Haiwell T Series User manual

Xiamen Haiwell Technology Co., Ltd. www.haiwell.com
Haiwell PLC User Manual
Programmable Logic Controller
C/T series PLC MPU user manual

www.haiwell.com Haiwell PLC - C/T series PLC MPU user manual
2 / 6
Contents
1. Product Model List & Dimensions.................................................................................................................................................................. 3
2. Indicator Description.........................................................................................................................................................................................3
3. Power Supply Specification.............................................................................................................................................................................4
4. Environmental specifications for Product......................................................................................................................................................4
5. Digital Input (DI) Specification........................................................................................................................................................................ 4
6. Digital Output (DO) Specification................................................................................................................................................................... 4
7. Digital Input/Output (DI/DO) Wiring................................................................................................................................................................5
8. MPU Terminal Wiring Diagram....................................................................................................................................................................... 5
9. Mounting and installation.................................................................................................................................................................................6
10. Programming Cable Wiring........................................................................................................................................................................... 6
11. Address Setting............................................................................................................................................................................................... 6
12. Power Supply Wiring......................................................................................................................................................................................6

www.haiwell.com Haiwell PLC - C/T series PLC MPU user manual
3 / 6
1. Product Model List & Dimensions
Ethernet Model
24VDC
Ethernet Model
220VAC
Model
24VDC
Model
220VAC
Dimension
C10S0R-e
0.33A
C10S2R-e
9.4W
C10S0R
0.3A
C10S2R
8.8W
93×95×82mm
C10S0T/P-e
0.33A
C10S2T/P-e
9.2W
C10S0T/P
0.3A
C10S2T/P
8.6W
C16S0R-e
0.34A
C16S2R-e
10.2W
C16S0R
0.31A
C16S2R
9.6W
C16S0T/P-e
0.34A
C16S2T/P-e
10.3W
C16S0T/P
0.31A
C16S2T/P
9.7W
T16S0R-e
0.56A
T16S2R-e
10.2W
T16S0R
0.53A
T16S2R
9.6W
T16S0T/P-e
0.58A
T16S2T/P-e
10.9W
T16S0T/P
0.55A
T16S2T/P
10.3W
C24S0R-e
0.39A
C24S2R-e
11.5W
C24S0R
0.36A
C24S2R
10.9W
131×95×82mm
C24S0T/P-e
0.39A
C24S2T/P-e
11.3W
C24S0T/P
0.36A
C24S2T/P
10.7W
T24S0R-e
0.6A
T24S2R-e
11.3W
T24S0R
0.57A
T24S2R
10.7W
T24S0T/P-e
0.62A
T24S2T/P-e
11.7W
T24S0T/P
0.59A
T24S2T/P
11.1W
C32S0T/P-e
0.43A
C32S2T/P-e
12W
C32S0T/P
0.4A
C32S2T/P
11.4W
C32S0R-e
0.42A
C32S2R-e
12.2W
C32S0R
0.39A
C32S2R
11.6W
T32S0R-e
0.64A
T32S2R-e
13.1W
T32S0R
0.61A
T32S2R
12.5W
T32S0T/P-e
0.66A
T32S2T/P-e
12.7W
T32S0T/P
0.63A
T32S2T/P
12.1W
C48S0R-e
0.7A
C48S2R-e
15W
C48S0R
0.67A
C48S2R
14.4W
131×95×82mm
C48S0T/P-e
0.71A
C48S2T/P-e
14.3W
C48S0T/P
0.68A
C48S2T/P
13.7W
T48S0R-e
0.72A
T48S2R-e
11.1W
T48S0R
0.69A
T48S2R
10.5W
T48S0T/P-e
0.74A
T48S2T/P-e
10.7W
T48S0T/P
0.71A
T48S2T/P
10.1W
C60S0R-e
0.77A
C60S2R-e
16.6W
C60S0R
0.74A
C60S2R
16W
C60S0T/P-e
0.77A
C60S2T/P-e
17W
C60S0T/P
0.74A
C60S2T/P
16.4W
T60S0R-e
0.78A
T60S2R-e
17.1W
T60S0R
0.75A
T60S2R
16.5W
T60S0T/P-e
0.8A
T60S2T/P-e
17.8W
T60S0T/P
0.77A
T60S2T/P
17.2W
2. Indicator Description
1PWR: Power indicator,green. Continuous ON - Power good; OFF - Power error.
2RUN: Running indicator,green. Continuous ON - PLC is in running state; OFF - PLC was shutdown.
3COM: Communication indicator,green. Flickering - PLC is in communicating state, the flicker frequency indicates the
speed of the communication; OFF - No communication.
4ERR: Error indicator, red. Continuous ON - Hardware failure; Flickering - Software failure; OFF - Normal state.

www.haiwell.com Haiwell PLC - C/T series PLC MPU user manual
4 / 6
According to the different states of the Error indicator, users are recommended to take the following actions:
State of the Error Indicator
Indication Information
Actions to Take
OFF
No error
Nothing
Flicker as below:
0.5 second’s on with 0.5 second’s off
Firmware abnormal or program error, keep running
program is not recommended
Re-upgrade firmware or modify program
Continuous ON
Hardware failure, program is unable to run
Send the PLC back to us for repair
3. Power Supply Specification
Item
AC Power Supply
DC Power Supply
Power Supply Voltage
100~240VAC
DC24V -15%~+20%
Power Supply Frequency
50~60Hz
——
Power Consumption
25VA MAX
——
Instantaneous Surge
20A 1.5ms MAX @220VAC
20A 1.5ms MAX @24VDC
Power Loss Time
20ms or less @220VAC
10ms or less
Fuse
2A, 250VAC
2A, 250VAC
5V Output Voltage (for CPU)
5V, -2%~+2%, 1.2A MAX
5V, -2%~+2%, 1.2A MAX
24V Output Voltage (for output and extension)
24V, -15%~+15%, 500mA MAX
24V, -15%~+15%, 500mA MAX
24V Output Voltage (for input and peripheral)
24V, -15%~+15%, 200mA MAX
Use external 24VDC power supply
Insulation Type
Transformer isolation or optoelectronic
isolation, 1500VAC/1 minute
No Electrical isolation
Power Protection
DC24V output over current
DC input power polarity reverse, over voltage
4. Environmental specifications for Product
Item
Environment Specification
Temperature/Humidity
Operating temperature:0~+55℃Storage temperature:-25~+70℃Humidity: 5~95%RH, No condensation
Vibration Resistance
10~57 HZ, amplitude=0.075mm, 57HZ~150HZ acceleration=1G, 10 times each for X-axis, Y-axis and Z-axis
Impact Resistance
15G, duration=11ms, 6 times each for X-axis, Y-axis and Z-axis
Interference Immunity
AC EFT:±2500V Surge:±2500V
DC EFT:±2500V Surge:±1000V
Over Voltage Resistance
1500VAC/1min between AC terminal and PE terminal, 500VAC/1min between DC terminal and PE terminal
Insulation Impedance
≧5MΩbetween AC terminal and all input/output points to PE terminal @500VDC
Ground
The third kind of grounding(Connecting to the ground of high voltage system is prohibited)
Operating environment
Avoid dust, moisture, corrosion, electric shock and external shocks
5. Digital Input (DI) Specification
Item
Digital Input (DI)
Input Signal
No voltage contact or NPN/PNP
Action driving
ON>3.5mA OFF<1.5mA
Input Impedance
Input Impedance≈4.3KΩ
Maximum Input Current
10mA
Reaction Time
6.4ms DEFAULT, can be configured to 0.8~51.2ms
Insulation Type
Optoelectronic isolation for each channel
Input Indication
LED's lighting indicates ON, no light indicates OFF
Power supply
MPU internal power supply:DC power supply (SINK or SOURCE) 5.3mA@24VDC
6. Digital Output (DO) Specification
Item
Output point type : Relay - R
NPN or PNP transistor output T/P
Maximum load
Resistive Load
2A/1 point, 8A/4 points COM
0.5A/1 point, 2A/4 points COM
Inductive Load
50VA
5W/DC24V
Lamp load
100W
12W/DC24V
Minimum Load
10mA
2mA
Voltage Specification
Below 250VAC, 30VDC
30VDC
Drive Capability
Maximum contact capacity: 5A/250VAC
1A MAX, 10 seconds
Reaction Time
Off→On 10ms, On→off 5ms
Off→On 10μs, On→Off 120μs
Insulation Type
Mechanical isolation
Optoelectronic isolation for each channel
Output Indication
LED's lighting indicates ON, no light indicates OFF
Power Supply
MPU internal 24VDC power supply

www.haiwell.com Haiwell PLC - C/T series PLC MPU user manual
5 / 6
7. Digital Input/Output (DI/DO) Wiring
8. MPU Terminal Wiring Diagram
C10S0R/T/P(-e) C24S0R/T/P(-e)
C32S0R/T/P(-e)
C24S2R/T/P(-e)
C32S2R/T/P(-e)
C60S0R/T/P(-e)
C48S0R/T/P(-e)
C16S2R/T/P(-e)
C10S2R/T/P(-e)
24G
+24V
S/S
X0
X4
X1
X5
X2 X3
DC POWER
24G
+24V
S/S
X0
X8
X1
X9
X2
X10
X3
X11
X4
X12
X5
X13
X6
X14
X7
X15
DC POWER
Y1
Y2 Y3 C4
Y4
Y6
Y5
Y7 B-
Y0
C0 A+
GND RS485
24G
+24V
S/S
X0
X8
X1
X9
X2
X10
X3
X11
X4
X12
X5
X13
X6
X14
X7
X15
DC POWER
Y2 Y3 C4 Y6 Y7 Y10 Y11 C12 Y14 Y15 Y18 Y19
C0 Y0 Y1 Y4 Y5 C8 Y8 Y9 Y12 Y13 C16 Y16 Y17 GND
A+ B-
AC
IN
RS485
24G
+24V
S/S
X0
X4
X1
X5
X2 X3
AC POWER
C48S2R/T/P(-e)
Y2 Y3 C4 Y6 Y7 Y10 Y11 C12 Y14 Y15 Y18 Y19 C20 Y22 Y23
C0 Y0 Y1 Y4 Y5 C8 Y8 Y9 Y12 Y13 C16 Y16 Y17 Y20 Y21 GND
A+ B-
AC
IN
RS485
S/S X19 X21 X22 X23 X24 X25 X26 X27
X0 X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X15 X16 X17
X20
X18 X14
OUTPUT
Max 200mA
+24V OUT-
S/S X19 X21 X22 X23 X24 X25 X26 X27 X28 X29 X30 X31 X32 X33 X34 X35
X0 X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X15 X16 X17
X20
X18 X14
OUTPUT
Max 200mA
+24V OUT-
Y2 Y3 C4 Y6 Y7 Y10 Y11 C12 Y14 Y15 Y18 Y19 C20 Y22 Y23
C0 Y0 Y1 Y4 Y5 C8 Y8 Y9 Y12 Y13 C16 Y16 Y17 Y20 Y21 GND
A+ B-
DC
IN
RS485
S/S X19 X21 X22 X23 X24 X25 X26 X27 X28 X29 X30 X31 X32 X33 X34 X35
X0 X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X15 X16 X17
X20
X18 X14
OUTPUT
Max 200mA
+24V OUT-
Y2 Y3 C4 Y6 Y7 Y10 Y11 C12 Y14 Y15 Y18 Y19
C0 Y0 Y1 Y4 Y5 C8 Y8 Y9 Y12 Y13 C16 Y16 Y17 GND
A+ B-
DC
IN
RS485
S/S X19 X21 X22 X23 X24 X25 X26 X27
X0 X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X15 X16 X17
X20
X18 X14
OUTPUT
Max 200mA
+24V OUT-
C60S2R/T/P(-e)
T16S2R/T/P(-e)
T24S0R/T/P(-e)
T32S0R/T/P(-e)
T24S2R/T/P(-e)
T32S2R/T/P(-e)
T60S0R/T/P(-e)
T48S0R/T/P(-e)
T48S2R/T/P(-e)
T60S2R/T/P(-e)
+ 24V IN -
+ 24V IN -
+ 24V IN -
+ 24V IN -
+ 24V IN -
N
L
N
L
Y1
Y2 Y3 A+ B-
Y0
C0 GND RS485
Y1
Y2 Y3 A+ B-
Y0
C0 GND RS485
24G
+24V
S/S
X0
X4
X1
X5
X2
X6
X3
X7
AC POWER
N
L
Y1
Y2 Y3 C4
Y4
Y6
Y5
Y7 C8
Y8
Y10
Y9
Y11 C12
Y12
Y14
Y13
Y15
B-
Y0
C0 A+
GND RS485
Y1
Y2 Y3 C4
Y4
Y6
Y5
Y7 C8
Y8
Y10
Y9
Y11 C12
Y12
Y14
Y13
Y15
B-
Y0
C0 A+
GND RS485
24G
+24V
S/S
X0
X8
X1
X9
X2
X10
X3
X11
X4
X12
X5
X13
X6
X14
X7
X15
AC POWER
Y1
Y2 Y3 C4
Y4
Y6
Y5
Y7 B-
Y0
C0 A+
GND RS485
24G
+24V
S/S
X0
X8
X1
X9
X2
X10
X3
X11
X4
X12
X5
X13
X6
X14
X7
X15
AC POWER
Y1
Y2
Y4
Y3 C4
Y5
Y6 Y7
A+ B-
Y0
C0 GND RS485
N
L
N
L
N
L
C16S0R/T/P(-e)
24G
+24V
S/S
X0
X4
X1
X5
X2
X6
X3
X7
DC POWER
T16S0R/T/P(-e)
+ 24V IN -
Y1
Y2 Y3
Y4
C4
Y5
Y6 Y7
A+ B-
Y0
C0 GND RS485

www.haiwell.com Haiwell PLC - C/T series PLC MPU user manual
6 / 6
9. Mounting and installation
The PLC should be secured to an enclosed cabinet while mounting. For
heat dissipation, make sure to provide a minimum clearance of 50mm
between the unit and all sides of the cabinet. (See the figure.)
Rail Mounting: Use standard 35 mm rail.
Screw Mounting: Each MPU or extension module has two positioning
screw holes, the diameter of the hole is 4.5mm. Please refer to the
dimension figure for the location of the positioning holes and their
spacing.
To avoid over temperature and for a better heat dissipation, do not
mount PLC to a position near to the bottom/top of the cabinet. Do not
mount PLC in vertical direction.
Extension Module Wiring: Connections between extension modules and connections between module and MPU are
achieved through bus.An extension cable will be configured to every extension module, for the connection between two
different modules.
Connection methods: turn the right side of extended interface (the last MPU or extension module) over, plug the extension
cable in the extended interface, then press down the cover of the extended interface to reset the interface, the extended
interface at the right side of the module will be reserved for extension of the next module. Connect all extension modules in turn
in the same way.
10. Programming Cable Wiring
Computer side (RS-232) DB9 female PLC side (COM1) 4 core S terminal male
11. Address Setting
Haiwell PLC with Ethernet port, the default IP address is : 192.168.1.111, subnet mask: 255.255.255.0,
gateway: 192.168.1.1. Hardware DIP dial switch address range: 1-15, the default address is 1. If you
need to set a bigger adress range, you can set on the software after connection with PLC, it can be set
on the PLC parameter option in the sofware menu by checking on the "soft address" with the range of
1-254 (the soft address is prior to the hardware dial address).
12. Power Supply Wiring
There are two kinds of power supplies for PLC: AC input and DC input. Please pay particular attention to the following notes:
AC input voltage is 100~240VAC 50/60Hz unless otherwise stated. Connecting any one of the AC input wires to the
terminal-L and terminal-N on the MPU will be OK, but for safety's sake, please connect the two wires (Live Wire & Neutral
Wire) of AC input to terminal-L and terminal-N respectively.
Any AC110V or AC220V connected to the +24V terminal or input points will permanently damage the PLC.
Please use wires of 2.5mm or above for the grounding of the MPU.
Thanks for choosing Haiwell PLC, If you have any questions about our products or services, please let us know!
Haiwell website: www.haiwell.com Copyright © 2005 Xiamen Haiwell Technology Co.,Ltd.