Simplex 4098-9019 Operating instructions

Introduction
This document contains:
• The wiring instructions needed to connect the 4098-9019 Motorized Infrared Optical Beam Smoke Detector System to a compatible Simplex
Fire Alarm Control Panel (FACP).
• The Beam Detector programming instructions for the FACP programmer.
For information pertaining to the installation, alignment, local controller programming and operation, please consult the other documents included
with this product.
Compatibility
This product is compatible with:
• 4100ES and 4010ES Control Panels / System Firmware 2.02 or higher.
• 4007ES Control Panel / all revisions.
• 4100ES System Power Supplies (SPS) / Firmware 3.12.05 or higher.
• 4010ES Extended System Supply (ESS) / all revisions.
• 4010ES Main System Supply (MSS) / Firmware 3.12.05 or higher.
• 4010ES Main System Supply 2 (MSS2) / all revisions.
• Separate IDNet/IDNet+/IDNet 1+ modules / Firmware 3.12.05 or higher.
• IDNet communications PCC Chip 0742-146 / Revision 2.02.03 or higher.
• IDNet 2+2 / all revisions.
Note: Refer to Appendix A: Compatible Module Identification for additional reference.
Electrical Specifications
The following consumption figures are based are on a 2 detector system across the operating voltage range.
• Voltage: 14 VDC - 36 VDC
• Maximum operating current: 50 mA
579-1039 Rev. D
4098-9019 IDNet Addressable Beam Detector Wiring and FACP Programming
*05791039D*

Wiring Specifications
Figure 1 depicts the wiring diagram that must be used when adding this device to an IDNet circuit.
Figure 1: Device Wiring on a IDNet Circuit
Consult Table 1 for the type of wiring needed to connect the FACP to the Beam Detector System Controller.
Table 1: Wiring Type
Card Type Wiring Type Reference Manual
IDNet 14 AWG -18 AWG Shielded Twisted Pair 574-800
IDNet+ 14 AWG -18 AWG Twisted Pair 579-786
IDNet1+ 14 AWG -18 AWG Twisted Pair 579-1014
IDNet 2+2 14 AWG -18 AWG Twisted Pair 579-1169
Note: Refer to the appropriate IDNet Card manual for the maximal wiring distances.
page 2 579-1039 Rev. D
4098-9019 IDNet Addressable Beam Detector Wiring and FACP Programming

IDNet LEDs and Addressing
Figure 2: LED and Address Switch Location
LEDs:
Remove the Beam Detector’s cover to access the LEDs.
• IDNET1: This red LED corresponds to the head connected to DET1 on the device. When lit, it indicates a trouble or an alarm on the DET1
channel.
• IDNET2: This red LED corresponds to the head connected to DET2 on the device. When lit, it indicates a trouble or an alarm on the DET2
channel.
Addressing:
This device has a unique address that is set via an eight-position DIP switch. Position 1 is the least significant bit (LSB) and position 8 is the most
significant bit (MSB).
To set the address:
1. Retrieve the address from the ES Programmer. Use the first address assigned by the programmer if multiple addresses are required for the
device (see Programming and Editing the device point).
2. Use a small screwdriver or pen to set the switches to the address.
3. Record the set address.
page 3 579-1039 Rev. D
4098-9019 IDNet Addressable Beam Detector Wiring and FACP Programming

Figure 3: Setting the Address
Programming and Editing the device point
To program or edit this device from the ES Programmer, follow these steps:
1. Open an already existing job or create a new one.
2. Click on the Programmer’s Hardware tab.
3. Click on the Grid View subtab at the bottom of the Hardware tab field.
4. Go to the IDNet channel that you are adding the device to and double click on it. The card properties window will open.
5. Click on the card’s Point Editing tab.
page 4 579-1039 Rev. D
4098-9019 IDNet Addressable Beam Detector Wiring and FACP Programming

Figure 4: Accessing the IDNet Channel
Figure 5: Accessing the Point Editing Tab
6. Use the options in the Point Editing tab, shown in Figure 6, to edit the following:
- Device Type. Click on the Device Type drop down list box and select BEAM.
- Point Type. Click on the Point Type drop down list box and select a point type.
• Select FBEAM for the Beam Detector
• Select LSBEAM for the Latched Supervisory Beam Detector
• Select UBEAM for the Utility Beam Detector
- Custom Label. Assign a customized label to the device point.
- Alternate custom Label. Define an alternate label of up to 40 characters for the point, typically the function, location, or other descriptive
text.
- PNIS Code. Allows selection of the PNIS code for the point*.
- Primary Action message. This selection assigns a Primary State Action Message to the point*.
- Trouble Action message. This selection assigns a Trouble Action Message to the point*.
Note: For more information on point editing consult the ES Programmer manual.
page 5 579-1039 Rev. D
4098-9019 IDNet Addressable Beam Detector Wiring and FACP Programming

Figure 6: The Point Editing Tab
7. Setting the address:
The Beam Detector System requires two addresses per device:
- One address for the device and the “first” head. This address will also be the one associated with the address switch.
- One address for the second head on the device reporting to the system.
Both of the addresses for one same device must be added consecutively when programming the job. However, each head can be programmed for a
separate point type, either “fire”, “latched supervisory”, or “utility”.
Note: A warning pop-up will appear with the notification that the device requires more than one address, prompting you to click Yes if you wish to
continue. You must click on Yes in order to install the device.
Figure 7: Multiple Address Prompting
Panel Operation
Each device head will appear on the FACP as an IDNet BEAM device type.
Since there are no trouble or alarm conditions specific to the system controller, all information can be reported against one of the heads. When the
Beam Detector controller is physically missing or has failed, each head will have a “no answer” trouble for a total of up to two troubles.
The following operations can be performed from the FACP:
page 6 579-1039 Rev. D
4098-9019 IDNet Addressable Beam Detector Wiring and FACP Programming

Table 2: Addressable Beam Detector FACP Operations
Operations Status Name State Point Type
Acknowledge the Beam device from
the panel
n/a n/a n/a
Disable and enable each head n/a Enabled / Disabled /
Trouble
Trouble
Turn off and on each device LED n/a n/a n/a
Measure the signal strength** Signal Strength% 0 to 100 n/a
Measure the compensation level** Compensation Level -50 to 205 n/a
Edit the almost dirty threshold Almost Dirty Threshold -50 to 205 (default = 100) n/a
Report the smoke status Smoke Status NORMAL, FIRE Fire
Report the device communications* Device Communications NORMAL, TROUBLE Trouble
Report a rapid obscuration trouble* Rapid Obscuration NORMAL, TROUBLE Trouble
Report the self aligned status Self Aligned status FALSE, TRUE n/a
Report the almost dirty status Almost Dirty FALSE, TRUE n/a
Report the excessively dirty trouble* Excessively Dirty FALSE, TROUBLE Trouble
Report a summary trouble* Summary Trouble NORMAL, TROUBLE Trouble
Toggle the alarm test output Alarm test OFF, ON ON triggers fire
Change the priority of the device Priority 0 to 15 n/a
Add the device to the install mode
list
n/a INSTALL MODE n/a
Edit the smoke threshold*** Smoke Threshold% 10 – 60 (default = 35) n/a
* This operation can also be completed or viewed at the Beam System Controller.
** This operation can be viewed at the FACP but must be edited at the Beam System Controller.
*** The smoke threshold can also
be set through the Custom Control
option in the ES Programmer. See
the example for a sample equation.
Consult the ES Panel Programmer
Manual 547-849 for more
information on custom controls.
Example:[INPUTS]
STATUS ON
A34 l ANALOG l TIMER l SYSTEM STARTUP PULSE TIMER
[END INPUTS]
[OUTPUTS]
SET_NUMERIC_OUTPUT 1 30 PRI=9,9
M1-1-0 l BEAM l FBEAM l 1ST BEAM DETECTOR
[END OUTPUTS]
When viewing the Beam Detector information through the FACP interface, the following information can be accessed by selecting the device on the
panel and then using the “More Info” button.
page 7 579-1039 Rev. D
4098-9019 IDNet Addressable Beam Detector Wiring and FACP Programming

Figure 8: Beam Detector Information
Troubles Reported
The following trouble conditions are monitored by the FACP:
IDNet Troubles Beam Detector Troubles
No Answer Device Communications Status
Bad Answer Rapid Obscuration
Wrong Device Summary Trouble
Disable Trouble Excessively Dirty
Manual Override Trouble
Part Replacement
For replacement parts contact your certified Simplex representative.
page 8 579-1039 Rev. D
4098-9019 IDNet Addressable Beam Detector Wiring and FACP Programming

Appendix A: Compatible Module Identification
• 4100-3101 566-044 IDNet Module – 250 Devices
• 4100-3104 566-329 IDNet Module – 127 Devices
• 4100-3105 566-330 IDNet Module – 64 Devices
• 4100-5111 566-071 Expansion System Pwr Supply (SPS)
• 4100-5112 566-072 Expansion System Pwr Supply (SPS)
• 4100-5113 566-071 Expansion System Pwr Supply (SPS)
• 4100-3106 566-421 4100-3106 IDNet Module – QuickConnect2
• 4100-3107 566-675 4100-3107 IDNet+ Module – 246 Devices, Quad Isolator
• 4010-9907 566-883 4010-9907 IDNet+ Module – 246 Devices, Quad Isolator
• 650-442 566-876 Main System Supply with IDNet+ (4010ES)
• 650-442 566-1104 Main System Supply with IDNet2 (4010ES)
• 650-1300/1301 566-1025 Extended System Supply (4010ES)
page 9 579-1039 Rev. D
4098-9019 IDNet Addressable Beam Detector Wiring and FACP Programming

579-1039 Rev. D
© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Simplex®
product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and
National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).
Table of contents
Other Simplex Smoke Alarm manuals

Simplex
Simplex 2098-9207A User manual

Simplex
Simplex 4098-9601 User manual

Simplex
Simplex 2098-9650 Manual

Simplex
Simplex 4099-9004 User manual

Simplex
Simplex 50RU User manual

Simplex
Simplex LifeAlarm 4005 Series User manual

Simplex
Simplex MINIPLEX 4100ES Series User manual

Simplex
Simplex 2098-9207 User manual

Simplex
Simplex 4004 User manual

Simplex
Simplex 4100U-S1 Instruction Manual