SWITCH-CONTROL FOR THE CONTROL OF COLOUR TEMPERATURE AND INTENSITY
Dimming the intensity
• Short press ON / OFF < 1 s → Switch the lights ON/OFF, ON level is always with last level setting of intensity and colour
temperature
• Changing the intensity
• Long press > 1s → Lights dims always first down, next long press lights dim up
Changing the colour temperature
• Long press > 1s dimming direction have to be up
• Hold the button → the light goes to full intensity
• Hold the button for addional 6 sec→ colour temperatures jumps to coldest colour temperature
• Still hold the button→ colour temperature changes from cold to warm
• Releasing the button sets the new colour temperature.
or
• Press and hold button > 1s → The lights dims slowely from min. to max. Hold the button for addional 6 second the
colour temperature change starts
RESET OF SWITCH-CONTROL IN IC DRIVERS
The intensity and/or CCT values of the various drivers might go out of sequence with time due to differences in the cable-
inductances of individual luminaires. In this case press and hold the Switch-Control until all lights are ON. Then perform a normal
colour temperature setting as described above. This will bring all lights back into synchronisation again.
You can as an alternative synchronisation carry out a power reset. Switching the mains OFF and ON will perform a reset of both
light intensity and colour temperature to the default factory setting providing “power on to last level “ is deactivated.
APPLICATION CONSIDERATIONS
• Cable length in a Switch-Control 2 installation is not restricted by the driver technology, but it must be always ensured that the
actual installation fulfills the relevant national legislation regulations regarding short-circuit current to ensure proper fuse
or MCB operation in case of a fault condition.
• If the length and the characteristics of the cabling in the Switch-Control 2 installation cause substantial induced voltages in
the cables (e.g. very long cables), this may introduce risks for the driver electronic circuit damages. In these cases Helvar
recommends using the X2 rated capacitor connected across the Switch-Control input, as instructed in more detail on page 1.
• Switch-Control or Switch-Control 2 circuits shall not be operated with push-buttons that include internal indicator bulbs /
lights sources.
UG22 001 1B 05.12.2018