintenance manual

WEG

WEG AVR-A-OPT-16 Installation, operation and maintenance manual

Mitsubishi Electric MELSEC iQ-F Series user manual

Mitsubishi Electric

Mitsubishi Electric MELSEC iQ-F Series user manual

Archer VR2K Installation operation & maintenance

Archer

Archer VR2K Installation operation & maintenance

Duratrax IntelliSpeed 12T operating instructions

Duratrax

Duratrax IntelliSpeed 12T operating instructions

Eurotherm 2132 operating instructions

Eurotherm

Eurotherm 2132 operating instructions

APD HV-PRO quick start guide

APD

APD HV-PRO quick start guide

Regin Exigo Instruction

Regin

Regin Exigo Instruction

Salus TRV10RFM user manual

Salus

Salus TRV10RFM user manual

National Instruments PXI-8231 installation guide

National Instruments

National Instruments PXI-8231 installation guide

Emec Centurio PRO operating manual

Emec

Emec Centurio PRO operating manual

Xilinx Zynq UltraScale+ ZCU104 GUI Tutorial

Xilinx

Xilinx Zynq UltraScale+ ZCU104 GUI Tutorial

HikRobot VB2200 Series user manual

HikRobot

HikRobot VB2200 Series user manual

Lavo LavoDose Series instruction manual

Lavo

Lavo LavoDose Series instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.