16
Model AV08CMVUSA AV10CMVUSA
Outdoor coil
Number of rows 2 2
Tube pitch (a)×row pitch (b) mm 19.05*22 19.05*22
Fin spacing mm 1.70 1.70
Fin type (code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating type Optional Clear lacquer Clear lacquer
Salt spray test duration Hour 168 168
Tube outside dia.and type INNERGROOVE TUBE INNERGROOVE TUBE
mm Ф8 Ф8
Coil length×height mm (1340×660)*2 (1340×660)*2
Number of circuits 10 10
Cabinet
coating
Coating type Powder coating Powder coating
Salt spray test duration Hour 72 72
Sheet metal material Hot zinc plate Hot zinc plate
Sheet metal thickness mm 0.8 0.8
Control panel enclosure IP class Standard IP24 IP24
Outdoor air ow m3/h 11100 11100
External static pressure Pa 50 50
Outdoor sound level (sound pressure level) (H) dB (A) 57 57
Outdoor sound level (sound power level ) (H) dB (A) 73 73
Outdoor unit
Dimension (W*H*D) mm 990×1808×750 990×1808×750
Packing (W*H*D) mm 1090×1990×860 1090×1990×860
Net weight kg 240 240
Gross weight kg 268 268
Refrigerant Type R410A R410A
Charged volume*3 kg 10 10
Throttle type EXV EXV
Design pressure MPa 4.15 4.15
Refrigerant
piping
Liquid pipe mm Ф9.52 Ф9.52
Gas pipe mm Ф19.05 Ф22.2
High pressure pipe mm Ф19.05 Ф19.05
Oil pipe mm 9.52 9.52
Total pipe lenth m 300 300
Max. pipe length
(Equivalent/ Actual) m175/150 175/150
Max. Diff. indoor/outdoor unit m50 (Outdoor higher than indoor)
40 (Indoor higher than outdoor)
Max. Diff. indoor/indoor unit m 15 15
Connectable indoor unit ratio % 50~130% 50~130%
Maximum indoor units Piece 13 16
Connection
wiring
Power wiring mm210 16
Signal wiring mm2Shield wire: (0.75-2)*2 Shield wire: (0.75-2)*2
Operation range °C
Cooling: -5°C-43DB (°C)
Cooling&Heating: -8°C-18WB (°C)
Heating: -15°C-15.5WB (°C)
Norminal condition:
Indoor temperature (cooling): 27DB (°C)/19WB (°C), indoor temperature (heating): 20DB (°C)/14.5WB (°C).
Outdoor temperature (cooling): 35DB (°C)/24WB (°C), outdoor temperature(heating): 7DB (°C)/6WB (°C).
The data is measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.