F3 DIO 20/8 02 3 Product Description
HI 800 345 E Rev. 2.00 Page 15 of 48
3.2 Equipment, Scope of Delivery
The following table specifies the available remote I/O variants:
Designation Description
F3 DIO 20/8 02 Remote I/O (20 digital inputs, 8 digital outputs),
Operating temperature: 0...+60 °C,
for ELOP II Factory programming tool
F3 DIO 20/8 021
(-20 °C)
Remote I/O (20 digital inputs, 8 digital outputs),
Operating temperature: -20...+60 °C,
for ELOP II Factory programming tool
F3 DIO 20/8 023 Remote I/O (20 digital inputs, 8 digital outputs),
Operating temperature: -25...+70 °C,
Salt mist resistance in accordance with IEC 60068-2-11,
for ELOP II Factory programming tool
F3 DIO 20/8 024 Remote I/O (20 digital inputs, 8 digital outputs),
Operating temperature: -25...+70 °C (temperature class T1),
Vibration and shock tested according to EN 50125-3 and EN 50155,
class 1B according to IEC 61373,
for ELOP II Factory programming tool
F3 DIO 20/8 02
SILworX
Remote I/O (20 digital inputs, 8 digital outputs),
Operating temperature: 0...+60 °C,
for SILworX programming tool
F3 DIO 20/8 021
SILworX
(-20 °C)
Remote I/O (20 digital inputs, 8 digital outputs),
Operating temperature: -20...+60 °C,
for SILworX programming tool
F3 DIO 20/8 023
SILworX
Remote I/O (20 digital inputs, 8 digital outputs),
Operating temperature: -25...+70 °C,
Salt mist resistance in accordance with IEC 60068-2-11,
for SILworX programming tool
F3 DIO 20/8 024
SILworX
Remote I/O (20 digital inputs, 8 digital outputs),
Operating temperature: -25...+70 °C (temperature class T1),
Vibration and shock tested according to EN 50125-3 and EN 50155,
class 1B according to IEC 61373,
for SILworX programming tool
Table 4: Available Variants
3.2.1 IP Address and System ID (SRS)
A transparent label is delivered with the device to allow one to note the IP address and the
system ID (SRS for system rack slot) after a change.
IP___.___.___.___SRS____.__.__
Default value for IP address: 192.168.0.99
Default value for SRS: 60 000.200.0 (SILworX)
60 000.0.0 (ELOP II Factory)
The label must be affixed such that the ventilation slots in the housing are not obstructed.
Refer to the First Steps manual of the programming tool for more information on how to modify
the IP address and the system ID.