manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Hitachi
  6. •
  7. Air Conditioner
  8. •
  9. Hitachi RAS-25YHA4 User manual

Hitachi RAS-25YHA4 User manual

FOR SERVICE PERSONNEL ONLY
SAFETY PRECAUTION
sRead the safety precautions carefully before operating the unit.
sThe contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING .......... Incorrect methods of installation may cause death or serious injury.
CAUTION .......... Improper installation may result in serious consequence.
Make sure to connect earth line.
This sign in the figures indicates prohibition.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of
the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual.
WARNING
sPlease request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the
installation work yourself.
sPlease observe the installation stated in the installation manual during the process of installation. Improper installation may cause
water leakage, electric shock and fire.
sMake sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may
collapse and impose danger.
sObserve the rules and regulations of the electrical installation and the methods described in the installation manual when dealing
with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and
fire may occur due to the use of low quality wire or improper work.
sBe sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the
conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the
terminal base. Improper insertion and loose contact may cause over-heating and fire.
sPlease use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or
stronger vibration may occur.
sBe sure to use the specified piping set for R410A. Otherwise, this may result in broken copper pipes or faults.
sWhen installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R410A)
does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally
which could result in a rupture and injury.
sBe sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may
occur.
sAfter completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the
room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
sUnauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner
technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
sBe sure to connect the earth line from the power supply wire to the outdoor unit and between
the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the
telephone unit. Improper earthing may cause electric shocks.
sWhen finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe.
If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a
pressure in the freezing cycle system will build up steeply, causing an explosion or injury.
sWhen installing the unit, be sure to install the refrigerant pipe before starting the compressor.
If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the
pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
CAUTION
sA circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the
outdoor unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed.
Without a circuit breaker, the danger of electric shock exists.
sDo not install the unit near a location where there is flammable gas. The outdoor unit may catch fire
if flammable gas leaks around it.
sPlease ensure smooth flow of water when installing the drain hose. Improper installing may wet your funiture.
sAn IEC approved power cord should be used. Power cord type: NYM.
TINUROODNI
WARNING
THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation.)
sThe unit should be mounted at stable, non-vibratory location
which can provide full support to the unit.
CAUTION
sNo nearby heat source and no obstruction near the air
outlet is allowed.
sThe clearance distances from top, right and left are
specified in figure below.
sThe location must be convenient for water drainage and
pipe connection with the Outdoor unit.
sTo avoid interference from noise, please place the unit and
its remote controller at least 1m from the radio and
television.
sTo avoid any error in signal transmission from the remote
controller, please put the controller far away from high-
frequency machines and high-power wireless systems.
TINUROODTUO
WARNING
sThe Outdoor unit must be mounted at a location which can
support heavy weight. Otherwise, noise and vibration will
increase.
CAUTION
sDo not expose the unit under direct sunshine or rain.
Besides, ventilation must be good and clear of obstruction.
sThe air blown out of the unit should not point directly to
animals or plants.
sThe clearances of the unit from top, left, right and front are
specified in figure below. At least three of the above sides
must be open air.
sThe installation height should be at least 2,300 mm or more
from the floor.
sBe sure that the hot air blown out of the unit and noise do
not disturb the neighbourhood.
sDo not install at a location where there is flammable gas,
steam, oil and smoke.
sThe location must be convenient for water drainage.
sPlace the Outdoor unit and its connecting cord at least 1 m
away from the antenna or signal line of television, radio or
telephone. This is to avoid noise interference.
Names of Indoor Components
Direction of Piping
Backward piping
from left
Connection
There are 6 directions allowed,
namely, backward piping,
backward piping from left,
horizontally piping from right,
horizontally piping from left,
vertically down from right, vertically
down from left.
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the insulator is
insufficient, please use commercial
products.)
sThe refrigerating machine oil is
easily affected by moisture. Use
caution to prevent water from
entering the cycle.
sThe difference in height between
the indoor and outdoor unit
should be kept below 10m.
sThe connecting pipe, no matter
big or small, should all be
insulated with insulation pipe and
then wrapped with vinyl tape.
(The insulator will deteriorate if
it is not wrapped with tape).
The connection of insulated drain
hose.
Inner diameter 16mm
Please use insulated drain hose for
the indoor piping (commercial
product)
TINUROODNI
1 Installation of Hanger, Wall Penetration and Installation of Protection Pipe
CAUTION
sThe draining of the water container inside the Indoor unit can be done from the left.
Therefore the hanger must be fixed horizontally or slightly tilted towards the side of
drain hose. Otherwise, condensed water may overflow the water container.
sDrill a ø65mm hole on wall which is
slightly tilted towards the outdoor side.
Drill the wall at a small angle.
sCut the protection pipe according to the
wall thickness.
sEmpty gap in the sleeve of protection
pipe should be completely sealed with
putty to avoid dripping of rain water into
the room.
sPlease ensure smooth flow of water
when installing the drain hose. Improper
installing may wet your funiture.
sAn IEC approved power cord should be
used. Power cord type: NYM.
WARNING
Be sure that the wire is not
in contact with any metal in
the wall. Please use the
protection pipe as wire
passing through the hollow
part of the wall so as to
prevent the possibility of
damaged by mouse.
Unless it seals completely,
any air with high humidity
flows from outdoor and any
dew may drop.
Seal with
putty
Protection
pipe Sleeve of
protection
pipe
Seal with
putty
Outdoor
Indoor
2-5mm
2 Installation Of The Indoor Unit
WALL

PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
sConnect connecting cord.
sPull out the pipe, connecting cord and drain hose.
Installation
sInsert the pipe through the wall hole.
The upper part of the Indoor unit is hanged on the
hanger.
The projection at the lower part of the Indoor unit is
hooked onto the hanger.
Connecting cords, pipe and
drain hose must be laid
together with Vinyl tape.

PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
Changed of Drain Hose and Installation Procedures.
s
Exchange the location of drain hose and drain cap while installing the pipe from the left side as
shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.
sPlease use pliers to pull out the drain cap.
(This is an easier way to remove the drain
cap).
CAUTION
Insufficient insert may
result in water leakage.
Drain Hose
Drain cap
s
Remove low cover
s
Insert drain cap up to the
location securely till the
cap stops.
Cutting Low Cover bush
sWhile installing the pipe from the right, left or
bottom side, use a knife to cut openings as
shown in figure. Then smoothen the edges of
openings with a file.
Openings
s
Push the pipe deeply until the insulating
section of the drain hose end gets over the
rib at the indoor unit side.
Openings
CAUTION
sThe rubber strap used for fixing the insulator
should not be tied with great force. Otherwise,
this will damage heat insulation and causes
water condensation.
sPlease pull the lower part of the Indoor unit
outwards to check if the unit is hooked onto
the hanger. Improper installation may cause
vibration and noise.
sTransform the piping while holding down the
lower portion of pipe-support by hand.
Pipe Rubber strap tied
with great force
INSTALLATION AFTER CONNECTION OF REFRIGERATING PIPES
sThe refrigerating pipe should be adjusted to fit into
the hole on the wall and then ready for further
connection.
sThe terminals of 2 connected pipes must be covered
with insulator used for terminal connection. Then the
pipes are wrapped with insulation pipe.
sConnect the connecting cord after removing low
cover.
(Refer to "CONNECTION OF POWER CORD")
sAfter adjustment, fit the connecting cord and pipes
into the space available under the unit. Use holder to
hold them tight.
sHolder can be attached at the either of 2 places.
Please select the easier position.
THE CONNECTION OF REFRIGERATING PIPE DURING
THE INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
sThe refrigerating pipes and connecting cord
transform and are attached.
Please bend at a small
radius to form an arc
Installation
Hang the indoor unit onto the hanger. Use the temporary stand
at the back of the Indoor unit to push its lower part 15cm
forwards.
sPlace the drain hose through the hole on the wall.
sWrap the refrigerating pipes with insulation pipe after
connecting refrigerating pipe.
sConnect the connecting cord after removing low cover.
(Refer to "Connection of Power Cord")
sAfter adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit.
sThe projection of Indoor unit must hook to the hanger.
Pull this to the front during the
connection of refrigerating
pipe to ease task.
Heat
insulation pipe
Refrigerating
pipe
Connecting
cord
Wall hole
Pipe
Drain hose
Cable
4 Installation of Drain Hose
CAUTION
Be sure that the drain hose is
not loosely connected bend or
proper condition like left figure.
CAUTION
You are free to choose the side (left or right) for the installation of drain
hose. Please ensure the smooth flow of condensed water of the Indoor
unit during installation. (Careless may result in water leakage.)
sThe connected terminals should be completed sealed
with heat insulator and then tied up with rubber strap.
sDo not tie the terminals with the tape too tight.
If any clearance or over-tightening may cause
condensation.
sPlease tie the pipe and power line together with vinyl
tape as shown in the figure showing the installation of
Indoor and Outdoor units.
sTo enhance the heat insulation and to prevent water
condensation, please cover the outdoor part of the
drain hose and pipe with insulation pipe.
sCompletely seal any gap with putty.
Insulation material for pipe
connection
Sleeve of
protection pipe
Putty
Putty
Wall hole
Drain layout of backward piping from left
The component of
the package of the outdoor unit.
The end of the refrigerating pipes are at
locations marked with “ ” symbol.
3 Heat Insulation and Finish of the Piping
Drain cap
Pipe
support Transform after
bending downward.
is included
in
Holder
Pipe Connecting
cord
Drain hose
Insulation pipe (must be wrapped with
vinyl tape at every 120 mm)
5mm
Protection
pipe
Connecting cord Connected
section
Drain hose
below
Indoor Unit / Outdoor Unit
67
Lift the body
of the unit
upwards and
then force it
downwards.
Hanger
Refrigerating
Pipe
Protection
Pipe Drain Hose Connecting Cord
Projection
Pipe
Drain hose
Cable
Drain layout of
backward piping
Hanger
pond
Bending upwards Condensed water
Ditch
about 15cm
Hook
Projection
No. Item Qty
Hanger
Screw for Hanger
AAA size Battery
Remote Controller
Insulation sheet
Drain Pipe











Bush
2
2
2
C-case
Air Cleaning
Mesh
Wasabi-Nano Titanium
Screw for Remote
Controller Holder
Remote Controller Holder
Direct Mounting On The Wall
Wall Penetration and Installation of Protection Pipe
sPlease use hidden beams in the wall to hold the hanger.
Procedures of Installation and Precautions
sProcedures to fix the hanger.
1.Drill holes on wall.
(As shown below)
2.Push plug into the holes.
(As shown below)
3.Fix the hanger on wall with
4.1 x 32 screw.
(As shown in figure below)
sProcedures to fix the holder of remote control.
1.Drill holes on wall.
(As shown below)
2.Push plug into the holes.
(As shown below)
Remote
Control
Holder
32mm
Wall
ømm8.4
Hanger
Screw
Wall
Plug (Procure locally)
Screw
20mm
ømm4.
4
Wall
Plug
(Procure
locally)
Screw the hanger at the
positions possibly near the
upper and lower hooks where
the indoor unit is hung. Use 4 or
more screws to fix the hanger.
Wall hole
Weight
Line
Hanger
Level
Drain Hose
Screw for Hanger
Visible outline of the
outdoor unit
Ceiling



pond
Condensed water
1
RAK-18_25_35PPA/RAC-18_25_35WPA_IM_English
Plug (Procure locally)




(3.1 x 16)
RAS-25YHA4 / RAC-25YHA4
RAS-35YHA5 / RAC-35YHA5
(unit : mm)
Dimension of Mounting
Stand of the Outdoor unit
Mounting
Stand
330
310 (10)10
500 35
50
12
125
Figure showing the Installation
of Indoor and Outdoor Unit.
12
above
50mm
above 50mm
above 50mm
about 300mm
about 0.45m
must not bend
Used in
horizontal piping
above 100mm
above 300mm
above 50mm
give clearance
as wide as
possible
above
200mm
Be sure to
completely
seal any gap
with putty.
Maximum pipe length 20m
above 50 mm when
installed on the
ceiling of balcony
above 200mm
2,300 mm or more
(4.1 x 32) 6
When the power is
supplied from the
indoor unit, pull the
power cable from the
cable drawer at the
right or left side of
the indoor unit.
Cable drawer (right side)
Holder

Minimum pipe length 4m
RAS-35YHA1/RAC-35YHA1_EN.p65
Please mount the Outdoor unit of stable ground to prevent vibration and increase
of noise level.
Decide the location for piping after sorting out the different types of pipe available.
When removing side cover, please pull the handle after undoing the hook by pulling
it downward. Reinstall the side cover in the reverse order of the removal.
CONDENSED WATER DISPOSAL OF OUTDOOR UNIT
There is holes on the base of Outdoor unit for condensed water to exhaust.
In order to flow condensed water to the drain, the unit is installed on a stand or a
block so that the unit is 100mm above the ground as shown figure. Join the drain
pipe to one hole.
Cover the drain hole with a bush. To install the bush, put it on the drain hole as
shown in the figure and press the both sides of the bush to fit into the hole.
After installation, check whether the drain pipe and bush cling to the base firmly.
Install the outdoor unit horizontally and make sure that condensate drains away.
In case of using in chilly area
Especially, in case that there are many snows by very cold in chilly area, condensed
water freezes on the base and may result not to drain. In this case, please remove
the bush and the drain pipe at the bottom of unit. (Left and center near discharge
portion of air, each 1 place). It becomes smooth drain.
Ensure that the distance from the drain hole to the ground is 250 mm or more.
OUTDOOR UNIT
CAUTION
Do not touch the suction
port, bottom surface, or
aluminum fin of the outdoor
unit.
Failure to do so may cause
an injury.
INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL
3 Remove of Air From The Pipe And Gas Leakage Inspection
AIR REMOVAL
Procedures of using Vacuum Pump for Air Removal
As shown in right figure, remove the cap
of valve core. Then, connect the charge
hose. Remove the cap of valve head.
Connect the vacuum pump adapter to the
vacuum pump and connect the charge
hose to the adapter.
1
Fully tighter the "Hi" shuttle of the manifold
valve and completely unscrew the "Lo"
shuttle. Run the vacuum pump for about
10-15 minutes, then completely tighten the
"Lo" shuttle and switch off the vacuum
pump.
Loosen the spindle of the service valve
with small diameter by 1/4 turn and
tighten the spindle immediately after 5
to 6 seconds.
Remove the charging hose from the
service valve.
2
Completely unscrew the spindle of the
service valve (at 2 places) in anticlockwise
direction to allow the flow of refrigerant
(using Hexagonal Wrench key).
3
Tighten the cap of valve head. Check the
cap's periphery if there is any gas leakage.
The task is then completed.
4
Gas leakage inspection
Please use gas leakage detector to check if leakage
occurs at connection of Flare nut as shown on the
right.
If gas leakage occurs, further tighten the connection
to stop leakage.
CONNECTION OF POWER CORD
WARNING
If you cannot attach the side plate due to the connection cord, please
press the connecting cord in the direction to the front panel to fix it.
Be sure that the hooks of the side cover fixed in certainly. Otherwise water
leakage may occur and this causes short circuit or faults.
The connecting cord should not touch to service valve and pipes. (it
becomes high temperature in heating operation.)
Wiring of the Outdoor Unit
Please remove the side cover for wire connection.
Checking for the electric source and the voltage range
Before installation, the power source must be checked and necessary wiring work must
be completed. To make the wiring capacity proper, use the wire gauge list below for the
wiring from house distribution fuse box to the outdoor unit in consideration of the blocked
rotor current.
IMPORTANT
Wire length Wire gauge
up to 6m 1.6mm2
up to 15m 2.5mm2
up to 20m 4.0mm2
Investigate the power supply capacity and other
electrical conditions at the installing location.
Depending on the model of room air conditioner to be
installed, request the customer to make arrangements
for the necessary electrical work etc.
The electrical work includes the wiring work up the
outdoor unit. In localities where electrical conditions
are poor, use of a voltage regulation is recommended.
Install outdoor for the room air conditioner within the
reaching range of the line cord.
IMPORTANT
Fuse Capacity
16A time delay fuse
Pull at the 1 and 2 in the directions as shown by arrows to remove
the cover.
Method to remove the low cover
Wiring of The Indoor Unit
For wire connection of the Indoor unit, you need to remove the front cover
under the body of the unit and terminal cover.
, the low cover
WARNING
The naked part of the wire core should be 10mm fix it to the terminal tightly. Then
try to pull the individual wire to check if the contact is tight. Improper insertion may
burn the terminal.
Be sure to use only wire specified for the use of air-conditioner.
Please refer to the manual for wire connection and the wiring technique should
meet the standard of the electrical installation.
There is an AC voltage drop between the LN terminal if the power is on. Therefore,
be sure to remove the plug from its socket.
WARNING
Leave some space in the connecting cord for maintenance
purpose and be sure to secure it with the cord band.
Secure the connecting cord along the coated part of the wire
using the cord band. Do not exert pressure on the wire as this
may cause overheating or fire.
When power supplies to Indoor Unit
WARNING
THIS APPLIANCE MUST BE
EARTHED.
Procedures of Wiring
Detail of cutting the connecting cord
FINAL STAGE OF INSTALLATION
1 Power Source And Operation Test
Power Source
WARNING
Never remodel the power plug nor extend the long-distance
cord.
Keep additional length for the power cord and do not render
the plug under external force as this may cause poor contact.
Do not fix the power cord with U-shape nail.
The power cable easily generates heat. Do not bring the
cable together with a wire or vinyl tie.
Operation test
Please ensure that the air conditioner is in normal operating
condition during the operation test.
Explain to your customer the proper operation procedures as
described in the user' s manual.
If the indoor unit won't operate, check the cable for correct
connection.
Turn on the lamp in the room where the indoor unit is installed
and check the remote controller for normal operation.
2 Installation of Remote Controller
The remote controller can be placed in its holder which is fixed
on wall or beam.
To operate the remote controller at its holder, please ensure that
the unit can receive signal transmitted from the controller at the
place where the holder is to be fixed. The unit will beep when
signal is received from the remote controller. The signal
transmission is weaken by the fluorescent light. Therefore, during
the installation of the remote control holder, please switch on
the light, even during day time, to determine the mounting location
of the holder.
The controller must be hooked onto the hook at the lower part
of the holder. Push in the remote controller in the direction as
shown in figure below.
Force-cooling operation
When the service switch
of the outdoor unit is
pressed for 1 or more
seconds, the force-
cooling operation starts.
Use this mode when
performing the failure
diagnosis or collecting
refrigerant into the
outdoor unit.
CAUTION
Do not operate the unit for more than 5 minutes
while the spindle of the service valve is closed.
After completing the service switch
operation, be sure to keep the
switch pressed for one or more
seconds and stop the force-cooling
operation.
2
30mm
10mm
10mm
70mm
Indoor Unit
Pull downward
Please face this side (suction side)
of the unit to the wall. Please remove side cover
when connecting the piping
and connecting cord.
9 DRAIN PIPE
8 BUSH DRAIN HOLE
above
100mm
Push Push
BASE
DRAIN HOLE
8 BUSH
Outer diameter: 16 mm or more
When the meter reaches -101KPa
(-76cmHg) during pumping fully
tighten the shuttle.
Meter showing
pressure Closed
R410A
Manifold
valve
Vacuum
pump
Valve
Charge
hose
Vacuum
pump
adapter
When pumping starts, slightly
loosen the flare nut to check of
air sucked in. Then tighten the
flare nut.
The body of service
valve
Cap of
valve core
Hexagonal
wrench Key
Cap of valve
head
Cap of valve
head
Valve
10mm
50mm
10mm
50mm
Green + Yellow
Green + Yellow
Green + Yellow
Strip wires
Outdoor Unit
Remote controller
Screw (2 pieces)
Holder for Remote
Controller
Service switch (If the switch is
pressed for one or more seconds, the
force-cooling operation starts. If the
switch is pressed for additional one or
more seconds, the operation stops.)
Screw
Cover
DCNLDC
Indoor Unit Outdoor Unit
Connecting Cord Connecting Cord
AC 240V
1.6 or
2.0
2.0
Connect the
earth cord
D
C
After remove the screw
and cover, and put the
connecting cords and fix
the cover with screw. cover
Earth terminal
CAUTION
sRemove burr and jagged edge will cause leakage.
sPoint the side to be trimmed downwards during trimming to prevent copper
chips from entering the pipe.
Copper pipe
Trimming tool
sBefore flaring, please put on the flare nut.
A
Die
Die
Copper pipe
sPlease use
exclusive tool for
refrigerant R410.
Outer A (mm) Rigid Flaring Tool
Diameter (Ø) For R410A tool For R22 tool
6.35 (1/4") 0 - 0.5 1.0
9.52 (3/8") 0 - 0.5 1.0
2 Pipe Connection
CAUTION
sIn case of removing flare nut of a indoor unit, first remove
a nut of small diameter side, or a seal cap of big diameter
side will fly out. Free from water into the piping when
working.
sBe sure to tighten the flare nut to the specified torque with
a torque wrench.
If the flare nut is overtightened, the nut may be split after a
long period has passed, and may cause a refrigerant leak.
sPlease be careful when bending the copper pipe.
sScrew in manually while adjusting the center. After that, use a torque wrench to
tighten the connection.
Torque
wrench
Flare nut
Wrench
Small diameter side 6.35 (1/4") 13.7 – 18.6 (140 – 190)
Large diameter side 9.52 (3/8") 34.3 – 44.1 (350 – 450)
Small diameter side
6.35 (1/4") 19.6 – 24.5 (200 – 250)
Large diameter side
9.52 (3/8") 19.6 – 24.5 (200 – 250)
Valve core cap 12.3– 15.7 (125 – 160)
Torque N·m
(kgf·cm)
Valve
head cap
1 Preparation of Pipe
sUse a pipe cutter to cut the copper pipe and remove burr.
Outer diameter
of pipe (ø)
How to remove the front cover How to Attach the Front Cover
Check that the drain pan is securely attached.
After installing the front cover onto the unit, hook three claws
at upper side of the cover securely. Then, push the center of
the front cover to lock the claws.
Tighten the two screws.
Install the filter.
Slide the shafts of the right and left arms on the front panel
along the steps to insert the shafts into the holes till they stop.
After checking that the shafts are securely inserted, close the
panel.
Remove the front panel
sPlease remove and attach the front panel by both hands.
sAfter opening the front panel by both hands.
Undo the right arm while pushing it inside.
Slide the front panel to right as shown in figure.Then remove
while pulling it to front.
Remove the filters.
After removing two screws, pull the center of the front cover
towards you and release the claws.
Pull the side faces (lower sections) of the front cover towards
you as shown in the figure and remove the cover.
sPush up the [PUSH] sections at the bottom of the indoor unit and
pull the bottom plate towards you. Then the claws are released
from the stationary plate.
(The [PUSH] sections are indicated by 2 arrows in the right figure)
HOW TO REMOVE INDOOR UNIT
[PUSH] mark positions





EE0013406A 2014.07

This manual suits for next models

3

Other Hitachi Air Conditioner manuals

Hitachi RAS-X10CZ User manual

Hitachi

Hitachi RAS-X10CZ User manual

Hitachi RAS-X13CXT User manual

Hitachi

Hitachi RAS-X13CXT User manual

Hitachi YUTAKI S Series User manual

Hitachi

Hitachi YUTAKI S Series User manual

Hitachi RCI-1.0FSN1E User manual

Hitachi

Hitachi RCI-1.0FSN1E User manual

Hitachi RAS-14G4 User manual

Hitachi

Hitachi RAS-14G4 User manual

Hitachi RAK-35RPD User manual

Hitachi

Hitachi RAK-35RPD User manual

Hitachi RA-13KF Specification sheet

Hitachi

Hitachi RA-13KF Specification sheet

Hitachi RASC-4HNPE User manual

Hitachi

Hitachi RASC-4HNPE User manual

Hitachi RAS-S13CDT User manual

Hitachi

Hitachi RAS-S13CDT User manual

Hitachi RAS-25YHA3 User manual

Hitachi

Hitachi RAS-25YHA3 User manual

Hitachi airHome RAD-DJ50QHAE User manual

Hitachi

Hitachi airHome RAD-DJ50QHAE User manual

Hitachi RPK-1.0FSN1M User manual

Hitachi

Hitachi RPK-1.0FSN1M User manual

Hitachi RAC-X10HAK User manual

Hitachi

Hitachi RAC-X10HAK User manual

Hitachi RAC-25WXE User manual

Hitachi

Hitachi RAC-25WXE User manual

Hitachi RAC-35WEF User manual

Hitachi

Hitachi RAC-35WEF User manual

Hitachi RAC-25WPB User manual

Hitachi

Hitachi RAC-25WPB User manual

Hitachi UTOPIA RAS-3HVRC2 User manual

Hitachi

Hitachi UTOPIA RAS-3HVRC2 User manual

Hitachi RAW-XH07CA User manual

Hitachi

Hitachi RAW-XH07CA User manual

Hitachi RAS-DX10CWK User manual

Hitachi

Hitachi RAS-DX10CWK User manual

Hitachi RAC-25WXD User manual

Hitachi

Hitachi RAC-25WXD User manual

Hitachi airHome MultiPro RAM-G55N3HAE User manual

Hitachi

Hitachi airHome MultiPro RAM-G55N3HAE User manual

Hitachi RAM-36NP2A User manual

Hitachi

Hitachi RAM-36NP2A User manual

Hitachi RAM-68NP3B User manual

Hitachi

Hitachi RAM-68NP3B User manual

Hitachi P-GP160NAP User manual

Hitachi

Hitachi P-GP160NAP User manual

Popular Air Conditioner manuals by other brands

mundoclima CL23420 installation manual

mundoclima

mundoclima CL23420 installation manual

Haier HWF05XC3 user manual

Haier

Haier HWF05XC3 user manual

Sealey sac9000.V3 instruction manual

Sealey

Sealey sac9000.V3 instruction manual

Fujitsu AUT12 operating manual

Fujitsu

Fujitsu AUT12 operating manual

Airwell Dakota DCI Series Service manual

Airwell

Airwell Dakota DCI Series Service manual

Panasonic CU-2S18NBU-1 Service manual

Panasonic

Panasonic CU-2S18NBU-1 Service manual

Daikin FFQ25B9V1B Operation manual

Daikin

Daikin FFQ25B9V1B Operation manual

EMI WLCA operation instruction

EMI

EMI WLCA operation instruction

Haier AU362XHERA installation manual

Haier

Haier AU362XHERA installation manual

PR KLIMA GPC10AL operating instructions

PR KLIMA

PR KLIMA GPC10AL operating instructions

Daikin RZQSG-LV1 Technical data

Daikin

Daikin RZQSG-LV1 Technical data

Samsung AQV12J Series user manual

Samsung

Samsung AQV12J Series user manual

Carrier RAV180 installation instructions

Carrier

Carrier RAV180 installation instructions

Mitsubishi Electric MSZ-FA25VA Service manual

Mitsubishi Electric

Mitsubishi Electric MSZ-FA25VA Service manual

Samsung AS07P2GE/XCH Owner's instructions

Samsung

Samsung AS07P2GE/XCH Owner's instructions

DEVOLA DVCO60P user manual

DEVOLA

DEVOLA DVCO60P user manual

Toshiba TCB-SIR41U-E installation manual

Toshiba

Toshiba TCB-SIR41U-E installation manual

Pro-Elec PELL0060 manual

Pro-Elec

Pro-Elec PELL0060 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.