Chapter 1 Meter Overview
DZS100-4P is an advanced, smart single-phase DIN rail energy meter. It meters electric
parameters of single-phase current, voltage, power, energy, frequency, power factor etc.
with high accuracy. It is LCD display and also equipped with RS485 communication and
pulse output.
Its main functions are as follows:
◆Measure import active energy and export active energy;
◆Measure combination of active energy, which is equal to the sum of import active energy
and export active energy
◆Measure all instantaneous values of electric parameters, including voltage, current,
power, energy, frequency, power factor etc.;
◆LCD displaying voltage, current, power etc..
◆Automatically blocking and saving the blocked energy of last 12 months
◆Timing Records with saving last 10 times of recording moments
◆Loading data storage with recording data such as voltage, current, power, frequency,
power factor and active energy;
◆Compatible with DL/T645-2007, DL/T645-1997 and Modbus-RTU protocols.
Chapter 2 Specification & Technical Parameters
2.1 Specification (the following parameters are subject to marks on nameplate)
Reference Voltage: AC220V(Un)
Current Specification: 1.5(6)A, 5(40) A, 10(80) A (which can be customized)
Frequency: 50Hz
Pulse Constant: 6400/1600/800imp/kWh (in the light of marks on nameplate)
Accuracy Class: Class 1.0
2.2 Technical Parameters
Starting Current: 0.004Ib
Insulation Strength: input to output, 2.0kV/min·1mA
Power Consumption: <2W,10VA
Creeping: Equipped with anti-creep logic circuits, when the energy meter loads 115% of
rated voltage and there is no current in current circuit, the energy meter shouldn’t output
more than one pulse in testing within the prescribed time.
Voltage Range: 0.9~1.1Un; limit range: 0.8~1.2Un
Communication Mode: RS485
Reference Temperature: 23℃±2℃;
Reference Humidity: 40%~60%RH
Working temperature: -20℃~50℃
Storage Temperature: -40℃~70℃ with relative humidity less than 85% and no corrosive