DO 8 01 3 Product Description
HI 800 207 E Rev. 2.00 Page 17 of 34
3.5 Product Data
General
Operating voltage 1) 24 VDC, -15...+20 %, rPP 15 %, at 0…+30 °C 2)
Operating voltage 1)
increased ambient
temperature
24 VDC, ±10 %, rPP 15 %, at >30…+50 °C 3)
24 VDC, -10...-2,5 %, rPP 15 %, at >50...+60 °C 3)
Current input max. 0.7 A
Electrical isolation of the
channels
Yes
Storage temperature -40...+85 °C
Space requirement 6 RU, 4 HP
Weight 300 g
1) From a power supply unit with safe insulation in accordance with IEC 61131-2.
2) Restricted temperature range!
3) With uses at temperatures higher than 30 °C, the operating voltage is only permitted in the
specified range.
Table 7: Product Data
Relay Outputs
Number 8 potential-free normally open contacts
Execution 2 safety relays with forcibly guided contacts,
1 standard relay
Switching voltage 6 V, 250 VAC / 250 VDC
Switching current 10 mA, 3 A,
internally fused with 3.15 A
fuse breaking capacity: 100 A
Type of protection IP40
Contact material Silver alloy, flash plated
Switching time approx. 30 ms
Reset time approx. 20 ms
Bounce time approx. 30 ms
Life time
mechanical
electrical
3 x 106switching operations
see Figure 3
Table 8: Specifications for the Relay Outputs
Relay output switching capacity (general safety applications)
≤30 VDC max. 90 W (3,15 A)
≤70 VDC max. 35 W (0,5 A)
≤127 VDC max. 45 W (0,315 A)
Switching capacity DC
induction-free1)
≤250 VDC max. 60 W (0,25 A)
Switching capacity AC
induction-free 1)
≤250 VAC max. 600 VA
Switching capacity AC
cos φ> 0,5
≤250 VAC max. 400 VA
Switching capacity DC,
UL 508
30 VDC at 3 A, resistive1)
60 VDC at 0,3 A, resistive1)
1) Circuit induction-free
- Free-wheeling diode
- Use suitable protective circuit, i.g., RC elements, Zener diodes or varistors
Table 9: Relays Output Switching Capacity