HIK VISION DS-PDSMK-S-WE User manual

2
Audible and Visual Alarm Indicators
When operang normally, a red LED adjacent to the Test buon will flash every 320 s. When smoke is detected, an internal sounder will acvate to alert occupants, and
the LED will flash rapidly. The sounder is a loud, pulsang alarm and produces a repeang Temporal 3 audible signal paern (0.5 s on, 0.5 s off for 3 cycles, followed by
1.5 s off, repeang).
Test/Hush BuonWhen there is no alarm present, hold the Test/Hush buon will acvate the smoke alarm to check its operaon. The alarm will sound and the LED will
flash rapidly. The unit will return to normal condion in about 10 s when the test is completed.
When the smoke alarm is in the Alarm condion, press the Test/Hush buon will hush the smoke alarm for approximately 11 min. The Hush feature should only be
used aer the cause of the alarm is known (such as normal cooking fumes). The Hush feature allows me for the smoke to clear. During the hush me, the LED will flash
twice every second. Aer the Hush me has expired, the smoke alarm will return to normal sensivity. If smoke is sll present in the unit, the alarm will re-acvate. The
Hush feature can be used repeatedly.
Smoke Chamber Fault
The detector monitors the condion of the smoke sensing chamber. If the smoke sensing chamber ceases to operate normally, the smoke alarm will emit a short
audible signal, then followed by a single Red LED indicator flash, repeang every 40 s. In this case, try vacuuming clean the detector to remove dust. If the condion
persists, replace the detector with a new unit.
Low Baery
When the baery is depleted, the detector will emit a short audible signal and the Red LED indicator flash, repeang every 40 s for at least 30 days. Interconnected
detector will also emit two short audible signals and the Red LED indicator will flash twice, repeang every 4 hours. When the Low Baery signal is given, replaced the
detector with a new unit.
Interconnecon
Wireless interconnecon allows up to 12 detectors to be connected together. Interconnected detector will acvate sounders on all units if any smoke alarm detector. In
this case, only the detector that detected smoke will flash the Red LED. This allows the home owner to quickly locate the cause of the alarm.
Local alarm memory
Aer alarm occurs, the green LED gives 3 flashes every 40 s up to 24 h, which stops flashing aer 24 hours. Any me before the next alarm, press the Test buon, the
detector shall emit 3 audible beeps every 1 s. Release of the Test buon shall reset the alarm.
Funcon
1Appearance
DS-PDSMK-S-WE
Wireless Photoelectric Smoke Detector
Diagram References
ENGLISH
©2020 Hangzhou Hikvision Digital Technology Co., Ltd. All rights reserved.
About this Manual
The Manual includes instrucons for using and managing the Product. Pictures, charts, images and all other informaon hereinaer are for descripon and explanaon only. The informaon contained in the Manual is subject to change,
without noce, due to firmware updates or other reasons. Please find the latest version of this Manual at the Hikvision website (hps://www.hikvision.com/).
Please use this Manual with the guidance and assistance of professionals trained in supporng the Product.
and other Hikvision's trademarks and logos are the properes of Hikvision in various jurisdicons. Other trademarks and logos menoned are the properes of their respecve owners.
Disclaimer
TO THE MAXIMUM EXTENT PERMITTED BY APPLICABLE LAW, THIS MANUAL AND THE PRODUCT DESCRIBED, WITH ITS HARDWARE, SOFTWARE AND FIRMWARE, ARE PROVIDED “AS IS” AND “WITH ALL FAULTS AND ERRORS”. HIKVISION MAKES
NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WITHOUT LIMITATION, MERCHANTABILITY, SATISFACTORY QUALITY, OR FITNESS FOR A PARTICULAR PURPOSE. THE USE OF THE PRODUCT BY YOU IS AT YOUR OWN RISK. IN NO EVENT WILL
HIKVISION BE LIABLE TO YOU FOR ANY SPECIAL, CONSEQUENTIAL, INCIDENTAL, OR INDIRECT DAMAGES, INCLUDING, AMONG OTHERS, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION, OR LOSS OF DATA, CORRUPTION OF
SYSTEMS, OR LOSS OF DOCUMENTATION, WHETHER BASED ON BREACH OF CONTRACT, TORT (INCLUDING NEGLIGENCE), PRODUCT LIABILITY, OR OTHERWISE, IN CONNECTION WITH THE USE OF THE PRODUCT, EVEN IF HIKVISION HAS BEEN
ADVISED OF THE POSSIBILITY OF SUCH DAMAGES OR LOSS.
YOU ACKNOWLEDGE THAT THE NATURE OF INTERNET PROVIDES FOR INHERENT SECURITY RISKS, AND HIKVISION SHALL NOT TAKE ANY RESPONSIBILITIES FOR ABNORMAL OPERATION, PRIVACY LEAKAGE OR OTHER DAMAGES RESULTING FROM
CYBER-ATTACK, HACKER ATTACK, VIRUS INSPECTION, OR OTHER INTERNET SECURITY RISKS; HOWEVER, HIKVISION WILL PROVIDE TIMELY TECHNICAL SUPPORT IF REQUIRED.
YOU AGREE TO USE THIS PRODUCT IN COMPLIANCE WITH ALL APPLICABLE LAWS, AND YOU ARE SOLELY RESPONSIBLE FOR ENSURING THAT YOUR USE CONFORMS TO THE APPLICABLE LAW. ESPECIALLY, YOU ARE RESPONSIBLE, FOR USING THIS
PRODUCT IN A MANNER THAT DOES NOT INFRINGE ON THE RIGHTS OF THIRD PARTIES, INCLUDING WITHOUT LIMITATION, RIGHTS OF PUBLICITY, INTELLECTUAL PROPERTY RIGHTS, OR DATA PROTECTION AND OTHER PRIVACY RIGHTS. YOU
SHALL NOT USE THIS PRODUCT FOR ANY PROHIBITED END-USES, INCLUDING THE DEVELOPMENT OR PRODUCTION OF WEAPONS OF MASS DESTRUCTION, THE DEVELOPMENT OR PRODUCTION OF CHEMICAL OR BIOLOGICAL WEAPONS, ANY
ACTIVITIES IN THE CONTEXT RELATED TO ANY NUCLEAR EXPLOSIVE OR UNSAFE NUCLEAR FUEL-CYCLE, OR IN SUPPORT OF HUMAN RIGHTS ABUSES.
IN THE EVENT OF ANY CONFLICTS BETWEEN THIS MANUAL AND THE APPLICABLE LAW, THE LATER PREVAILS.
This product and - if applicable - the supplied accessories too are
marked with "CE" and comply therefore with the applicable harmonized
European standards listed under the EMC Direcve 2014/30/EU, the RE
Direcve 2014/53/EU, the RoHS Direcve 2011/65/EU.
replacement of a baery with an incorrect type that can defeat a safeguard (for example, in the case of some lithium
baery types);
– disposal of a baery into fire or a hot oven, or mechanically crushing or cung of a baery, that can result in an
explosion;
– leaving a baery in an extremely high temperature surrounding environment that can
result in an explosion or the leakage of flammable liquid or gas; and
– a baery subjected to extremely low air pressure that may result in an explosion or the leakage of flammable liquid
or gas
2012/19/EU (WEEE direcve): Products marked with this symbol
cannot be disposed of as unsorted municipal waste in the European
Union. For proper recycling, return this product to your local supplier
upon the purchase of equivalent new equipment, or dispose of it at
designated collecon points. For more informaon see:
www.recyclethis.info
2006/66/EC (baery direcve): This product contains a baery that cannot be disposed of as unsorted municipal
waste in the European Union. See the product documentaon for specific baery informaon. The baery is marked
with this symbol, which may include leering to indicate cadmium (Cd), lead (Pb), or mercury (Hg). For proper
recycling, return the baery to your supplier or to a designated collecon point. For more informaon see:www.recy-
clethis.info
T
E
S
T
/
H
U
S
H
Test/Hush Buon
Indicator
Coding Buon
Power Switch
replacement of a baery with an incorrect type that can defeat a safeguard (for example, in the
case of some lithium baery types);
– disposal of a baery into fire or a hot oven, or mechanically crushing or cung of a baery,
that can result in an explosion;
– leaving a baery in an extremely high temperature surrounding environment that can
result in an explosion or the leakage of flammable liquid or gas; and
– a baery subjected to extremely low air pressure that may result in an explosion or the
leakage of flammable liquid or gas
The addional force shall be equal to three mes the weight of the
equipment but not less than 50N. The equipment and its
associated mounng means shall remain secure during the
installaon. Aer the installaon, the equipment, including any
associated mounng plate, shall not be damaged.
INSTALLATION CAUTION
BATTERY CAUTION
Chemical burning danger
Do not swallow the baery.
Keep new and used baeries away from the children.
If you think baeries might have been swallowed or placed inside any part of the
body, seek immediate medical aenon.
Risk of explosion if baery is replaced by an incorrect type.
Replacement of a baery with an incorrect type that can defeat a safeguard.
Dispose of used baeries according to the instrucons and local regulaon.
If the baery compartment does not close securely, stop using the product and keep it away from children.
1116-CPR-116-2
EN14604:2005/AC:2008 20

3Enrollment
1. Log in the Hik-ProConnect, and select a site.
2. Select the AX PRO in the site.
3. Enter“Sengs-System Sengs” , and tap the "Enrollment Mode" buon to make the
AX PRO enter the enrollemnt status.
Enroll the Detector Locally
Register the Detector via APP
1. Log in the Hik-ProConnect, and select a site.
2. Select the AX PRO in the site.
3. Tap the “+” icon on the boom of the page, and scan the QR code to add the peripheral.
4. Turn the power switch of the peripheral on, and it will be automacally enrolled to the control panel.
1
2
3
Locaon and number of smoke alarms may be specified in relevant regulaons. Where these do not exist, the requirements of DIN 14676 can be used.
Before commencing installaon, ensure all equipment and tools to mount and test the device are available, such as drills, mounng screws (supplied), cables
and ladders.
According to German applicaon standard DIN 14676
Locaon Selecon
Equipment
Installaon
2
1
4
BEDROOM
CHILDREN’S
BEDROOM
CHILDREN’S
BEDROOM
LIVING ROOM
BATH-
ROOM KITCHEN
Figure 1 a) Example of the applicaon in a flat
xxxx
Device
Hold the coding buon and power the detector on at the same me. The detector will be formaed aer 8 s.
Format

Smoke alarm are to be used as minimum requirement in all bedrooms, children's rooms and hallways which act as escape routes, and are to be installed
in each case in the middle of the room, on the ceiling only (do not install on wall).
Select the installaon locaon with a minimum distance of 50 cm to surrounding walls, furniture and lamps.
Configuraon is opmal when devices are also located in all other rooms as well as staircases.
In kitchens and wet rooms, smoke alarms are only used when false alarm caused by the characteriscs of these space are excluded.
Please observe the graphics in this guide.
Install smoke alarms as close to the centre of the ceiling as possible, away from light fings and air-condioning ducts. If this is not praccal, put the alarm on the
ceiling, no closer than 50 cm from any wall or corner.
In rooms with ceiling slopes> 20 °, the smoke alarm shall be mounted at least 0.5 m and not more than 1 m away from the ceiling peak.
In rooms with sloping ceilings that is prorated, if the horizontal ceiling is ≤ 1 m wide, mount the smoke alarm as shown in Mounng for gabled ceiling with
slope > 20°. If the horizontal ceiling> 1 m wide, mount the smoke alarm in the centre on the horizontal ceiling as shown in Mounng in rooms with sloping
ceiling and horizontal ceiling.
Ceilings with a slope angle ≤ 20 ° should be treated as horizontal ceiling.
Install the smoke alarm in either le posion or right posion.
Installaon Locaon
Rooms with sloped ceiling
Figure 2 Mounng for ceiling with slope > 20° Figure 3 Mounng for gabled ceiling with slope > 20°
Figure 4 Mounng in rooms with sloping ceiling and horizontal ceiling
CHILDREN’S
BEDROOM
KITCHEN
WORKSHO
P
BOILER ROOM
LIVING ROOM
BEDROOM
Figure 1 b) Example of the applicaon in a typical single-family house
0,5m-1m
0,5m-1m
1-Smoke alarm in the le posion
2-Smoke alarm in the right posion

Nuisance alarms occur when smoke alarms are installed where they will not work properly. To avoid nuisance alarms, do not install smoke alarms in the
following situaons.
• In or near areas where combuson parcles are present, such as kitchens with few windows or poor venlaon, garages where there may be vehicle
exhaust, near furnaces, combuson heaters, and space heaters. Combuson parcles are the by-products of something that is burning, which the smoke
alarm may detect.
• Within 6 m of kitchens where combuson parcles are normally present. If a 6 m distance is not possible, e.g. in a mobile home, try to install the smoke
alarm as far away from the combuson parcles as possible. Ensure the area is well venlated.
• In dead-air areas, where venlaon systems cause air-flow that would not pass through the smoke alarm sensing chamber. Avoid also air-flow from areas
where normal combuson parcles are expected, such as kitchens.
• In damp or very humid areas, or within 3 m of bathrooms with showers. Moisture in humid air can enter the sensing chamber, then condense into droplets
upon cooling, which can cause nuisance alarms.
• In very cold or very hot areas, including unheated buildings or outdoor rooms. If the temperature rises above or falls below the operang range of smoke
alarm, it may not funcon properly. The temperature range for your smoke alarm is -10 °C ~ 60 °C.
• In very dusty or dirty areas. Dirt and dust can build up on the smoke alarm’s sensing chamber, to make it overly sensive. Addionally, dust or dirt can block
openings to the sensing chamber and limit the smoke alarm from sensing smoke.
• Near fresh air vents or high dra areas like air condioners, heaters or fans, fresh air vents and dras, which can drive smoke away from smoke alarms.
• In dead air spaces, which are oen at the top of a peaked roof or in apex of ceilings and walls. Dead air may prevent smoke from reaching a smoke alarm. See
Fig. 2, Fig. 3, Fig. 4 and Fig. 5 for recommended mounng locaon.
• In insect-infested areas. If insects enter a smoke alarm’s sensing chamber, they may cause a nuisance alarm. Where insects are a problem, get rid of them
before installing the smoke alarm.
• Near fluorescent lights. Electrical “noise” from fluorescent lights may cause nuisance alarms. Do not install smoke alarms within 1.5 m of such lights.
Where Not to Install the Smoke Detector
Figure 5 Mounng in rooms with sloping ceiling and horizontal ceiling
1.Check the signal strength.
1.Draw a 150 mm line at the required place.
2.Rotate the mounng bracket counter -clockwise and remove it from the detector.
3. Align the two longest hole slots with the drawed line. Draw a mark In each of keyhole slots.
4.Drill two 5 mm (3/16-inch) holes at the marks and insert the plasc mounng plugs (supplied).
5.Aach the bracket to the ceiling with the screws supplied.
6.Align the slot of the bracket with the detector, push the detector onto the mounng bracket,
and rotate it clockwise to finish the mounng.
Mounng with Screws
Mounng
3
Tap the Signal Strength Test in the Hik-ProConnect to enter the mode and tap the test buon:
Solid green for 3 s - Strong Signal
Flashing green for 3 s - Medium Signal
Solid red for 3 s - Weak Signal
Flashing red for 3 s - Failure
Signal Strength Test
T
E
S
T
/
H
U
S
H
T
E
S
T
/
H
U
S
H

1.Paste the sponge tape on the rear side of the detector.
2.Tear off the film.
3.Paste the detector on the required place.
Press and hold the Test/Hush buon, and the buzzer and LED will indicates the alarm.
WARNING: The smoke alarm has a loud alarm signal. Use hearing protecon when tesng smoke alarms.
Test
Mounng with Sponge Tape
4
Up to 12 smoke detectors can be interconnected, with a typical distance of 30 m indoors and 100 m in free space. Interconnecon range depends on the
building construcon, and is influenced by the building structure and any intervening structures that may absorb or reflect radio signals.
r = 100 m in free space, 30 m indoors (depending on construcon and obstrucons)
1. Turn on the power switch on the boom of the first detector.
5Interconnect Funcon Configuraon
Interconnecon limitaons
7
9
11
3
6
4 12 1
2
5
200m
8
10
3 S
1 s 1 s
0.5 s 0.5 s 0.5 s 0.5 s 0.5 s 0.5 s
……
……
T
E
S
T
/
H
U
S
H
T
E
S
T
/
H
U
S
H
>50 cm
Note: Installing with sponge tape is non EN compliant.

2. Short press down the coding buon on the boom of the first detector, the red LED flashes slowly, approximately once every one second. Release the buon
then. Noce pressing the coding buon again will end the coding process.
3. Turn on the power switch on the boom of the second detector.
4. Short press down the coding buon on the boom of the second detector, the red LED flashes slowly, approximately once every one second. Then release
the buon.
5. wait and see…
At this me, the two detectors are in the coding mode. The period of coding is about 60 seconds.
If two green LEDs of the detectors are illuminated at the same me, no flashing, which indicates that two detectors have built a new wireless interconnecon, the
coding is successful. Otherwise, aer 60 seconds, two detectors will exit the coding mode automacally, please do it again. Please noce repeated press of coding
buon will also end the coding process.
6. To connect another smoke detector. Repeat above steps. First, choose the new smoke alarm you want to add. Then choose a smoke alarm already interconnect-
ed. The new smoke alarm shall join the exisng network. Repeat the above steps for other interconnected smoke alarms (up to 12).
7. Once all smoke alarms are interconnected, press the Test/Hush on each smoke alarm, and check the smoke alarm sounder operates on all interconnected smoke
alarms.
8. Check that the red LED adjacent to the Test/Hush buon operates only on the smoke alarm being tested.
Smoke detectors should be interconnected within only one family residence. Otherwise, you might encounter nuisance alarms when a smoke detector is
operated or tested in another residence.
>50 cm
T
E
S
T
/
H
U
S
H
>50 cm
T
E
S
T
/
H
U
S
H
>50 cm
T
E
S
T
/
H
U
S
H
T
E
S
T
/
H
U
S
H
>50 cm

1. Vacuum or carefully wipe the cover of the smoke detector to remove any dust, lint or dirt around the openings of the smoke detector. Do not spray aerosols
into the smoke detector.
2. Aer annual maintenance, test all smoke detectors.
Before using the Hush feature, idenfy the source of smoke and be certain that safe condions exist.
Never use a naked flame of any kind to test your smoke alarm. You may set fire to and damage the smoke alarm, as well as your home. The built-in
Test/Hush buon accurately tests all alarm funcons.
Once installed and tested, the detector will immediately start monitoring for smoke. If the sounder in the detector operates, check for a fire and execute your
safety plan.
If the detector was caused by a nuisance situaon, open a window or fan the air to remove the smoke or dust from within the smoke detector. The detector will
turn off as soon as the air is completely clear. Do not disconnect the baery to silence the smoke detector.
If invesgaon shows the alarm signal is likely caused by a known nuisance source (such as cooking fumes), the Test/Hush buon can be pressed to silence the
smoke alarm for 11 min.
Aer the Hush me has expired, the smoke alarm will return to normal sensivity. If smoke is sll present, the alarm will be re-acvated. The Hush feature can
be used repeatedly.
1. Press and hold the Test/Hush buon on each smoke alarm.
2. Check the smoke detector sounder operates with a loud audible signal paern (0.5 s on, 0.5 s off for 3 cycles, followed by 1.5 s off, repeang) sound, and the
red LED adjacent to the Test/Hush buon flashes twice every second.
3. For interconnected smoke detectors, check the smoke detector sounder operates on all interconnected detector and the red LED adjacent to the Test/Hush
buon operates only on the smoke detector being tested. Repeat the test on all interconnected smoke alarms.
Hush
8Protecon From Fire
6
Operaons
7Care and Maintenance
Weekly Tests
Annual Maintenance
When the baery is depleted, the smoke detector will emit a short audible signal, and the LED indicator will flash once every 40 s for at least 30 days. When the
low baery signal is given, change the smoke detector without delay. The baery is not user-replaceable.
Where smoke detectors are connected together and a Low Baery Alert occurs on any individual unit, other interconnected smoke detectors will emit a double
beep and the LED a double flash signal 4 hours aer the inial low baery warning. The signals will repeat every 4 hours.
Installing smoke alarms is only one step in protecng your family from fires. You should also reduce the chances that fires will start in your home and you must
increase your chances of escaping safely if one does start. The following informaon will help you develop a fire safety program.
1. Install smoke alarms properly. Carefully follow all the instrucons in this manual. Keep your smoke alarms clean, and test them every week.
2. Non-working smoke alarms will not alert you. Replace your smoke alarms immediately if they are not working properly.
3. Follow fire safety rules, and prevent hazardous situaons:
• Use smoking materials properly. Never smoke in bed.
• Keep matches and cigaree lighters away from children.
• Store flammable materials in proper containers. Never use them near open flames or sparks.
• Keep electrical appliances in good condion. Do not overload electrical circuits.
• Keep stoves, fireplaces, chimneys, and barbecue grills grease free. Make sure they are properly installed and away from any combusble materials.
• Keep portable heaters and open flames such as candles away from combusble materials.
• Do not allow rubbish to accumulate.
• Keep a supply of extra baeries on hand for your baery powered smoke alarms.
Prepare and pracce a family escape plan. Review the following with your children each me you have fire escape drills. This will help everyone remember them
in case of a real fire emergency.
1. Don’t panic and stay calm. Your safe escape may depend on thinking clearly and remembering what you have pracced.
2. Get out of the house as quickly as possible. Follow a planned escape route. Do not stop to collect anything or to get dressed.
3. Feel the doors to see if they are hot. If they are not, open them carefully. Do not open a door if it is hot. Use an alternate escape route.
4. Stay close to the floor. Smoke and hot gases rise.
5. Cover your nose and mouth with a wet or damp cloth. Take short, shallow breaths.
6. Keep doors and windows closed. Open them only if you have to in order to escape.
7. Meet at your planned meeng place aer leaving the house.
8. Call the Fire Service as soon as possible from outside your house. Give the address and your name.
9. Never go back inside a burning building.
10. Contact your local Fire Service. They will give you more ideas about how to make your home safer from fires and how to plan your family’s escape.
If a Smoke Chamber Fault occurs, vacuum the cover of the smoke detector to remove any dust, lint or dirt around the openings. If the fault connues, replace
the smoke detector.
Low Baery Alert
Smoke Chamber Fault
Low Baery Alert With Interconnected Smoke Alarms

9Indicaon Decripon
Normal Off 1 flash every320s
0.5 son,0.5 sofffor 3cycles, then 1.5 s
off(repeang unl manual hush or smoke dissipated) 2 flashesevery1 s
For other interconnectedsmoke alarms:
0.5 son,0.5 sofffor 3cycles, then 1.5 s
off(repeat 3 mes)
For other interconnected
smoke alarms: Off
0.5 son,0.5 sofffor 3cycles, then 1.5 s
off(repeang)
2 flashesevery1 s
For other interconnectedsmoke alarms:
0.5 son,0.5 sofffor 3cycles, then 1.5 s
off(repeang)
For other interconnected
smoke alarms: Off
HushOff 2 flashesevery1 s
For the smoke alarmwith the depleted
baery: 1 audible beep every40 s
(synchronously with the LED)
For the smoke alarmwith the
depletedbaery: 1 flash every
40 s(synchronously with the
sounder)
For other interconnectedsmoke alarms:
2 audible beepsevery4h
(synchronously with LED)
For other interconnected
smoke alarms: 2 flashesevery
4h (synchronously with
sounder)
Codingin progress Off 1 flash every1 sup to 60 s
Codingsuccessful 1 shortbeep Off On for 10s
Anyme before the next alarm, press
the Test buon,3audible beepsevery1 s
Release ofthe Test buon shall resetthe
alarm
End-of-life3audible beepsevery40 s
Factorydefault
sengs
1 audible beep 2 flashesevery1 s
Localalarm
memory
3flashesevery40 s
up to 24h
Condion
Alarm
Test
1 audible beep every40 s(separately to
the LED)
1 flash every40 s(separately
to the sounder)
Smoke chamber
fault
Lowbaery
Sounder Indicaon RedLED Green LED

10 Specificaon
Detecon Method
Chamber With Photoelectric Sensor
EnvironmentTemperature
Indicator
Support
SignalStrength Indicator
Support
Power Switch
Power Up Enrolling
LED Indicator
Red(Alarm)
Buzzer
≥85dB @ 3m
Transmission Method
Two-WayRF Wireless
Transmission Frequency
868MHz
Transmission Security
AES-128Encrypon
Transmission Range(Free Space)
800m
EnrollingMethod
Power up,Remote ID,QR Code
Power Supply
BaeryPowered
BaeryType
Non Replaceable CR17450 x1
TypicalVoltage
3V
StandardBaeryLife 10 Years
Operaon Temperature
-10°C to 60 °C (14°F to 140°F)
Storage Temperature
-20°C to 60 °C (-4 °F to 140 °F)
Operaon Humidity
10% to 90%
Dimension(WxHxD)
φ102 × 35mm
Weight
125g
MounngMethod
Ceiling
Applicaon Scenario
Indoor
Version: 1.2
2020-10-23
Table of contents
Other HIK VISION Smoke Alarm manuals
Popular Smoke Alarm manuals by other brands

Kidde
Kidde Signature Series Installation sheet

Digital Monitoring Products
Digital Monitoring Products 521LX Installation

SpreadNet
SpreadNet SN980-SMOKE installation instructions

Fire-Lite Alarms
Fire-Lite Alarms BG-12LR manual

Ei Electronics
Ei Electronics Ei 156TLR Optical quick start guide

Notifier
Notifier CP-651 Installation and maintenance instructions