HVM0009 Rev. 011519 www.hessaire.com
Tools/Materials Needed:
• Drill/drill bits/phillips bit
• Ratchet/Socket set
Contents:
• Exhaust Fan(1)
• Instruction manual(1)
Instruction Manual: Galvanized Slant Wall
Exhaust Fans - Direct Drive
Model Numbers Covered:
36DSW370, 48SWD750, 48SWD750T
Please read and save these instructions. Read carefully before attempting to assemble,
install, operate or maintain the equipment described within this manual. Carefully follow all
safety information.
Save this manual for future reference.
Model # ________________________________Purchase Date:____________________
General Safety Instructions
Warning:
1. Before installing or servicing, disconnect all power. Keep hands and body parts clear of all moving parts when installing or servicing.
2. Read and follow all instructions, cautions, dangers and warnings. Failure to do so could result in personal injury, death or property damage.
3. Make sure the electrical power source conforms to the requirement of the fan(s) as well as local codes.
4. Electrical connections, installation and maintenance must be done by qualified electrical personnel in accordance with all applicable codes.
5. Unit must be adequately grounded.
6. To reduce the risk of fire or electrical shock, do not expose this fan to water.
7. Do not touch electrically live components.
8. Free rotation of the propeller is critical. It must not touch any part of the venturi or framework.
9. Assure that all power cords do not come in contact with any sharp edges, hot surfaces or chemicals. Immediately replace any damaged cords.
10. Keep hands and body parts clear of all moving parts when installing or servicing.
Specifications(See Dimension Key On Following Page)
Dimension (In.) Rough-in Opening
Model Prop
Dia.
# Of
Wings
A
(In.)
B
(In.)
AA
(In.)
BB
(In.)
C
(In.)
D
(In.)
E
(In.)
F
(In.) Height Width Ship
Wt
Ship.
Dims.
36SWD370 36” 3 44 45 1/4 39 1/2 40 1/8 27 16 3/4 4 1/2 45 3/4 42 7/8 40 7/8 140 48x32x51
48SWD750 48” 2 56 57 7/8 51 1/2 53 1/4 29 1/4 15 5/8 3 58 1/8 55 1/2 52 7/8 260 60x34x62
48SWD750T 48” 2 56 57 7/8 51 1/2 53 1/4 29 1/4 15 5/8 3 58 1/8 55 1/2 52 7/8 260 60x34x62
Caution: OSHA requires OSHA compliant guards within 7ft of the floor or working level.
Inspection:
After unpacking your fan, carefully inspect for any damage that may have occurred during transit. Inspect for loose, missing or damaged parts.
If there is physical damage to any parts of the fan, a freight claim must be filed with the carrier. Check to assure that all bolts, screws and set
screws are securely tightened and have not become loose during transit. Retighten as required.
High CFM CFM/Watt
Model HP Spd F.L.A. Volt. Ph Hz Fan
RPM
0.00"
SP
0.05"
SP
0.10"
SP
0.15"
SP
0.00"
SP
0.05"
SP
0.10"
SP
0.15"
SP
Db @
7ft
Bess Labs
Test #
36SWD370 1/2 1 5.2/2.6 115/230 1 60 825 10,770 10,100 9,390 8,640 19.3 17.4 15.5 13.8 76 16137
48SWD750 1 1 11.0/5.5 115/230 1 60 850 19,100 17,900 16,500 14,900 18.1 16.5 14.8 13.1 80 16143
48SWD750T 1 1 5.6/2.8 230/460 3 60 850 19,050 17,850 16,425 14,820 18 16.4 14.7 13 80 -
Performance