BG-12LR and BG-12LRA Agent Release Pull Station
Patented, U.S. Patent No. Des. 428,351; 6,380,846; Other Patents Pending
Document 51370 I56-2265-003
Description
The BG-12LR and BG-12LRA Agent Release Pull Stations are designed for use with
Fire•Lite control panels that include releasing capabilities. These stations are ideally suited
for areas such as clean rooms and computer rooms, where a chemical agent is used to extin-
guish a re. Both pull stations provide a dual-action, normally open contact (N/O), release
initiating point with a key-lock reset feature. The BG-12LRA also includes a manual abort
switch, System Normal LED, and System Activated (release) LED. Both stations meet the
ADAAG controls and operating mechanisms guidelines (section 4.1.3[13]), and the ADA
requirement for a 5 lb. maximum pull force to activate the pull station. Operating instructions
are molded into the pull station handle along with Braille text. Molded terminal numbers
are also present.
Ratings
Switch contact (N/O) is gold plated for reliability and rated at 0.25 A at 30 volts (AC or
DC).
Installation
The BG-12LR pull station can be surface mounted to an SB-10 or SB-I/O surface backbox
or semi-ush mounted on a standard single-gang, double-gang or 4″ (10.16 cm) square
electrical box. The optional BG-TR trim ring can be used if the BG-12LR is to be semi-ush
mounted. The BG-12LRA must be surface-mounted to a SBA-10 backbox.
Operation
To initiate an agent release, push in and pull down on the handle. The word ‘ACTIVATED’
appears after the handle is pulled down. This will remain until the pull station is reset.
The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O)
switch which closes upon activation of the pull station.
Resetting the Pull Station
1. Insert the key into the lock and rotate 1/4 turn counterclockwise.
2. Open the door until the handle returns to normal.
3. Close and lock the door.
NOTE: Closing the door automatically resets the switch to the ‘Normal’ position. Open-
ing the door will not activate or deactivate the alarm switch.
P0219-00
STRIP GAUGE
1 2 3 4
IDC –
FROM
FACP + TO NEXT
DEVICE
– IDC
+
WARNING: DO NOT LOOP WIRING
UNDER ANY TERMINALS. BREAK WIRE
RUN TO MAINTAIN IDC SUPERVISION.
P0105-00
Wiring
CAUTION! Do not detach the door of the pull station during installation. The door of
the pull station cannot be reattached to the backplate after the backplate has already been
installed onto an electrical box.
CAUTION!
Install the Fire•Lite BG-12LR and BG-12LRA pull station in accordance with these instructions,
applicable NFPA standards, national and local Fire and Electrical codes and the requirements
of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be con-
ducted in accordance with the appropriate NFPA standards. Failure to follow these directions
may result in failure of the device to report an alarm condition. Fire•Lite is not responsible for
devices that have been improperly installed, tested or maintained.
ADA Compliance
For ADA compliance, if the clear oor space only allows forward approach to an object, the
maximum forward reach height allowed is 48 inches (121.92 cm). If the clear oor space
allows parallel approach by a person in a wheelchair, the maximum side reach allowed is
54 inches (137.16 cm).
BG-12LR
Agent Release Pull Station
WARNING! Do not loop wiring under any
terminals. Break wire run to
maintain IDC supervision.
Document 51370 I56-2265-003
Abort Feature (BG-12LRA only)
The operation and reset of the BG-12LRA agent release pull station is the same as the BG-12LR,
with the addition of the Abort Feature: The System Normal LED will stay illuminated when the
Agent Release Control Panel is “All Systems Normal.” When the station has been activated, ini-
tiating the agent release process in the control panel, the System Activated LED will illuminate.
If the control panel has been congured to abort the releasing of an extinguishing agent,
then pushing and holding-in the abort switch will cancel the agent release sequence. Please
refer to the respective agent release control panel manual for further instructions about us-
ing the Abort feature.
Abort Plate Wiring (BG-12LRA only)
Connect the wiring from the agent release control panel’s Abort Circuit to the wire leads
D&E of the normally open abort switch. Connect 24 VDC (+) to a form-c relay, this relay
shall be called the Release Relay. Connect the relay's normally closed contact to the System
Normal LED wire lead A. Connect the relays normally open contact to the System Activated
LED wire lead B. Connect the 24 VDC (–) to the LED assembly ground wire C.
A
B
C
Release Relay
(+) N.C.
24 VDC N.O.
(–)
To
Abort
Circuit
D
E10K,1/4W
Resistors
N.O. Abort Switch
System
Operated
LED (Red)
To
Manual
Release
Circuit
10K,1/4W
Resistors
*
10K
1/4W
10K
1/4W
System
Normal
LED
(Green)
*
1 2 3 4
US PAT4440991
D
BCA
DE
E
P0166-00
Normally Open
Abort Switch
P0167-00
*Mount End of line resistor on last unit.
WARNING
When used for CO2 releasing applications, observe proper precautions as stated in NFPA
12. Do not enter the protected space unless physical lockout and other safety procedures
are fully completed. Do not use software disable functions in the panel as lockout. For ADA
compliance, if the clear oor space only allows forward approach to an object, the maxi-
mum forward reach height allowed is 48 inches (121.92cm). If the clear oor space allows
parallel approach by a person in a wheelchair, the maximum side reach height allowed is
54 inches (137.16cm).
STRIP GAUGE
1 2 3 4
US PAT 4440991
––
++
To next agent release
initiating device or ELR
if last device on circuit
From agent release control panel’s
manual release circuit or previous
agent release initiating device
P0165-00

This manual suits for next models

1

Other Fire-Lite Alarms Smoke Alarm manuals

Fire-Lite Alarms D350PL User manual

Fire-Lite Alarms

Fire-Lite Alarms D350PL User manual

Fire-Lite Alarms BG-12LXSP User manual

Fire-Lite Alarms

Fire-Lite Alarms BG-12LXSP User manual

Fire-Lite Alarms OSI-RI-FL User manual

Fire-Lite Alarms

Fire-Lite Alarms OSI-RI-FL User manual

Fire-Lite Alarms OSI-RI-FL User manual

Fire-Lite Alarms

Fire-Lite Alarms OSI-RI-FL User manual

Fire-Lite Alarms BG-12LPS User manual

Fire-Lite Alarms

Fire-Lite Alarms BG-12LPS User manual

Fire-Lite Alarms 100 Series User manual

Fire-Lite Alarms

Fire-Lite Alarms 100 Series User manual

Fire-Lite Alarms 6424 User manual

Fire-Lite Alarms

Fire-Lite Alarms 6424 User manual

Fire-Lite Alarms BG-12L User manual

Fire-Lite Alarms

Fire-Lite Alarms BG-12L User manual

Fire-Lite Alarms 1400 User manual

Fire-Lite Alarms

Fire-Lite Alarms 1400 User manual

Fire-Lite Alarms BG-12LX User manual

Fire-Lite Alarms

Fire-Lite Alarms BG-12LX User manual

Fire-Lite Alarms BG-12 User manual

Fire-Lite Alarms

Fire-Lite Alarms BG-12 User manual

Fire-Lite Alarms D350P User manual

Fire-Lite Alarms

Fire-Lite Alarms D350P User manual

Popular Smoke Alarm manuals by other brands

First Alert PC900V user manual

First Alert

First Alert PC900V user manual

aguilera AE/C5-OPT Technical manual

aguilera

aguilera AE/C5-OPT Technical manual

BRK electronic FG250RV user manual

BRK electronic

BRK electronic FG250RV user manual

ADE Optima 2 Plus user guide

ADE

ADE Optima 2 Plus user guide

Kidde P3010CU user guide

Kidde

Kidde P3010CU user guide

ELRO FS1105P quick start guide

ELRO

ELRO FS1105P quick start guide

ELRO FZ500221R instruction manual

ELRO

ELRO FZ500221R instruction manual

Visonic MCT-427 features and benefits

Visonic

Visonic MCT-427 features and benefits

GST DI-9101E manual

GST

GST DI-9101E manual

Ravel RE317 Series Installation Wiring Diagram

Ravel

Ravel RE317 Series Installation Wiring Diagram

Siemens DELTA Reflex SD9 Operating and mounting instructions

Siemens

Siemens DELTA Reflex SD9 Operating and mounting instructions

bolid DIP-34SA instruction manual

bolid

bolid DIP-34SA instruction manual

merten 663819 Installation and operation instructions

merten

merten 663819 Installation and operation instructions

Firex KF30 user manual

Firex

Firex KF30 user manual

First Alert P900 user manual

First Alert

First Alert P900 user manual

Vesta SD-29-SC-AC Series quick start guide

Vesta

Vesta SD-29-SC-AC Series quick start guide

Xtralis VESDA VFT-15-C Product guide

Xtralis

Xtralis VESDA VFT-15-C Product guide

Firex ADH owner's manual

Firex

Firex ADH owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.