Hisense DH16 User manual

Thank you very much for purchasing this dehumidifier. Please
read this use and care guide carefully before using this appliance
and keep this manual for future reference.
Hisense (Guangdong) Air Conditioning Co., Ltd.
No.8 Hisense Road Advanced Manufacturing
Jiangsha Demonstration Park,Jiangmen City,
Guangdong Province,P.R.China
,
Model:DH16

12
12
17
17
18
13
16
15
INSTALLATION REQUIREMENTS 12
Electrical Requirements
Location Requirements
DEHUMIDIFIER CARE
Cleaning the Air Filter
Cleaning the Dehumidifier
Setting the Controls
DEHUMIDIFIER USE
Draining the Dehumidifier
Normal Sounds
13
17
TROUBLE SHOOTING
DEHUMIDIFIER SAFETY
9
PRODUCT OVERVIEW 1
SAFETY PRECAUTIONS 2
TABLE OF CONTENTS
SAFETY INSTRUCTIONS
This appliance can be used by children aged from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience and knowledge
if they have been given supervision or instruction concerning use of the appliance in a
safe way and understand the hazards involved. Children shall not play with the
appliance. Cleaning and user maintenance shall not be made by children without
supervision.
Children should be supervised to ensure that they do not play with the appliance.
If the supply cord is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard. The appliance shall be
installed in accordance with national wiring regulations. The range of external static
pressures is -0.2Pa to 0.2Pa. Keep the unit 5m or more apart from combustible
surfaces.
Do not operate your air conditioner in a wet room such as a bathroom or laundry room.

SAFEGUARDING THE ENVIRONMENT
This appliance is made of recyclable or re-usable material. Scrapping must be carried
out in compliance with local waste disposal regulations. Before scrapping it, make
sure to cut off the mains cord so that the appliance cannot be re-used.
For more detailed information on handling and recycling this product, contact your
local authorities who deal with the separate collection of rubbish or the shop where
you bought the appliance.
This appliance is marked according to the European Directive 2012/19/EU, Waste
Electrical and Electronic Equipment (WEEE).
SCRAPPING OF APPLIANCE
This marking indicates that this product should not be
disposed with other household wastes throughout
the EU. To prevent possible harm to the environment
or human health from uncontrolled waste disposal,
recycle it responsibly to promote the sustainable
reuse of material resources. To return your used device,
please use the return and collection systems or contact
the retailer where the product was purchased.
They can take this product for environmental safe recycling.
CAUTION
Do not use means to accelerate the defrosting process or to clean, other than
those recommended by the manufacturer
sources(for example: open flames, an operating gas appliance or an operating
electric heater)
The appliance shall be installed, operated and stored in a room with a floor
area larger than 4 m .
Spaces where refrigerant pipes shall be compliance with national gas
regulations.
Servicing shall be performed only as recommended by the manufacturer.
The appliance shall be stored in a well-ventilated area where the room
size corresponds to the room area as specified for operation.
All working procedure that affects safety means shall only be carried by
competent persons.
The appliance shall be stored in a room without continuously operating open
flames (for example an operating gas appliance) and ignition sources (for
example an operating electric heater).
The appliance shall be so as to prevent mechanical damage from occurring.
Any person who is involved with working on or breaking into a refrigerant circuit
should hold a current valid certificate from an industry-accredited assessment
authority, which authorises their competence to handle refrigerants safely in
accordance with an industry recognised assessment specification.
Servicing shall only be performed as recommended by the equipment
manufacturer. Maintenance and repair requiring the assistance of other skilled
personnel shall be carried out under the supervision of the person competent in
the use of flammable refrigerant.
.
.
.
The appliance shall be stored in a room without continuously operating ignition
Do not pierce or burn
Be aware that refrigerants may not contain an odour.
2

NOTE:
The figures in this manual are based on the external view of a standard model. They may differ
from that dehumidifier you have selected.
Explanation of symbols displayed on the appliance:
Fuse parameter of the machine:
DH-16S4GH* (T2.5A, 250V).
WARNING
This symbol shows that this appliance uses a
flammable refrigerant.
If the refrigerant is leaked and exposed to an
external ignition source, there is a risk of fire
CAUTION This symbol shows that the operation manual
should be read carefully.
CAUTION
This symbol shows that a service personnel
should be handling this equipment with
reference to the installation manual.
CAUTION
This symbol shows that information is
available such as the operating manual or
installation manual.
Caution, risk of fire
C
Control Panel
Bucket
Air Intake Grill
and Air Filter
Removable Air Filter Handle
Handle
Power Plug
Hose Cover
User Manual
Thank you very much f or purchasing this dehumidifi er. Please
read this use and care g uide carefu lly before using this applian ce
and keep this manual f or future re ference.

Precautions for using R290 refrigerant
The basic installation work procedures are the same as the conventional refrigerant (R22 or
R410A). However, pay attention to the following points:
CAUTION
1.
Compliance with the transport regulations
2.
Compliance with local regulations
3.
Compliance with national regulations
4.
The storage of equipment should be in accordance with the manufacturer's
instructions.
5.
Storage package protection should be constructed such that mechanical
damage to the equipment inside the package will not cause a leak of the
refrigerant charge.
The maximum number of pieces of equipment permitted to be stored together
will be determined by local regulations.
6.
6-1
Prior to beginning work on systems containing flammable refrigerants, safety
checks are necessary to ensure that the risk of ignition is minimised. For repair
to the refrigerating system, the following precautions shall be complied with
prior to conducting work on the system.
6-2
Work shall be undertaken under a controlled procedure so as to minimise the
risk of flammable gas or vapour being present while the work is being
performed.
6-3
All maintenance staff and others working in the local area shall be instructed
on the nature of work being carried out. Work in confined spaces shall be
avoided.
The area around the workspace shall be sectioned off. Ensure that the
conditions within the area have been made safe by control of flammable
material.
6-4
The area shall be checked with an appropriate refrigerant detector prior to and
during work, to ensure the technician is aware of potentially flammable
atmospheres.
Ensure that the leak detection equipment being used is suitable for use with
flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically
safe.
Transport of equipment containing flammable refrigerants
Marking of equipment using signs
Disposal of equipment using flammable refrigerants
Storage of equipment/appliances
Storage of packed (unsold) equipment
Information on servicing
Checks to the area
Work procedure
General work area
Checking for presence of refrigerant
SAFETY PRECAUTIONS
2

CAUTION
6-5
If any hot work is to be conducted on the refrigeration equipment or any
associated parts, appropriate fire extinguishing equipment shall be available
to hand.
Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
6-6
No person carrying out work in relation to a refrigeration system which involves
exposing any pipe work that contains or has contained flammable refrigerant
shall use any sources of ignition in such a manner that it may lead to the risk of
fire or explosion.
All possible ignition sources, including cigarette smoking, should be kept
sufficiently far away from the site of installation, repairing, removing and
disposal, during which flammable refrigerant can possibly be released to the
surrounding space.
Prior to work taking place, the area around the equipment is to be surveyed to
make sure that there are no flammable hazards or ignition risks. “No Smoking”
signs shall be displayed.
6-7
Ensure that the area is in the open or that it is adequately ventilated before
breaking into the system or conducting any hot work.
A degree of ventilation shall continue during the period that the work is carried
out.
The ventilation should safely disperse any released refrigerant and preferably
expel it externally into the atmosphere.
6-8
Where electrical components are being changed, they shall be fit for the
purpose and to the correct specification.
At all times the manufacturer's maintenance and service guidelines shall be
followed. If in doubt consult the manufacturer's technical department for
assistance.
The following checks shall be applied to installations using flammable
refrigerants:
The charge size is in accordance with the room size within which the
refrigerant containing parts are installed;
The ventilation machinery and outlets are operating adequately and are not
obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit shall be
checked for the presence of refrigerant;
Marking to the equipment continues to be visible and legible. Markings and
signs that are illegible shall be corrected;
Refrigeration pipe or components are installed in a position where they are
unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials
Presence of fire extinguisher
No ignition sources
Ventilated area
Checks to the refrigeration equipment
–
–
–
–
–
3

CAUTION
which are inherently resistant to being corroded or are suitably protected
against being so corroded.
6-9
Repair and maintenance to electrical components shall include initial safety
checks and component inspection procedures.
If a fault exists that could compromise safety, then no electrical supply shall be
connected to the circuit until it is satisfactorily dealt with.
If the fault cannot be corrected immediately but it is necessary to continue
operation, an adequate temporary solution shall be used.
This shall be reported to the owner of the equipment so all parties are advised.
Initial safety checks shall include:
That capacitors are discharged: this shall be done in a safe manner to avoid
possibility of sparking;
That there no live electrical components and wiring are exposed while
charging, recovering or purging the system;
That there is continuity of earth bonding.
7.
During repairs to sealed components, all electrical supplies shall be
disconnected from the equipment being worked upon prior to any removal of
sealed covers, etc.
If it is absolutely necessary to have an electrical supply to equipment during
servicing, then a permanently operating form of leak detection shall be located
at the most critical point to warn of a potentially hazardous situation.
Particular attention shall be paid to the following to ensure that by working on
electrical components, the casing is not altered in such a way that the level of
protection is affected.
This shall include damage to cables, excessive number of connections,
terminals not made to original specification, damage to seals, incorrect fitting
of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no
longer serve the purpose of preventing the ingress of flammable atmospheres.
Replacement parts shall be in accordance with the manufacturer's
specifications.
NOTE:
The use of silicon sealant may inhibit the effectiveness of some types of
leak detection equipment. Intrinsically safe components do not have to be
isolated prior to working on them.
8.
Do not apply any permanent inductive or capacitance loads to the circuit
without ensuring that this will not exceed the permissible voltage and current
permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while
Checks to electrical devices
Repairs to sealed components
Repair to intrinsically safe components
–
–
–
4

CAUTION
live in the presence of a flammable atmosphere. The test apparatus shall be at
the correct rating.
Replace components only with parts specified by the manufacturer.
Other parts may result in the ignition of refrigerant in the atmosphere from a
leak.
9.
Check that cabling will not be subject to wear, corrosion, excessive pressure,
vibration, sharp edges or any other adverse environmental effects.
The check shall also take into account the effects of aging or continual
vibration from sources such as compressors or fans.
10.
Under no circumstances shall potential sources of ignition be used in the
searching for or detection of refrigerant leaks.
A halide torch (or any other detector using a naked flame) shall not be used.
11.
The following leak detection methods are deemed acceptable for systems
containing flammable refrigerants:
Electronic leak detectors shall be used to detect flammable refrigerants, but
the sensitivity may not be adequate, or may need re-calibration. (Detection
equipment shall be calibrated in a refrigerant-free area.)
Ensure that the detector is not a potential source of ignition and is suitable
for the refrigerant used.
Leak detection equipment shall be set at a percentage of the LFL of the
refrigerant and shall be calibrated to the refrigerant employed and the
appropriate percentage of gas (25 % maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use
of detergents containing chlorine shall be avoided as the chlorine may react
with the refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed/ extinguished.
If a leakage of refrigerant is found which requires brazing, all of the
refrigerant shall be recovered from the system, or isolated (by means of shut
off valves) in a part of the system remote from the leak.
Oxygen free nitrogen (OFN) shall then be purged through the system both
before and during the brazing process.
12.
When breaking into the refrigerant circuit to make repairs – or for any other
purpose – conventional procedures shall be used.
However, it is important that best practice is followed since flammability is a
consideration.
The following procedure shall be adhered to:
Remove refrigerant;
Purge the circuit with inert gas;
Cabling
Detection of flammable refrigerants
Leak detection methods
Removal and evacuation
–
–
–
–
–
–
–
–
–
5

CAUTION
–
–
–
–
–
–
–
–
–
Evacuate;
Purge again with inert gas;
Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders.
The system shall be “flushed” with OFN to render the unit safe.
This process may need to be repeated several times.
Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and
continuing to fill until the working pressure is achieved, then venting to
atmosphere, and finally pulling down to a vacuum.
This process shall be repeated until no refrigerant is within the system. When
the final OFN charge is used, the system shall be vented down to atmospheric
pressure to enable work to take place.
This operation is absolutely vital if brazing operations on the pipe-work are to
take place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources
and there is ventilation available.
13.
In addition to conventional charging procedures, the following requirements
shall be followed:
Ensure that contamination of different refrigerants does not occur when
using charging equipment.
Hoses or lines shall be as short as possible to minimise the amount of
refrigerant contained in them.
Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed prior to charging the system
with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system it shall be pressure tested with OFN.
The system shall be leak tested on completion of charging but prior to
commissioning.
A follow up leak test shall be carried out prior to leaving the site.
14.
Before carrying out this procedure, it is essential that the technician is
completely familiar with the equipment and all its detail.
It is recommended good practice that all refrigerants are recovered safely.
Prior to the task being carried out, an oil and refrigerant sample shall be taken in
case analysis is required prior to re-use of reclaimed refrigerant. It is essential
that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
Charging procedures
Decommissioning
6

CAUTION
c) Before attempting the procedure ensure that:
Mechanical handling equipment is available, if required, for handling
refrigerant cylinders;
All personal protective equipment is available and being used correctly;
The recovery process is supervised at all times by a competent person;
Recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes
place.
g) Start the recovery machine and operate in accordance with manufacturer's
instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
I ) Do not exceed the maximum working pressure of the cylinder, even
temporarily.
j ) When the cylinders have been filled correctly and the process completed,
make sure that the cylinders and the equipment are removed from site
promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system
unless it has been cleaned and checked.
15.
Equipment shall be labelled stating that it has been de-commissioned and emptied
of refrigerant.
The label shall be dated and signed.
Ensure that there are labels on the equipment stating the equipment contains
flammable refrigerant.
16.
When removing refrigerant from a system, either for servicing or
decommissioning, it is recommended good practice that all refrigerants are
removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed.
Ensure that the correct number of cylinders for holding the total system charge
is available.
All cylinders to be used are designated for the recovered refrigerant and
labelled for that refrigerant (i.e. special cylinders for the recovery of
refrigerant).
Cylinders shall be complete with pressure relief valve and associated shut-
off valves in good working order.
Empty recovery cylinders are evacuated and, if possible, cooled before
recovery occurs.
The recovery equipment shall be in good working order with a set of
–
–
–
–
Labelling
Recovery
7

CAUTION
instructions concerning the equipment that is at hand and shall be suitable for
the recovery of flammable refrigerants.
In addition, a set of calibrated weighing scales shall be available and in good
working order.
Hoses shall be complete with leak-free disconnect couplings and in good
condition.
Before using the recovery machine, check that it is in satisfactory working
order, has been properly maintained and that any associated electrical
components are sealed to prevent ignition in the event of a refrigerant release.
Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the
correct recovery cylinder, and the relevant Waste Transfer Note arranged.
Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have
been evacuated to an acceptable level to make certain that flammable
refrigerant does not remain within the lubricant.
The evacuation process shall be carried out prior to returning the compressor
to the suppliers.
Only electric heating to the compressor body shall be employed to accelerate
this process.
When oil is drained from a system, it shall be carried out safely.
8

■ Plug into a grounded 3 prong outlet. Do not remove ground prong.
■ Never attempt to operate this appliance if it is damaged, malfunctioning, partially
disassembled, or has missing or broken parts, including a damaged cord or plug.
■ Do not use an electrical adapter or multiple-outlet adaptors with this dehumidifier.
■ Do not use an extension cord.
■ Unplug dehumidifier before servicing.
■ Do not drink water collected in the water bucket.
■ The appliance is not intended for use by young children or impaired people without
supervision, young children should be supervised to ensure that they do not play with
the appliance.
■ When installing or moving the appliance, be careful not to pinch, crush, or damage
the power cord.
■ Keep packing materials out of the reach of children. Packaging material can be
dangerous for children. There is a risk of suffocation.
■ Do not use the appliance in standing water or allow the product to be directly splashed by water
during use.
■ Store and install the appliance where it will not be exposed to temperatures below
freezing or exposed to outdoor weather conditions.
■ Call an authorized service technician to repair or immediately replace all power cords
that have become damaged. Do not use a cord that shows cracks or abrasion damage
along its length or at either end.
INSTALLATION
To reduce the risk of explosion, fire, death, electric shock, scalding, or injury to
persons when using this appliance, follow basic precautions, including the following:
9

■
■
Do not use the product if the outlet is damaged or loose.
In the event of a gas leak propane gas LP gas, etc.) do not operate this or any other
appliance Open a window or door to ventilate the area immediately.
Do not disassemble, repair or modify the product.
Do not store or use flammable gases or materials near the dehumidifier.
( ,
.
■
■
■ Read all instructions before using the appliance and save these instructions.
■ Do not tamper with controls.
■ Push the power plug all the way into the wall outlet so that it is not loose.
■ Do not grasp the power cord or touch the appliance controls with wet hands.
■ Do not modify or extend the power cord.
■ If the product makes a strange noise or emits a smell or smoke, pull the power plug out and
contact Hisense customer service.
■ Avoid placing the dehumidifier or other heavy objects on top of the power cord.
■ Do not use water to clean the dehumidifier.
■ Keep the air inlet and outlet free from obstructions.
■ Do not cover the power cord with a rug or carpeting. Placing heavy objects on top of the cord
could damage it.
■ Keep the product away from fire and high heat.
■ Do not use the product in places where it could be splashed by water.
■ Do not insert fingers, sticks etc. into the air inlet or outlet. The fan is running at high speeds
and could cause personal injuries.
■ Do not repair or replace any part of the appliance. All repairs and servicing must be performed
by qualified service personnel unless specifically recommended in this owner's manual. Use
only authorized factory parts.
■ Connect to a properly rated, protected, and sized power circuit to avoid electrical overload.
OPERATION
10

■ Do not use the product for preserving animals/plants, precision instruments, art works etc.
■ Do not place any objects on top of the dehumidifier.
■ Turn off the dehumidifier and empty the water bucket before moving the dehumidifier.
■ Pull out the power plug if you will not be using the product for an extended period.
■ Do not use the product in a very small space such as a closet.
Poor ventilation could result in overheating.
■ Do not use wax, thinner or a strong detergent when cleaning. Wipe the product using a soft
cloth.
■ Do not use the product in direct sunlight or rain.
■ Do not touch the product with wet hands.
■ Position the product on a firm, stable surface.
■ Remove cable ties and extend power cord before use.
■ Do not spray foreign substances or water on the product.
■ Dispose of this appliance in accordance with Federal and Local regulations.
■ Refrigerants must be evacuated before disposal.
■ Please recycle or dispose of the packaging material of the product in an environment-friendly
manner.
■ To avoid damage to the compressor, never store or ship the appliance upside down or sideways.
OPERATION
■ Use this appliance only for its intended purpose.
This product is not designed for preserving precision instruments, tableware or art works.
■ Never unplug the appliance by pulling on the power cord. Always grip the plug firmly and pull
straight out from the outlet.
■ Do not use the product in places where chemicals are used.
Chemicals and solvents dissolved in the air could cause product deformation and leaking,
■ Turn off the dehumidifier and pull out the power plug before cleaning.
Wait for the fan to stop moving.
■ Do not operate the dehumidifier without a filter.
Using the product without a filter could result in a reduced product lifespan, electric shock
or injury.
INSTALLATION
To reduce the risk of injury to persons, malfunction, or damage to the product
or property when using this appliance, follow basic safety precautions, including the following:
11

■ Do not locate outdoors. This dehumidifier is intended for indoor,
residential use only. This dehumidifier is not recommended for
commercial use.
■ Allow at least 12" to 18" (30.5 cm to 45.7 cm) of space on the rear
and sides of the dehumidifier for models with back louver and
above the dehumidifier for models with top louvers.
■ You will need a surface strong enough to support the
dehumidifier when its bucket is full of water.
■ You will need a surface level enough to keep the water from
spilling when the bucket is full of water.
■ Do not block the louvers of the unit .
■ Never operate this dehumidifier in an area that is likely to
accumulate standing water. If this condition develops, for your
safety disconnect the power supply before stepping into the
water.
To reduce the risk of injury to persons, malfunction, or damage to the product or
property when using this appliance, follow basic safety precautions, including the following:
12
Power Supply Requirements
Recommended Grounding Method
Your model may differ from the one shown.
NOTE:
A. 12" to 18" (30.5cm to 45.7cm)
■ 220-240V ~ / 50Hz
■ 15A time-delay fuse or circuit breaker
Specific electrical requirements are listed in the chart below.
Follow the requirements for the type of plug on the power
supply cord.
This dehumidifier must be grounded. This
dehumidifier is equipped with a power supply
cord with a three-prong grounding plug. The
cord must be plugged into a mating, grounded
three-prong outlet, grounded in accordance
with all local codes and ordinances. If a mating
outlet is not available, it is the customer's
responsibility to have a properly grounded
three-prong outlet installed by a qualified
electrician.
It is the customer's responsibility:
■ To contact a qualified electrical installer.
■ To assure that the electrical installation is
adequate and conforms to the Nation
Electrical Code, ANSI/NFPA 70-last edition,
and all local codes and ordinances.
A
A

NOTE:
NOTE:
■ Before turning on the dehumidifier, be sure that
the bucket is empty and fits all the way into the
dehumidifier.
■ Each time you unplug the dehumidifier or power
is interrupted, the controls will return to the
previous settings when power is restored.
■ Humidity displayed is between 30% Relative
Humidity and 90% Relative Humidity.
■ Humidity can be set between 30% Relative
Humidity and 80% Relative Humidity.
■ It's important to set the desired humidity level
to an achievable setting. To ensure energy-
efficient operation, only use the dehumidifier in
a closed space, with no open windows or other
sources of moist air (to avoid continuous running).
■ Operating temperature is between 5ºC to 32ºC.
Operating humidity is between 30% RH to 80% RH.
At temperatures of 5ºC or less, water freezes
inside the product. At temperatures over 32ºC,
the internal temperature of the product trips a
protective device which deactivates the product
to avoid product damage.
■ The compressor has a 3-minute delay
before restarting. If the product is stopped
and immediately restarted, to protect the
compressor there is a 3-minute delay until
the compressor restarts.
The dehumidifier should be
upright for at least 2 hours before use.
Do not pull out the water
bucket during normal use, otherwise there may
be electric shock risk. If you want to move the
dehumidifier, be sure that pull out the power plug
at first.
When the dehumidifier is operating the
indoor temperature will rise
The dehumidifier does not have a cooling
heating function
Heat is generated during operation so the
room temperature may be increased by
about 5ºC depending on the usage
conditions indoor temperature size of the
room
■
,
.
/ .
,
( ,
).
13
NOTE:
In the case of a power outage or interruption, the
dehumidifier will automatically restart, in the
settings last used, after the power is restored.
The control panel of your model may differ from the one shown above.
1. Plug into a grounded three-prong outlet.
2. Press POWER to turn on the dehumidifier.
3. Press the plus or minus button to set the
level of humidity.
4. Press POWER to turn off the dehumidifier.
Control Panel

1. Single Fan speed .
Press POWER to turn on or turn off the dehumidifier.
1. Humidity can be adjusted manually .
The display shows relative humidity.
1. When the dehumidifier is running, the display
shows the relative humidity of the room.
2. “CO” will be displayed when the dehumidifier
is operating in continuous mode.
3. In continuous mode, room humidity will
be displayed.
NOT
NOTE:
The humidity displayed is only for reference.
For accurate humidity, please check a hygrometer.
NOTE:
The de-icing function will turn off the compressor
if a low temperature condition occurs. When the
de-icer senses the correct operating temperature,
the compressor will cycle back on. Some freezing
is normal when dehumidifiers are used at low
temperatures.
When this light is on, the compressor and the fan
stop running, it indicates that you need to check:
NOTE:
Once the relative humidity of the room hit the
desired setting, the compressor will stop and the
fan will keep running.
14
Empty Bucket Light
■ If the bucket is full, empty and re-install
bucket.
■ If the bucket is not in position, remove the
bucket and re-install it. Make sure the
bucket fits all the way into the dehumidifier
and the bucket light is off, or the dehumidifier
will not run.
■ If the humidity level of the room is higher
than the desired humidity setting, the
compressor will turn on. If the humidity level
of the room is lower than the desired humidity
setting, the compressor will turn off and the fan
will keep running.
1. Press the Plus or Minus button to set the
desired humidity level. Desired humidity in
the digital display will flash for 5 seconds
after operation.
3. To set the dehumidifier for continuous
operation, press the Minus button until “CO”
flash for 5 seconds and then display. In
continuous mode, room humidity will
be displayed .
NOT
NOTE:
If continuous mode is selected, the
dehumidifier will operate continuously at its
maximum dehumidification settings if
attached to a hose to drain or until the bucket
is full.
4. When the dehumidifier is operating in
continuous mode, press the Plus button and
then unit will stop the continuous running
and goes back to manual mode.
2. Actual room humidity will be displayed after
5 seconds of flashing the desired humidity.
Humidity Level
Fan Speed
Desired Humidity-Mode
Power
Digital Display
1.
When the Clean Filter indicator light is on,
remove, clean and replace the air filter. See
“Cleaning the Air Filter”.
2. Press the POWER button for 5 seconds after
cleaning and replacing the air filter to reset
the filter monitor.
NOTE:
When the light is on, it will remain on for 180 hours
or until you press POWER button for 5 seconds.
Clean Filter

15
2. Lift the bucket up by the handle.
3. Pour water into a sink or tub.
If a floor drain is not available, or you do not plan
to run your dehumidifier continuously, you may
want to simply empty the bucket.
1. Grasp the bucket sides to slide out bucket.
4. Fold down the handle and reinstall the bucket.
IMPORTANT:
If the Empty Bucket light comes on, the
dehumidifier will not operate. The bucket may
need to be emptied or re-installed.
NOTE:
■ If the water bucket is removed immediately
after turning off the dehumidifier, the water
remaining in the heat exchanger may drip
inside the water bucket storage area.
Remove the water with a soft cloth.
■ While cleaning, do not touch the water level
float.
■ Clean the water bucket once a week during
use.
■ If the ambient temperature is low, there is
less moisture in the air for the product to
remove.
■ Unplug the product before removing the water
bucket. If the bucket is removed while the
product is operating, the compressor will stop.
If you plan to run your dehumidifier continuously,
you can choose direct draining by attaching a
garden hose to the unit.
1. Turn off the dehumidifier and unplug the power
supply cord.
2. Uncover the connector cover on the side of
the unit.
Option 1 Bucket Draining
Option 2 Gravity Draining

Take care not to injure hands
while connecting the hose.
NOTE:
■
■
To use the bucket without the garden
hose, simply remove the garden hose,
then reinstall bucket.
The bucket must be installed and
properly aligned for the dehumidifier to
operate with or without a garden hose
connected.
NOTE:
■
■
The garden hose sold separately.
The connection is designed for North
American garden hoses only.
16
3. Remove bucket.
4. Attach a garden hose to the drain hose
connector on the inside of the dehumidifier.
Securely attach the hose to be sure there is
no water leak.
5. Place the other end of garden hose into a
floor drain. Check to see that the hose lies
flat and is in the drain. Make sure the
draining end of the hose is on a lower level
than the hose connection to the
dehumidifier. The hose should not be
kinked or pinched.
6. Reinstall bucket.
A. Garden hose
B. Drain hose connector
IMPORTANT:
In North America the garden hose connectors are
3/4” diameter straight (non-tapered) thread with a
pitch of 11.5 threads per inch(male part has an
outer diameter of 1 1/16 inches (26.99mm).
When your dehumidifier is operating normally, you may hear sounds such as:
■ Compressor sounds, which may be loud.
■ Air movement from the fan.
■ Clicking sounds when the dehumidifier or compressor turns on and off, and when the Automatic
shut-off Switch is working.

17
Water level float
NOTE:
Do not wash air filter in the dishwasher or use
any chemical cleaner. Air dry filter completely
before reinstalling to ensure maximum operating
efficiency.
The dehumidifier's water bucket has a water level
float. Do not damage or remove the bucket’s water
level float. If the float is not properly in place, the
Empty Bucket light will turn on, preventing
operation, and could result in leaking.
Every few weeks, rinse the inside of the water
bucket with a mild detergent to avoid growth of
mold, mildew and bacteria.
Your new dehumidifier is designed to give you many years of dependable service. This section explains
how to clean and care for your dehumidifier.
To avoid damage to the compressor, never store or ship the appliance upside down or sideways.
The air filter is removable for easy cleaning. A
clean filter helps remove dust, lint, and other
particles from the air and is important for best
operating efficiency. Check the filter every two
weeks to see whether it needs cleaning.
1. Turn off the dehumidifier.
2. Pull out the air filter.
3. Use a vacuum cleaner to clean the air filter if
the air filter is dirty, wash it in warm water with
a mild detergent.
4. Insert the air filter into the dehumidifier.
5. Turn on the dehumidifier.
1. Turn off the dehumidifier and unplug the power
supply cord.
2. Dust the surface of the unit with a soft cloth or
the dusting attachment of your vaccum cleaner.
A. Water level float
B. Bucket
Cleaning the Dehumidifier
Cleaning the Air Filter
NOTE:
Be sure the float is snapped correctly in place.
Exterior
Water Bucket
A
B
Table of contents
Languages:
Other Hisense Dehumidifier manuals

Hisense
Hisense DH-35K1SJE5 User manual

Hisense
Hisense DH5019K1G User manual

Hisense
Hisense DH7019KP1WG User manual

Hisense
Hisense DH-70K1SJE User manual

Hisense
Hisense DH5020K1G User manual

Hisense
Hisense DH5021KP1W User manual

Hisense
Hisense DH-50K1SJE5 User manual

Hisense
Hisense DH35K1SCLE User manual

Hisense
Hisense DH-70KP1SDLE User manual

Hisense
Hisense DH3020K1W User manual