HDL BusPro SB-DN-PM3P01 User manual

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter–User Manual
INDEX
1. Overview.......................................................................................................................1
1.1 General Information ............................................................................................. 1
1.1.1 Description................................................................................................. 1
1.1.2 Mounting....................................................................................................1
1.1.3 Serial Numbers..........................................................................................2
1.2 Functionnalities Description................................................................................. 2
1.3 Device Description...............................................................................................3
2. Safety Instructions.........................................................................................................3
3. Technical Data............................................................................................................... 4
4. Installation.....................................................................................................................5
4.1 Wiring...................................................................................................................5
4.2 HDL Bus Pro Description ..................................................................................... 6
4.3 Commissioning ....................................................................................................6
5. Software Configuration.................................................................................................. 7
5.1 Basic Information................................................................................................. 7
5.1.1 Change the ID of the device ...................................................................... 7
5.1.2 Date Settings.............................................................................................7
5.2 Status Information................................................................................................7
5.2.1 Status Information......................................................................................7
5.2.2 Other Information.......................................................................................8
5.3 Functional Logic................................................................................................... 9
5.3.1 Logic information .......................................................................................9
5.3.2 Logic Settings............................................................................................9
5.3.3 Relation.................................................................................................... 10
5.3.4 Trigger targets..........................................................................................10
5.3.5 Application ............................................................................................... 11
5.4 View Power Consumption..................................................................................12
5.5 Adjust Power Meter............................................................................................13
6. Note ............................................................................................................................14

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 1
1. Overview
1.1 General Information
1.1.1 Description
Intelligent digital power meter which has the functions of electric parameter measurement
and record. It can be used for power consumption recording and it can record one year
power consumption. And the current, voltage, power and power factor can be also
measured by the meter. The current, voltage, power consumption, time, UV Switch, etc
can be set as the logic input. The extra current transformer can be added for high power
detection.
1.1.2 Mounting
Standard 35mm Din Rail Installation
Inside Distribution Box (DB)

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 2
1.1.3 Serial Numbers
SB-DN-PM1P03 SB-DN-MP3P01
1.2 Functionnalities Description
Can measure the voltage, current, power, active power, reactive power, apparent
power, power factor, etc.
24 Logic Blocks: The Phase voltage, current of each channel, time, channel electric
degree in specified time interval, Universal Switch can be used as the logic inputs to
trigger the control targets. The logic relation can be AND, OR.
Recorded data can be stored for one year. The record can be checked by month, day,
hour, minute from application software.
Single phase
3 Separate Channels
Max. 16A per channel
Three phase
1 Channel per Phase
Max. 10A per channel

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 3
1.3 Device Description
2. Safety Instructions
Screw down strength is less than 0.4Nm
Installation Position: Distribution Box (DB )
Do not make wrong connection on Bus interface, it will damage the Bus interface of
this module
Never let liquids get into the module, it will damage this device
Do not get AC power into Bus wire , it will damage all of devices in the system
Avoid contact with liquids and aggressive gas
○
aLive/Neutral line
○
bCurrent IN/OUT Port
○
cLED Indicator
○
dProgramming Button
○
eHDL-Buspro
○
f5A Relay Output

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 4
3. Technical Data
SB-DN-PM1P03 SB-DN-PM3P01
Electric Parameters
Working voltage DC12~30V
BUS power consumption 60mA/DC24V
Measuring voltage AC 0~250V
Maximum current in each channel 16A 10A
Environmental Conditions
Working temperature 0℃~45℃
Working relative humidity Up to 90%
Storage temperature -20℃to +60℃
Storage relative humidity Up to 93%
Approved:
CE
RoHS
Production Information:
Dimensions 72×90×66 (mm)
Housing material Nylon, PC
Installation 35mm DIN rail installation

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 5
Protection degree IP20
4. Installation
4.1 Wiring
SB-DN-PM1P03:
SB-DN-PM3P01:
Connection for power meter
without current transformer
Connection for power meter
with current transformer
Connection of 3 Phase – 4 wire
Power Meter without current transformer
Connection of 3 phase – 4 wire
Power Meter with current transformer

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 6
4.2 HDL Bus Pro Description
Connector Information
buspro
DC24V Red
COM Black
DATA - White
DATA + Yellow
4.3 Commissioning
Method One:
a) open the HDL-BUS Pro Setup tool.
b) keep pressing the programming button for 3 seconds, it turns to red color.
c) on the software, click the “Address management”, and select the “Modify address
(when device button is pressed)”, it will show a window like this:
d) click the “Indicate initial address”, then it will show the ID of this device. If you want to
modify the address, fill in the new address, and click the “Modify initial address”. Click the
“+Add” button, the device will be add in “ON-line devices” list.
Method Two:
a) open the HDL-BUS Pro Setup tool.
b) click the search button, it will show a new window, click fast search button,search the
online devices. Click the “Add all”button, the devices which be searched will be added in
“ON-line devices” list.

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 7
5. Software Configuration
5.1 Basic Information
5.1.1 Change the ID of the device
Every HDL-BUS device has one Subnet ID and one Device ID, the Device ID should be
unique in its subnet and the Subnet ID should be kept consistent with the Gateway
(typically the SB-DN-1IP or HDL-MBUS01IP.431).
5.1.2 Date Settings
Build-in clock chip, can set Date and Time manually or read it from PC, the password for
save is 85521566. It also can broadcast time to system.
Warning: Recommend to set time before using, if change time when in use, the record
data will be messed.
5.2 Status Information
5.2.1 Status Information
Can check each channel’s information from this window

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 8
5.2.2 Other Information
- Detect Interval Time Setup
Interval time to refresh the information, setting range is 1-60s
- Clear the Electricity Degree
Clear the active and inactive electricity degree to 0, needs to wait for 13s when clearing.
1 column: clear channel1’s active and inactive electricity degree to 0
2 column: clear channel2’s active and inactive electricity degree to 0
3 column: clear channel3’s active and inactive electricity degree to 0
Clear total: clear all channels’ active and inactive electricity degree to 0
- Rate of the Current and Power
The external current transformation ratio, when use current transformer, the transformer
should be corrected as
If the connected current transformation ratio is 10, then the detected current of power
meter is up to 10*16A=160A .
When there is no current transformer, the rate should be 1.

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 9
5.3 Functional Logic
You can set up to 24 logics and in each logic you can combine up to 7 inputs (conditions),
trigger up to 10 targets when the logic is true and another 10 targets when false.
5.3.1 Logic information
- Logic No.
Up to 24 logic blocks
- Remark
You can make some remarks for the logic blocks
- Current Status
You can set current logic to be valid or invalid
5.3.2 Logic Settings
There are 7 conditions, select the conditions you need. The details are as follows.
- Voltage (V)
Condition is satisfied when the voltage is in the range you set.
- Chn 1 Current (A)
Condition is satisfied when chn 1 current is in the range you set.

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 10
- Chn 2 Current (A)
Condition is satisfied when chn 2 current is in the range you set.
- Chn 3 Current (A)
Condition is satisfied when chn 3 current is in the range you set.
- Time Setting
Can set different time type as a condition, some of them can combine the power
consumption of each channel together to be one condition.
- Days of the Week
Can set days of the week as a condition, they are: Sunday, Monday, Tuesday, Wednesday,
Thursday, Friday and Saturday.
- UV switch
Use UV switch as a condition, setting range is 1-254, and the status can be on or off.
5.3.3 Relation
If more than one conditions are selected, you can set the logic relationship between them
as ‘AND’ or ‘OR’
- AND
Only when all the conditions are satisfied, the logic is ‘true’
- OR
Once one condition is satisfied, the logic is ‘true’
5.3.4 Trigger targets
No matter the logic is true or not, you can trigger the targets you want
- Logic True Delay
When the logic is true, you can choose to delay some certain time before triggering
targets. Setting range: 0-36000s
- Trigger when True
When the logic is true, you can set up to 10 targets to trigger

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 11
- Logic False Delay
When the logic is false, you can choose to delay some certain time before triggering
targets. Setting range: 0-36000s
- Trigger when False
When the logic is false, you can set up to 10 targets to trigger
5.3.5 Application
Use one button to enable/disable the power saving mode, when in power saving mode, if
channel A’s detected current is between 10A to 16A during weekend, turn off some lights
and AC.
a) Use one button to send out UV Switch No.20 to power meter module to enable/disable
the power saving mode, key mode ’single on/off’, parameter1 ‘20’, parameter2 ‘ON’.
b) Enable Chn1 current from 10 to 16A, ‘Sunday’ and ‘Saturday’ , and UV Switch 20 ‘ON’
as three input conditions

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 12
c) Select the relation between them as ‘AND’, better to set some delay, here is 10s.
d) Turn off relay module’s chn1 and chn2, turn off AC in ‘Trigger when true’ window
5.4 View Power Consumption
Can check each channel’s power consumption every 5 minutes, every hour, every day,
every month and every week in HDL BUS setup tool. Also can check the power
consumption from the application software, e.g iLife.
Here check channel1’s power consumption by Day, from 2014-09-01 to 2014-09-04.
a) Select Channel No.1
b) Select ‘Query by Day’ in ‘Format Select’ line
c) Select 2014-09-01 for ‘Start Time’, 2014-09-04 for ‘End Time’
d) Click ‘Read’
e) View channel1’s day power consumption from the TChart, also the total power

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 13
consumption upon the TChart.
5.5 Adjust Power Meter
Use special equipment to adjust the parameters when in factory, the password: 85521566.
Do not allow to modify them when the power meter is in use.

User Manual
SB-DN-PM1P03 / SB-DN-PM3P01
Intelligent Digital Power Meter – User Manual 14
6. Note
……………………………………………………………………………………………………….
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
………………………………………………………………………………………………………
Other manuals for BusPro SB-DN-PM3P01
1
This manual suits for next models
1
Table of contents
Other HDL Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Trans-Tek
Trans-Tek LS502-E instruction manual

C-SCOPE
C-SCOPE CS990XD operating instructions

Kyoritsu Electrical Instruments Works, Ltd.
Kyoritsu Electrical Instruments Works, Ltd. KEW SNAP 2007A instruction manual

Delta OHM
Delta OHM HD2124.1 operating manual

Hillrom
Hillrom Welch Allyn TM286 Instructions for use

Spot-on
Spot-on 29360 product manual