Heatmiser UH4 User manual

Model: UH4

Wiring Centre2
UH4 – Installation Manual
Description
The UH4 is an 4 Zone & Hot water wiring centre for use with Heatmiser
230v thermostats.
The UH4 can be used to control any actuator or valve which requires
a 230v AC signal to open. For mid position valves and those requiring
a closing signal, a changeover relay is required. At the same time the
UH4 oers the ability to operate a boiler or other heat source through
a volt free output.
An additional output designed for use with underoor heating
systems, is also included as standard. This is the pump/valve Output,
which would normally operate a manifold pump or a manifold valve.
The H/W output provides a 230v hot water enable signal to the valve,
the auxiliary wires of the valve are wired to the Gr & Or terminals.
Zone 4 can be used as an isolated radiator zone by using the
Yes/No switch.
If the switch is set to NO;
When zone 4 calls for heat this will provide an output to a radiator
zone valve and the boiler but WILL NOT enable the underoor heating
pump/valve output.
If the switch is set to YES;
When Zone 4 calls for heat, this will act as an underoor heating zone,
by enabling the actuator, boiler and pump/valve outputs.
Any output which is not needed can be ignored.

3Model: UH4
Installation
The UH4 can be mounted directly to a wall using four screws or
alternatively, the unit can be DIN rail mounted.
When DIN Rail mounting, you first need to insert the two clips
provided on the back of the UH4, as shown in the image;
• On the back of the UH4, position the clip in the middle
and slide down.
• Points A and B locate in the corresponding holes and
lock into place.
• Locate the UH4 onto the DIN rail from the top.
• Pull the clip down and push the bottom of the UH4 onto
the DIN rail.
• Releasing the clip will lock the UH4 in place on the DIN rail.
To remove the UH4, pull both clips down and remove from the DIN rail.
B
A
Insert clip here.
Then Slide down to lock in place.

Wiring Centre4
H/W
This output is used to control a hot water valve via a cylinder
thermostat
L = Live
E = Earth
N = Neutral
Gr = Grey
Or = Orange
The auxiliary wires of the valve, usually grey & orange, are wired to the
Gr & Or terminals.
Zones 1…4
Zones outputs are clearly marked
L = live out to actuator or valve
N = neutral to actuator or valve
There are two connections live (L) and neutral (N), both terminals
marked L are the same and both terminals marked N are the same.
Each zone output corresponds to the thermostat wired in at the
top of the pcb.
Connections
Mains Supply
Power supply into the UH4 which should be fused at 5 amps these
connections are marked
L = live or phase 230v AC 50/60Hz
N = Neutral
E = Earth
Heat Enable
This is the main call for heat for the system, there are 3 connections;
LS = Live Supply
E = Earth
LR = Live Return
Electrically this is a volt free switch, whatever supply is placed on the
LS connection, is fed to the LR connection when there is a call for heat.
UH4 Wiring

5Model: UH4
Manifold Pump/Valve
Used for an underoor heating manifold pump and or valve.
Connections are clearly marked
L = Live
E = Earth
N = Neutral
When an under-oor heating zone sends a call for heat to the UH4, the
live & neutral output will supply 230v to the manifold pump/valve.
It is recommended that this is fed through a high limit switch placed
on the heating manifold, to protect against mechanical failure of the
manifolds temperature control.
Fuses
Fuse 1. 5amp, 20mm anti-surge fuse, this fuse supplies
power to all 230v outputs from the board it protects the zone,
pump/valve outputs.

Wiring Centre6
MANIFOLD PUMP
OR VALVE
ZONE 2 ZONE 3 HOT WATER VALVEZONE 4ZONE 1
BOILER
POWER
ZONE 4 MANIFOLD PUMP CONTROL SWITCH
SELECT YES FOR UNDERFLOOR HEATING
AND NO FOR ALL OTHER SYSTEMS
HEAT ENABLE
MAINS
SUPPLY
BOILER
ENABLE
MAINS
NNNNN
NN NNN
--- -1A1A1A1A-A1 2TR2TR2TR2TR 1TR1TR1TR1TR2TR 2A2A2A2A1TRA2
LSLS SLSLSL
ZONE 3 HOT WATERZONE 4ZONE 2ZONE 1
LLLLL
EE EELLE LLL
LLLL LLLL N
L
L
L
GR
E
ELS LR E
E
NNNN N
NO
YES
NNN OR
N
N
LL
LNN
N
ZONE 2ZONE 2
ZONE 1
VALVE WITH
ENDSWITCH
HOT WATER STAT
HOT WATER VALVE
UFH PUMP
UFH
RADIATOR
VALVE
THREE CORE AND
EARTH 1.5 CABLE
NEO STAT
UFH
NEO STAT
UFH
NEO STAT
RADIATOR
NEO STAT
TIMER
NEO STAT
NOTE
THE HOT-WATER VALVE LIVE FEED MUST BE
CONNECTED THROUGH THE CYLINDER HIGH
LIMIT THERMOSTAT
ACTUATORS
230V
ACTUATORS
230V
ACTUATORS
230V
5A FUSE
LS AND LR IS
VOLT FREE
EARTH
END SWITCH AND
BOILER ENABLE
UFM UNDER FLOOR MANIFOLD
LIVE
SWITCH LIVE
NEUTRAL
UFH VALVE
Wiring UH4 – UH4 to neoStat – 3 x Underfloor Heating, 1 x Radiator zone & Hot Water.
(Manifold Valve & Pump connections)
This equipment should be installed by an appropriately
qualied/registered electrician.
Fully read the instructions for proper wiring before applying power.
The warranty does not cover damage from improper wiring
or installation.
MANIFOLD PUMP
OR VALVE
ZONE 2 ZONE 3 HOT WATER VALVEZONE 4ZONE 1
BOILER
POWER
ZONE 4 MANIFOLD PUMP CONTROL SWITCH
SELECT YES FOR UNDERFLOOR HEATING
AND NO FOR ALL OTHER SYSTEMS
BOILER
MAINS
SUPPLY
BOILER
ENABLE
MAINS
NNNNN
NN NNN
--- -1A1A1A1A-A1 2TR2TR2TR2TR 1TR1TR1TR1TR2TR 2A2A2A2A1TRA2
LSLS SLSLSL
ZONE 3 HOT WATERZONE 4ZONE 2ZONE 1
LLLLL
EE EELLE LLL
LLLL LLLL N
L
L
L
GR
E
ELS LR E
E
NNNN N
NO
YES
NNN OR
N
N
LL
LNN
N
ZONE 2ZONE 2
ZONE 1
VALVE WITH
ENDSWITCH
HOT WATER STAT
HOT WATER VALVE
UFH PUMP
UFH
RADIATOR
VALVE
THREE CORE AND
EARTH 1.5 CABLE
NEO STAT
UFH
NEO STAT
UFH
NEO STAT
RADIATOR
NEO STAT
TIMER
NEO STAT
NOTE
THE HOT-WATER VALVE LIVE FEED MUST BE
CONNECTED THROUGH THE CYLINDER HIGH
LIMIT THERMOSTAT
ACTUATORS
230V
ACTUATORS
230V
ACTUATORS
230V
5A FUSE
LS AND LR IS
VOLT FREE
EARTH
END SWITCH AND
BOILER ENABLE
UFM UNDER FLOOR MANIFOLD
LIVE
SWITCH LIVE
NEUTRAL

7Model: UH4
MANIFOLD PUMP
OR VALVE
ZONE 2 ZONE 3 HOT WATER VALVEZONE 4ZONE 1
BOILER
POWER
ZONE 4 MANIFOLD PUMP CONTROL SWITCH
SELECT YES FOR UNDERFLOOR HEATING
AND NO FOR ALL OTHER SYSTEMS
HEAT ENABLE
MAINS
SUPPLY
BOILER
ENABLE
MAINS
NNNNN
NN NNN
--- -1A1A1A1A-A1 2TR2TR2TR2TR 1TR1TR1TR1TR2TR 2A2A2A2A1TRA2
LSLS SLSLSL
ZONE 3 HOT WATERZONE 4ZONE 2ZONE 1
LLLLL
EE EELLE LLL
LLLL LLLL N
L
L
L
GR
E
ELS LR E
E
NNNN N
NO
YES
NNN OR
N
N
LL
LNN
N
ZONE 2ZONE 2
ZONE 1
VALVE WITH
ENDSWITCH
HOT WATER STAT
HOT WATER VALVE
UFH PUMP
UFH
RADIATOR
VALVE
THREE CORE AND
EARTH 1.5 CABLE
NEO STAT
UFH
NEO STAT
UFH
NEO STAT
RADIATOR
NEO STAT
TIMER
NEO STAT
NOTE
THE HOT-WATER VALVE LIVE FEED MUST BE
CONNECTED THROUGH THE CYLINDER HIGH
LIMIT THERMOSTAT
ACTUATORS
230V
ACTUATORS
230V
ACTUATORS
230V
5A FUSE
LS AND LR IS
VOLT FREE
EARTH
END SWITCH AND
BOILER ENABLE
UFM UNDER FLOOR MANIFOLD
LIVE
SWITCH LIVE
NEUTRAL
UFH VALVE

Wiring Centre8
ZONE 4 MANIFOLD PUMP CONTROL SWITCH
SELECT YES FOR UNDERFLOOR HEATING
AND NO FOR ALL OTHER SYSTEMS
N
N
NN
N-
--- 1A
1A
NCA1
TR1A
RT2RT2RT RT1RT1
A2
A2 COMNOA2
A2
L
L
LL
L
NO
YES
L
L
L
N
N
N
ZONE 2
ZONE 2
ZONE 1
VALVE WITH
ENDSWITCH
HOT WATER STAT
HOT WATER VALVE
RADIATOR
VALVE
UH4
NOTE
THE HOT-WATER VALVE LIVE FEED MUST BE
CONNECTED THROUGH THE CYLINDER HIGH
LIMIT THERMOSTAT
ACTUATORS
230V
ACTUATORS
230V
ACTUATORS
230V
UFH UFH
UFH HEATING HOT WATER
NEOSTATTOUCH
SLIMLINEDS1
SMART STAT
HEAT ENABLE
MAINS
SUPPLY
BOILER
ENABLE
UFH PUMP
THREE CORE AND
EARTH 1.5 CABLE
5A FUSE
LS AND LR IS
VOLT FREE
MANIFOLD PUMP
OR VALVE
BOILER
POWER ZONE 1
ZONE 1
MAINS
LEN
LEN SL
LLN N
ZONE 2
ZONE 2
LEN SL
LLN N
ZONE 3
ZONE 3
LEN SL
LLN N
ZONE 4
ZONE 4
LEN SL
LLN N
HOT WATER
HOT WATER VALVE
LEN SL
LEN GR OR
LEN
LS ELR
UH4 – Heatmiser 230v Thermostat Wiring
This equipment should be installed by an appropriately
qualied/registered electrician.
Fully read the instructions for proper wiring before applying power.
The warranty does not cover damage from improper wiring
or installation.
MANIFOLD PUMP
OR VALVE
ZONE 2 ZONE 3 HOT WATER VALVEZONE 4ZONE 1
BOILER
POWER
ZONE 4 MANIFOLD PUMP CONTROL SWITCH
SELECT YES FOR UNDERFLOOR HEATING
AND NO FOR ALL OTHER SYSTEMS
BOILER
MAINS
SUPPLY
BOILER
ENABLE
MAINS
NNNNN
NN NNN
--- -1A1A1A1A-A1 2TR2TR2TR2TR 1TR1TR1TR1TR2TR 2A2A2A2A1TRA2
LSLS SLSLSL
ZONE 3 HOT WATERZONE 4ZONE 2ZONE 1
LLLLL
EE EELLE LLL
LLLL LLLL N
L
L
L
GR
E
ELS LR E
E
NNNN N
NO
YES
NNN OR
N
N
LL
LNN
N
ZONE 2ZONE 2
ZONE 1
VALVE WITH
ENDSWITCH
HOT WATER STAT
HOT WATER VALVE
UFH PUMP
UFH
RADIATOR
VALVE
THREE CORE AND
EARTH 1.5 CABLE
NEO STAT
UFH
NEO STAT
UFH
NEO STAT
RADIATOR
NEO STAT
TIMER
NEO STAT
NOTE
THE HOT-WATER VALVE LIVE FEED MUST BE
CONNECTED THROUGH THE CYLINDER HIGH
LIMIT THERMOSTAT
ACTUATORS
230V
ACTUATORS
230V
ACTUATORS
230V
5A FUSE
LS AND LR IS
VOLT FREE
EARTH
END SWITCH AND
BOILER ENABLE
UFM UNDER FLOOR MANIFOLD
LIVE
SWITCH LIVE
NEUTRAL

9Model: UH4
ZONE 4 MANIFOLD PUMP CONTROL SWITCH
SELECT YES FOR UNDERFLOOR HEATING
AND NO FOR ALL OTHER SYSTEMS
N
N
NN
N-
--- 1A
1A
NCA1
TR1A
RT2RT2RT RT1RT1
A2
A2 COMNOA2
A2
L
L
LL
L
NO
YES
L
L
L
N
N
N
ZONE 2
ZONE 2
ZONE 1
VALVE WITH
ENDSWITCH
HOT WATER STAT
HOT WATER VALVE
RADIATOR
VALVE
UH4
NOTE
THE HOT-WATER VALVE LIVE FEED MUST BE
CONNECTED THROUGH THE CYLINDER HIGH
LIMIT THERMOSTAT
ACTUATORS
230V
ACTUATORS
230V
ACTUATORS
230V
UFH UFH
UFH HEATING HOT WATER
NEOSTATTOUCH
SLIMLINEDS1
SMART STAT
HEAT ENABLE
MAINS
SUPPLY
BOILER
ENABLE
UFH PUMP
THREE CORE AND
EARTH 1.5 CABLE
5A FUSE
LS AND LR IS
VOLT FREE
MANIFOLD PUMP
OR VALVE
BOILER
POWER ZONE 1
ZONE 1
MAINS
LEN
LEN SL
LLN N
ZONE 2
ZONE 2
LEN SL
LLN N
ZONE 3
ZONE 3
LEN SL
LLN N
ZONE 4
ZONE 4
LEN SL
LLN N
HOT WATER
HOT WATER VALVE
LEN SL
LEN GR OR
LEN
LS ELR
Ratings
Number of Heating Zones 4
Number of Hot Water Zones 1
Neon Indication Y
DIN Rail Mounting Y
Supply 230v AC 50Hz 1 Phase
Relay Load Max 3 Amp Resistive
Total Load Max 5 Amp Resistive
IP Protection IP20
Installed Dimensions (L,H,D) 384 x 148 x 60mm
Weight 800g

Wiring Centre10
System Configuration PLEASE COMPLETE DURING INSTALLATION
UH4 Title:
In Use Zone Type Zone Title
Under-Floor Radiator
Zone 1
Zone 2
Zone 3
Zone 4
Hot Water

11Model: UH4
Notes
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................
............................................................................................................................................................................................................................................................................................................................................

Rev 1.1
DS-1NeoStat Touch SmartStatSlimline
Want More Information?
Products Commonly used with the UH4 wiring centre.
PDF FAQ VIDEO
Call our support team on: +44 (0)1254 669090
Or view technical specifications directly on our website:
www.heatmiser.com
Twitter: @heatmiseruk Facebook: facebook.com/thermostats
Table of contents
Popular Heater manuals by other brands

FMC
FMC Econat C-15 User manual & certificate of warranty

Fagor
Fagor TRV-200 Instructions for use

Zodiac
Zodiac Heat Line 20 Instructions for installation and use

flowair
flowair LEO S1 Technical documentation operation manual

Pinnacle Products International
Pinnacle Products International Heat-Stream HS-18-PCH-A User's manual and operating instructions

Dyna-Glo
Dyna-Glo RMC-KFA50DGD User's manual and operating instructions