Halton Max Ultra Circular User manual

Enabling Wellbeing
All rights reserved ©Halton
Halton Max Ultra Circular (MUC) - Quick
guide for commissioning

Halton Max Ultra Circular (MUC) - Quick guide for commissioning
2
2.0
All rights reserved ©Halton
Contents
1Introduction ................................................................................................................................................................. 3
1.1 About this document........................................................................................................................................... 3
1.2 Copyright and disclaimers .................................................................................................................................. 3
1.3 Summary of changes ......................................................................................................................................... 3
1.4 Contact information ............................................................................................................................................ 3
2Product description ..................................................................................................................................................... 4
2.1 Overview ............................................................................................................................................................ 4
3Commissioning ........................................................................................................................................................... 5
3.1 Before you start .................................................................................................................................................. 5
3.1.1 Commissioning process............................................................................................................................. 5
3.1.2 Commissioning information........................................................................................................................ 5
3.1.3 Airflow control panel................................................................................................................................... 6
3.1.4 Airflow control panel: start-up views .......................................................................................................... 7
3.1.5 Modbus RTU communication..................................................................................................................... 8
3.1.6 Self-diagnosis function............................................................................................................................... 8
3.2 Step by step instructions .................................................................................................................................... 9
3.2.1 Configuring basic controller settings in analog mode ................................................................................ 9
3.2.2 Configuring basic controller settings in Modbus mode .............................................................................. 9
3.2.3 Configuring basic controller settings in console mode (service or testing) .............................................. 10
3.2.4 Calculating the airflow control and feedback signals ............................................................................... 10
3.2.5 Rebooting the controller........................................................................................................................... 11
3.2.6 Configuring the scheduled restart function .............................................................................................. 11
4Troubleshooting ........................................................................................................................................................ 11
5Technical reference data .......................................................................................................................................... 12
5.1 Controller connections...................................................................................................................................... 12
5.2 Parameters ....................................................................................................................................................... 13
5.2.1 Halton Max Ultra Circular (MUC) installation cases................................................................................. 13

Halton Max Ultra Circular (MUC) - Quick guide for commissioning
3
2.0
All rights reserved ©Halton
1 Introduction
1.1 About this document
This quick guide provides the instructions on how to commission the product. This document is intended for
properly trained persons performing these tasks.
Note: Project-specific variations are possible.
1.2 Copyright and disclaimers
The contents of this document are strictly confidential and for information purposes only. Disclosing the information
in this document without an appropriate contract or permission by Halton to any third party is prohibited. This
document remains the sole property of Halton and may not be duplicated, borrowed, copied, amended, modified,
reproduced, transmitted or distributed to any third party without the prior written consent of Halton. Any information
held in this document or associated materials may only be used for the purpose specified in this document.
Halton disclaims any and all liability related to this document. Halton gives no explicit or implied warranties in terms
of this document. Any permitted use of the information included herein is at your own risk. Halton may amend or
replace the information included in this document at its sole discretion without further notice and liability.
All intellectual property rights or applications thereof, including without limitation copyright, model rights, patents,
trade secrets, trade names, trademarks, know-how (whether registered or unregistered) attributable to this
document remain the sole and exclusive property of Halton. No rights or licenses are granted.
1.3 Summary of changes
Release Date Description
2.0 12-Apr-2022 ▪Duct connection size 400 mm added.
▪New actuator models added.
▪Chapter Commissioning updated.
▪Chapter Troubleshooting added.
▪Editorial changes.
1.4 Contact information
For contact information, see www.halton.com.

Halton Max Ultra Circular (MUC) - Quick guide for commissioning
4
2.0
All rights reserved ©Halton
2 Product description
2.1 Overview
Fig. 1. Halton Max Ultra Circular (MUC)
Circular airflow management damper using the ultrasound technique for airflow measurement.
Application areas
▪Variable (VAV) and constant (CAV) airflow control applications
▪Supply and exhaust installations
Key features
▪Insensitive to dust collection
▪Enables flexibility in terms of space layout
▪Individually calibrated for higher accuracies
▪Low pressure loss for reducing the noise level
▪Can be connected to Building Management System (BMS)

Halton Max Ultra Circular (MUC) - Quick guide for commissioning
5
2.0
All rights reserved ©Halton
3 Commissioning
3.1 Before you start
3.1.1 Commissioning process
The main steps in the commissioning process are the following:
▪Configuring the basic controller settings (including: selecting the installation case)
▪Setting the Modbus communication parameters (optional)
3.1.2 Commissioning information
Before the system start-up, the controller settings (including the correct installation case) and optionally the Modbus
communication parameters have to be set.
Factory settings
The airflow range for Halton Max Ultra Circular (MUC) is preset at the factory. The factory settings for the control
signal and feedback signal are the same, but they can be configured individually. If the airflow range is not
specified by the customer, the default factory settings are the following:
▪Minimum airflow rate: 0 l/s
▪Maximum airflow rate corresponds to an airflow velocity of 10 m/s
The maximum airflow rates in the following table are given with an airflow velocity of 10 m/s. This applies to all
Halton Max Ultra Circular (MUC) actuator models.
NS
Max. airflow [l/s] @ 10 m/s (Vnom) Max. airflow [m3/h] @ 10 m/s (Vnom)
100 79 283
125 123 442
160 201 724
200 314 1131
250 491 1767
315 779 2806
400 1257 4524
Table 1. Halton Max Ultra Circular (MUC) factory settings

Halton Max Ultra Circular (MUC) - Quick guide for commissioning
6
2.0
All rights reserved ©Halton
3.1.3 Airflow control panel
Halton Max Ultra Circular (MUC) airflow controller has a control panel with a display and four pushbuttons.
Fig. 2. Control panel
The LCD display can show 16 characters in 2 lines.
▪Press the OK button to move to the next view. Press the ESC button to move to the previous view.
▪Press the left or right arrow buttons to move between different parameter settings.
▪When the 'Settings' view is displayed, press the OK button to see the controller parameter menu.
▪If no button is pressed, the display goes back into the default view.
▪LED signal lights indicate Modbus communication:
▪The red light indicates RS-485 Rx communication packet from master.
▪The green light indicates RS-485 Tx communication packet to master.

Halton Max Ultra Circular (MUC) - Quick guide for commissioning
7
2.0
All rights reserved ©Halton
No. Description
1Default view
2Software version
3Measured airflow in m/s
4
Measured airflow in m3/h
5Measured airflow in l/s
6Damper blade position (0-100%)
7Measured temperature
8Measured room temperature
9Settings view
1
2
3
Air flow (AF)
. m
3
/s *{CtrlSig}
4
Air flow (AF)
. l/s *{CtrlSig}
5
6
7
Aux. temperature
. % *{CtrlSig}
8
9
Butto
S1
n
Settings
“OK” to enter
Air speed
. m/s *{CtrlSig}
Air temperature
. °C *{CtrlSig}
Damper position
. % *{CtrlSig}
LAC1.U01
FW ver: 01
Halton
3.1.4 Airflow control panel: start-up views
Fig. 3. Halton Max Ultra Circular (MUC) start-up views
▪Press the OK button to move to the next view. Press the ESC button to move to the previous view.
▪Press the left or right arrow buttons to move between different parameter settings.
▪When the 'Settings' view is displayed, press the OK button to see the controller parameter menu.

Halton Max Ultra Circular (MUC) - Quick guide for commissioning
8
2.0
All rights reserved ©Halton
3.1.5 Modbus RTU communication
The Halton Max Ultra Circular (MUC) airflow control damper can communicate with the Building Management
System (BMS) via Modbus RTU. With the Modbus register, you can read and configure parameter values.
The default communication settings are Slave-ID 1, 115200bsp, O (Odd), 8 (bit), 1 (stop bit).
You can change the communication settings on the correct parameter pages of the Halton Max Ultra Circular
(MUC) controller:
▪Controller support slave ID: 1..247
▪Communication speed: 4k8 / 9k6 / 14k4 / 19k2 / 38k4 / 56k0 / 57k6 / 115k2
▪Parity: None / Even / Odd
There can be up to 64 devices in one Modbus RTU bus. The length and quality of the bus cable as well as other
disturbances can affect the maximum number of devices. The shortest poll time of the controller is 200 ms.
To configure parameters using Modbus, you need to send a password to MUC before it approves the changes.
When configuring the Holding register or Coils, first send the register value you want to change. After that, send
value 9055 to Holding register 40905, then send value 0 to Holding register 40905.
3.1.6 Self-diagnosis function
Halton Max Ultra Circular (MUC) includes an advanced self-diagnosis function for monitoring the controller's own
performance.
If the controller is installed in a location where the airflow is highly turbulent and the air velocity is high
(approximately 10 m/s), it can cause a wrong kind of measurement action to the sensor. In cases like this, the self-
diagnosis function restarts the measurement sensors. During the restart process, the damper blade goes into the
close position for 1 second, then continues normal operation.
If the airflow continues to be highly turbulent, the controller goes into 'Service request' mode after three sensor
restarts. In 'Service request' mode, text Fault 7 is showing on the controller display and the damper blade goes into
the 30% open position. You can reboot the 'Service request' mode in the following ways:
▪In the controller parameter menu
▪By rebooting the controller
▪With a Modbus parameter
▪By using the scheduled restart function
For instructions, see Rebooting the controller and Configuring the scheduled restart function.

Halton Max Ultra Circular (MUC) - Quick guide for commissioning
9
2.0
All rights reserved ©Halton
3.2 Step by step instructions
3.2.1 Configuring basic controller settings in analog mode
1. Go to the controller parameter menu.
2. Set parameter CtrlMode to 'Analog'.
3. Check the values of the following parameters. If needed, modify the values.
▪Control signal range (AI1rg)
▪Possible values: 0..10V / 2..10V
▪Default: 0..10V
▪Minimum flow setting Vmin (AI1min)
▪Default: Vmin=0
▪Maximum flow setting Vmax (AI1max)
▪Default: Vmax=Vnom
▪Feedback signal range (AO1rg)
▪Possible values: 0..10V / 2..10V
▪Default: 0..10V
4. To ensure accurate measurement results, select the correct installation case and set the value of parameter
SelectDuctType accordingly.
▪Possible values: #0..#51
▪Default: #0
▪For information on the installation cases and their corresponding SelectDuctType parameter values,
see chapter Halton Max Ultra Circular (MUC) installation cases in Technical reference data.
3.2.2 Configuring basic controller settings in Modbus mode
See also Modbus RTU communication.
1. Go to the controller parameter menu.
2. Set parameter CtrlMode to 'Modbus'.
3. To ensure accurate measurement results, select the correct installation case and set the value of parameter
SelectDuctType accordingly.
▪Possible values: #0..#51
▪Default: #0
▪For information on the installation cases and their corresponding SelectDuctType parameter values,
see chapter Halton Max Ultra Circular (MUC) installation cases in Technical reference data.
4. Check the values of the following Modbus RTU parameters. If needed, modify the values.
▪Slave ID (SlvID)
▪Possible values: 1..247
▪Default: 1

Halton Max Ultra Circular (MUC) - Quick guide for commissioning
10
2.0
All rights reserved ©Halton
▪Baud rate (Baud)
▪Possible values: 4k8 / 9k6 / 14k4 / 19k2 / 38k4 / 56k0 / 57k6 / 115k2
▪Default: 115k2
▪Parity (Pr )
▪Possible values: None / Even / Odd
▪Default: Odd
3.2.3 Configuring basic controller settings in console mode (service or testing)
1. Go to the controller parameter menu.
2. Set parameter CtrlMode to 'Console'.
3. Set the value of the setpoint parameter SP.
▪Default: Vnom
4. To ensure accurate measurement results, select the correct installation case and set the value of parameter
SelectDuctType accordingly.
▪Possible values: #0..#51
▪Default: #0
▪For information on the installation cases and their corresponding SelectDuctType parameter values,
see chapter Halton Max Ultra Circular (MUC) installation cases in Technical reference data.
3.2.4 Calculating the airflow control and feedback signals
With these formulas, you can calculate the airflow control and feedback signals when using the analog mode.
1. Calculate the airflow control signal.
▪If you use a 0-10 DC control signal, use the following formula:
▪If you use a 2-10 DC control signal, use the following formula:
2. Calculate the airflow feedback signal.
▪If you use a 0-10 DC feedback signal, use the following formula:
▪If you use a 2-10 DC feedback signal, use the following formula:

Halton Max Ultra Circular (MUC) - Quick guide for commissioning
11
2.0
All rights reserved ©Halton
3.2.5 Rebooting the controller
1. Go to the controller parameter menu.
2. Press the left arrow button, the right arrow button, and the OK button at the same time for 2 seconds.
The second level of the controller parameter menu opens.
3. Set parameter Recal. Pos to 'Yes'.
The controller restarts.
3.2.6 Configuring the scheduled restart function
You can set the controller to restart at scheduled intervals.
For more information, see Self-diagnosis function.
1. Go to the controller parameter menu.
2. Press the left arrow button, the right arrow button, and the OK button at the same time for 2 seconds.
The second level of the controller parameter menu opens.
3. Select parameter Actuator param. > Recal., then set a value (hours between restarts).
▪Value range: 0-999 hours
▪Default value: 0 hour (no scheduled restarts)
4 Troubleshooting
Problem Possible cause Possible solution
No values on the
controller display
Missing power Check the power supply.
Measured airflow
values are out of
tolerance
Installation location Check the installation case and make
sure the correct parameter value is
used. See Halton Max Ultra Circular
(MUC) installation cases.
Fault 7 showing on the
controller display
The controller is in 'Service request'
mode. For more information, see Self-
diagnosis function.
Reboot the controller. For instructions,
see Rebooting the controller.

Halton Max Ultra Circular (MUC) - Quick guide for commissioning
12
2.0
All rights reserved ©Halton
5 Technical reference data
5.1 Controller connections
Connection diagram
Fig. 4. Halton Max Ultra Circular (MUC) connection diagram
Terminals
Terminal Name Comment
1GND Ground
224 V DC/AC Power supply input
3GND Ground
4Standard RS-485 B Data receive/send line B -
5Standard RS-485 A Data receive/send line A +
6GND Ground
7** AI3 Input for NTC 10k temperature sensor
8GND Ground
9AI1 Input for airflow or damper control signal
10 GND Ground
11
AO1
Output for airflow or damper feedback signal
12* AI2 Analog actuator feedback signal
13* AO2 Analog actuator reference signal
14* GND Ground
15* 24 V DC/AC Power supply output for the analog actuator
* Connected to Siemens GDB 161.1E actuator ** Not included in delivery

Halton Max Ultra Circular (MUC) - Quick guide for commissioning
13
2.0
All rights reserved ©Halton
5.2 Parameters
5.2.1 Halton Max Ultra Circular (MUC) installation cases
Installation case
Sensor
position
Safety distance
(L)
Value of
parameter
SelectDuctType
-> 7D #0
-1D #1
1D..7D #2
-1D #3
2D #4
3D #5
3D..7D #6
Outwards 1D #7
2D #8
3D #9
5D #10
5D..7D #11
Inwards 1D #12
2D #13
3D #14
5D #15
5D..7D #16
Side 1D #17
2D #18
3D #19
5D #20
5D..7D #21

Halton Max Ultra Circular (MUC) - Quick guide for commissioning
14
2.0
All rights reserved ©Halton
Installation case
Sensor
position
Safety distance
(L)
Value of
parameter
SelectDuctType
Outwards 1D #22
2D #23
3D #24
5D
#25
5D..7D #26
Inwards 1D #27
2D #28
3D #29
5D #30
5D..7D #31
Side 1D #32
2D #33
3D #34
5D #35
5D..7D #36
Outwards
1D #37
2D #38
3D #39
5D #40
5D..7D #41
Inwards
1D #42
2D #43
3D #44
5D #45
5D..7D #46
Side
1D #47
2D #48
3D #49
5D #50
5D..7D #51
Other manuals for Max Ultra Circular
1
Table of contents
Popular Industrial Equipment manuals by other brands

S&C
S&C TripSaver II Installation, Operation, and Configuration

Piranha
Piranha MegaFab IRONWORKER P-50 Instructions And Repair Parts

Danfoss
Danfoss BHO 64A instructions

Electrocorp
Electrocorp Clean Breeze III Operation and maintenance manual

Fast & Fluid Management
Fast & Fluid Management SO-300 manual

Siemens
Siemens SINUMERIK 808D installation manual