NO. 0585E
SPECIFICATIONS AND PARTS ARE SUBJECT TO CHANGE FOR IMPROVEMENT
ROOM AIR CONDITIONER
OUTDOOR UNIT
JANUARY 2015
Refrigeration & Air-Conditioning Division
SERVICE MANUAL
PM
RAM-68NP3B
REFER TO THE FOUNDATION MANUAL
TECHNICAL INFORMATION
FOR SERVICE PERSONNEL ONLY
CONTENTS
SPECIFICATIONS---------------------------------------------------------------------5
FEATURES---------------------------------------------------------------------------- 10
INSTALLATION----------------------------------------------------------------------- 14
CONSTRUCTION AND DIMENSIONAL DIAGRAM ----------------------- 18
MAIN PARTS COMPONENT ---------------------------------------------------- 19
WIRING DIAGRAM ----------------------------------------------------------------- 21
CIRCUIT DIAGRAM ---------------------------------------------------------------- 23
BLOCK DIAGRAM ------------------------------------------------------------------ 25
BASIC MODE ------------------------------------------------------------------------ 27
REFRIGERATING CYCLE DIAGRAM----------------------------------------- 47
DESCRIPTION OF MAIN CIRCUIT OPERATION------------------------- 48
TROUBLE SHOOTING ------------------------------------------------------------ 82
PARTS LIST AND DIAGRAM---------------------------------------------------- 90
After installation
850
800
298
55
(W)
(A)
COOLING CAPACITY
DC INVERTER TRIPLE SYSTEM MULTI
TYPE
MODEL
POWER SOURCE
TOTAL INPUT
TOTAL AMPERES
SPECIFICATIONS
OUTDOOR UNIT
RAM-68NP3B
HEATING CAPACITY
DIMENSIONS (mm)
NET WEIGHT
1ø, 220 - 240V, 50/60Hz
W
H
D
(kg)
(kW)
(B.T.U.)
REFER TO THE SPECIFICATIONS PAGE
RAM-68NP3B
– 1 –
SAFETY DURING REPAIR WORK
1. In order to disassemble and repair
the unit in question, be sure to
disconnect the power cord plug
from the power outlet before starting
the work.
2. If it is necessary to replace any parts, they should be replaced with respective genuine parts for the unit,
and the replacement must be effected in correct manner according to the instructions in the Service Manual
of the unit.
If the contacts of electrical
parts are defective, replace the
electrical parts without trying to
repair them.
3. After completion of repairs, the initial state
should be restored.
4. Lead wires should be connected and laid as
in the initial state.
5. Modification of the unit by the user himself
should absolutely be prohibited.
6. Tools and measuring instruments for use in repairs or inspection should be accurately calibrated in advance.
7. In installing the unit having been repaired, be careful to prevent the occurence of any accident such as
electrical shock, leak of current, or bodily injury due to the drop of any part.
8. To check the insulation of the unit, measure the insulation resistance between the power cord plug and
grounding terminal of the unit. The insulation resistance should be 1M or more as measured by a 500V
DC megger.
9. The initial location of installation such as window, floor or the other should be checked for being and safe
enough to support the repaired unit again.
If it is found not so strong and safe, the unit should be installed at the initial location after reinforced or at
a new location.
10. Any inflammable object must not
be placed about the location of
installation.
11. Check the grounding to see whether
it is proper or not, and if it is found
improper, connect the grounding
terminal to the earth.





– 2 –
WORKING STANDARDS FOR PREVENTING BREAKAGE OF SEMICONDUCTORS
1. Scope
The standards provide for items to be generally observed in carrying and handling semiconductors in relative
manufacturers during maintenance and handling thereof. (They apply the same to handling of abnormal
goods such as rejected goods being returned).
2. Object parts
(1) Micro computer
(2) Integrated circuits (I.C.)
(3) Field-effective transistor (F.E.T.)
(4) P.C. boards or the like to which the parts mentioned in (1) and (2) of this paragraph are equipped.
3. Items to be observed in handling
(1) Use a conductive container for carrying and storing of parts. (Even rejected goods should be handled
in the same way).
Fig. 1. Conductive container
(2) When any part is handled uncovered (in counting, packing and the like), the handling person must always
use himself as a body earth. (Make yourself a body earth by passing 1M earth resistance through a
ring or bracelet).
(3) Be careful not to touch the parts with your clothing when you hold a part even if a body earth is being
taken.
(4) Be sure to place a part on a metal plate with grounding.
(5) Be careful not to fail to turn off power when you repair the printed circuit board. At the same time, try
to repair the printed circuit board on a grounded metal plate.
1M
Fig. 2. Body Earth
Body earth
(Elimik conductive band)
Clip for connection with a
grounding wire
IC
A conductive polyvinyl bag IC
Conductive sponge
– 3 –
(6) Use a three wire type soldering iron including a grounding wire.
Bare copper wire (for body earth)
Working table
Resistor 1 M (1/2W)
Earth wire
Fig. 3. Grounding of the working table
2
Screw stop at the screwed
part using a rag plate
Soldering iron
Grounding wire
Fig. 4. Grounding a solder iron
Use a high insulation mode (100V, 10M or higher) when ordinary iron is to be used.
(7) In checking circuits for maintenance, inspection or some others, be careful not to have the test probes of
the measuring instrument short circuit a load circuit or the like.
Metal plate (of aluminium, stainless steel, etc.)
Staple
– 4 –
1. In quiet or stop operation, slight flowing noise of refrigerant in the refrigerating cycle is heard occasionally,
but this noise is not abnormal for the operation.
2. When it thunders nearby, it is recommend to stop the operation and to disconnect the power cord plug
from the power outlet for safety.
3. In the event of power failure, the air conditioner will restart automatically in the previously selected mode
once the power is restored. In the event of power failure during TIMER operation, the air conditioner will
not start automatically. Re-press ON/OFF button after 3 minutes from when the unit off or power recovery.
4. If the room air conditioner is stopped by adjusting thermostat, or missoperation, and re-start in a moment,
there is occasion that the cooling and heating operation does not start for 3 minutes, it is not abnormal
and this is the result of the operation of IC delay circuit. This IC delay circuit ensures that there is no
danger of blowing fuse or damaging parts even if operation is restarted accidentally.
5. This room air conditioner should not be used at the cooling operation when the outside temperature is
below –10°C (14°F).
6. This room air conditioner (the reverse cycle) should not be used when the outside temperature is below
–15°C (5°F).
If the reverse cycle is used under this condition, the outside heat exchanger is frosted and efficiency falls.
7. When the outside heat exchanger is frosted, the frost is melted by operating the hot gas system, it is not
trouble that at this time fan stops and the vapour may rise from the outside heat exchanger.
!
CAUTION
– 5 –
SPECIFICATIONS
MODEL
FAN MOTOR
FAN MOTOR CAPACITOR
FAN MOTOR PROTECTOR
COMPRESSOR
COMPRESSOR MOTOR CAPACITOR
OVERLOAD PROTECTOR
OVERHEAT PROTECTOR
FUSE (for MICROPROCESSOR)
POWER RELAY
POWER SWITCH
TEMPORARY SWITCH
SERVICE SWITCH
TRANSFORMER
VARISTOR
NOISE SUPPRESSOR
THERMOSTAT
REMOTE CONTROL SWITCH (LIQUID CRYSTAL)
47 W
NO
NO
JU151XC1
NO
YES
YES
5.0A
G4A
NO
NO
YES
NO
450NR
YES
YES(IC)
NO
2300gUNIT
REFRIGERANT CHARGING
VOLUME
(Refrigerant R410A)
WITHOUT REFRIGERANT BECAUSE
COUPLING IS FLARE TYPE.
PIPES (MAX.)
In case the pipe length is more than 30m, add refrigerant R410 at 20gram per every meter exceeds.
RAM-68NP3B
MAX. 60m
– 6 –
SPECIFICATIONS FOR INDOOR UNITS COMBINATION
OPERATION SCOPE
TYPE
DC INVERTER TRIPLE SYSTEM MULTI COOLING AND HEATING
MODEL OUTDOOR UNIT
PHASE/VOLTAGE/FREQUENCY
CIRCUIT AMPERES TO CONNECT (A)
COOLING
(THREE
UNITS)
CAPACITY (kW)
(B.T.U./h)
TOTAL INPUT (W)
EER (B.T.U./hW)
TOTAL AMPERES (A)
POWER FACTOR (%)
HEATING
(THREE
UNITS)
CAPACITY (kW)
(B.T.U./h)
TOTAL INPUT (W)
EER (B.T.U./hW)
TOTAL AMPERES (A)
POWER FACTOR (%)
MAXIMUM LENGTH OF PIPING
STANDARD
RAM-68NP3B
1ø, 220 - 240V, 50/60Hz
20A
6.80
23,200
2,080
11.15
9.55 - 8.75
99
8.50
29,010
2,280
12.72
10.5 - 9.6
99
MAX. 60m (THREE UNIT TOTAL)
CE (EMC&LVD)
RAM-68NP3B
MODEL
W
PACKING
(mm)
H
D
cu.ft.
1,008
848
394
11.89
63
GROSS WEIGHT (kg)
(6.35DX4)/(9.52DX3)
FLARE NUT SIZE (SMALL/LARGE)
INDOOR SUCTION
TEMPERATURE (˚C)
COOLING OPERATION SCOPE
OUTDOOR SUCTION
TEMPERATURE (˚C)
INDOOR SUCTION
HUMIDITY (%)
HEATING OPERATION SCOPE
16 ~ 32 -10 ~ 43 BELOW 80
BELOW 27 –15 ~ 21—
3 ROOM MULTI-SPLIT INVERTER TYPE RAC: RAM-68NP3B
POSSIBLE COMBINATION TO OPERATE (SAME TIME OPERATION)
POWER POWER
CONSUMPTION 220 - 230 - 240 CONSUMPTION 220 - 230 - 240
TOTAL (W) TOTAL (W)
1.50 400 2.00 560
(200-480) (320-850)
450 720
(280-500) (320-1130)
650 980
(280-720) (320-1480)
1030 1150
(280-1130) (320-1950)
1450 2030
(280-1800) (320-2530)
1.5 + 1.5 1.50 + 1.50 870 2.00 + 2.00 4.00 1080
(380-980) (200-1100)
1.5 + 1.8 1.50 + 1.80 3.30 950 2.00 + 2.50 4.50 1200
(380-1000) (200-1300)
1.5 + 2.5 1.50 + 2.50 4.00 1150 2.00 + 3.40 5.40 1450
(380-1300) (200-1780)
1.5 + 3.5 1.50 + 3.50 5.00 1450 2.00 + 4.30 6.30 1660
(380-1450) (200-2010)
1.5 + 5.0 1.50 + 5.00 6.50 1950 2.00 + 6.50 8.50 2200
(380-2380) (390-3120)
1.8 + 1.8 1.80 + 1.80 1020 2.50 + 2.50 1380
(380-1020) (390-2750)
1.8 + 2.5 1.80 + 2.50 1120 2.50 + 3.40 1610
(380-1360) (390-3000)
1.8 + 3.5 1.80 + 3.50 1600 2.50 + 4.30 1850
(380-1950) (390-3120)
1.8 + 5.0 1.80 + 5.00 2050 2.36 + 6.14 2350
(380-2820) (390-3120)
2.5 + 2.5 2.50 + 2.50 1410 3.40 + 3.40 2000
(380-1720) (390-3120)
2.5 + 3.5 2.50 + 3.50 1850 3.40 + 4.30 2120
(380-2380) (390-3120)
2.5 + 5.0 2.40 + 4.70 2060 2.92 + 5.58 2350
(380-2980) (390-3120)
3.5 + 3.5 3.50 + 3.50 2060 4.25 + 4.25 2350
(380-2940) (390-3120)
3.5 + 5.0 2.90 + 4.20 2060 3.38 + 5.12 2350
(380-2890) (390-3120)
5.0 + 5.0 3.55 + 3.55 2060 4.25 + 4.25 8.50 2350
(380-3170) (390-3120)
1.5 + 1.5 + 1.5 1.50 + 1.50 + 1.50 1400 2.00 + 2.00 + 2.00 1650
(420-1680) (430-1800)
1.5 + 1.5 + 1.8 1.50 + 1.50 + 1.80 1480 2.00 + 2.00 + 2.50 6.50 1750
(240-1880) (430-2100)
1.5 + 1.5 + 2.5 1.50 + 1.50 + 2.50 1680 2.00 + 2.00 + 3.40 7.40 2010
(420-2280) (430-2200)
1.5 + 1.5 + 3.5 1.50 + 1.50 + 3.50 2010 2.00 + 2.00 + 4.30 8.30 2260
(420-2480) (430-2500)
1.5 + 1.5 + 5.0 1.28 + 1.28 + 4.25 2100 1.62 + 1.62 + 5.26 8.50 2300
(420-2890) (430-2600)
1.5 + 1.8 + 1.8 1.50 + 1.80 + 1.80 1550 2.00 + 2.50 + 2.50 7.00 1900
(420-2280) (430-2400)
1.5 + 1.8 + 2.5 1.50 + 1.80 + 2.50 1800 2.00 + 2.50 + 3.40 7.90 2150
(420-2480) (430-2600)
1.5 + 1.8 + 3.5 1.50 + 1.80 + 3.50 2100 1.93 + 2.41 + 4.15 8.50 2290
(420-2480) (430-2600)
1.5 + 1.8 + 5.0 1.23 + 1.47 + 4.10 2100 1.55 + 1.93 + 5.02 8.50 2290
(420-2890) (430-2600)
1.5 + 2.5 + 2.5 1.50 + 2.50 + 2.50 2020 1.93 + 3.28 + 3.28 8.50 2290
(420-2480) (430-2600)
1.5 + 2.5 + 3.5 1.36 + 2.27 + 3.17 2100 1.75 + 2.98 + 3.77 8.50 2290
(420-2890) (430-2600)
1.5 + 2.5 + 5.0 1.13 + 1.89 + 3.78 2100 1.43 + 2.43 + 4.64 8.50 2310
(420-2960) (430-2600)
1.5 + 3.5 + 3.5 1.20 + 2.80 + 2.80 2100 1.60 + 3.45 + 3.45 8.50 2310
(420-2890) (430-2600)
1.5 + 3.5 + 5.0 1.02 + 2.38 + 3.40 2100 1.33 + 2.86 + 4.32 8.50 2310
(420-2960) (430-2600)
1.8 + 1.8 + 1.8 1.80 + 1.80 + 1.80 1450 2.50 + 2.50 + 2.50 7.50 2050
(420-2190) (430-2600)
1.8 + 1.8 + 2.5 1.80 + 1.80 + 2.50 1720 2.50 + 2.50 + 3.40 8.40 2290
(420-2480) (430-2600)
1.8 + 1.8 + 3.5 1.72 + 1.72 + 3.35 2080 2.28 + 2.28 + 3.93 8.50 2290
(420-2890) (430-2600)
1.8 + 1.8 + 5.0 1.42 + 1.42 + 3.95 2080 1.85 + 1.85 + 4.80 8.50 2280
(420-2960) (430-2600)
1.8 + 2.5 + 2.5 1.80 + 2.50 + 2.50 2080 2.28 + 3.11 + 3.11 8.50 2290
(420-2780) (430-2600)
1.8 + 2.5 + 3.5 1.57 + 2.18 + 3.05 2080 2.08 + 2.83 + 3.58 8.50 2290
(420-2960) (430-2600)
1.8 + 2.5 + 5.0 1.32 + 1.83 + 3.66 2080 1.71 + 2.33 + 4.46 8.50 2280
(440-2770) (430-2600)
1.8 + 3.5 + 3.5 1.39 + 2.70 + 2.70 2080 1.91 + 3.29 + 3.29 8.50 2290
(420-2960) (430-2600)
1.8 + 3.5 + 5.0 1.19 + 2.31 + 3.30 2080 1.60 + 2.75 + 4.15 8.50 2280
(420-2960) (430-2600)
2.5 + 2.5 + 2.5 2.27 + 2.27 + 2.27 2080 2.83 + 2.83 + 2.83 8.50 2290
(420-2890) (430-2600)
2.5 + 2.5 + 3.5 2.00 + 2.00 + 2.80 2080 2.60 + 2.60 + 3.29 8.50 2290
(420-2960) (430-2600)
2.5 + 2.5 + 5.0 1.70 + 1.70 + 3.40 2080 2.17 + 2.17 + 4.15 8.50 2280
(420-2960) (430-2600)
2.5 + 3.5 + 3.5 1.79 + 2.51 + 2.51 2080 2.41 + 3.05 + 3.05 8.50 2290
(420-2960) (430-2600)
2.5 + 3.5 + 5.0 1.55 + 2.16 + 3.09 2080 2.04 + 2.57 + 3.89 8.50 2280
(420-2960) (430-2600)
3.5 + 3.5 + 3.5 2.27 + 2.27 + 2.27 2080 2.83 + 2.83 + 2.83 8.50 2280
(420-2960) (430-2600)
<REMARKS>
*
ONE UNIT INDICATED ARE ONLY FOR ONE UNIT OPERATION WHEN TWO OR THREE INDOOR UNITS ARE CONNECTED.
*
TWO UNITS INDICATED ARE ONLY FOR TWO UNIT OPERATION WHEN TWO OR THREE INDOOR UNITS ARE CONNECTED.
*
THREE UNITS INDICATED ARE ONLY FOR THREE UNIT OPERATION WHEN THREE INDOOR UNITS ARE CONNECTED.
*Total nominal coolin
g
ca
p
acit
y
should not be more than 11kW.
ONE UNIT
- 9.6 3.73 A
(2.20-8.00) (2.40-9.50)
3.27 A 10.5 - 10.0
(2.20-8.00) (2.40-9.50)
8.75
10.0-
10.5 6.80 9.55 - 9.13 -
- 9.6 3.73 A3.27 A 10.5
A
(2.20-8.00) (2.40-9.50)
11.0 6.80 9.55 - 9.13 - 8.75
- 10.1 - 9.6 3.718.8 3.27 A 10.59.5 6.80 9.6 - 9.1 -
(2.20-8.00) (2.40-9.50) - 9.6 3.73 A3.27 A 10.5 - 10.0
A
(2.20-8.00) (2.40-9.50)
10.0 6.80 9.6 - 9.1 - 8.8
- 10.1 - 9.6 3.718.8 3.27 A 10.58.5 6.80 9.6 - 9.1 -
3.71 A
(2.20-7.80) (2.40-9.50)
3.27 A
(2.20-8.00) (2.40-9.50)
7.5 6.80 9.6 - 9.1 - 8.8
- 9.6
10.5 - 10.1 - 9.6
3.73 A3.27 A 10.5 - 10.0
A
(2.20-8.00) (2.40-9.50)
10.3 6.80 9.6 - 9.1 - 8.8
- 10.1 - 9.6 3.718.8 3.27 A 10.58.8 6.80 9.6 - 9.1 -
(2.20-8.00) (2.40-9.50) - 9.6 3.73 A3.27 A 10.5 - 10.0
A
(2.20-8.00) (2.40-9.50)
9.3 6.80 9.6 - 9.1 - 8.8
- 10.1 - 9.6 3.718.8 3.27 A 10.57.8 6.80 9.6 - 9.1 -
3.71 A
(2.20-7.50) (2.40-9.50)
3.27 A6.8 6.80 9.6 - 9.1 - 8.8 10.5 - 10.1 - 9.6
A
(2.20-8.00) (2.40-9.50) - 10.0 - 9.6 3.738.8 3.27 A 10.58.6 6.80 9.6 - 9.1 -
3.71 A
(2.20-7.80) (2.40-9.50)
3.27 A
(2.20-6.70) (2.40-9.50)
7.1 6.80 9.6 - 9.1 - 8.8
- 9.6
10.5 - 10.1 - 9.6
3.67 A3.55 A 10.5 - 10.1
A
(2.20-5.90) (2.40-9.50)
6.1 6.10 7.9 - 7.6 - 7.2
- 9.0 - 8.6 3.666.1 3.72 A 9.45.4 5.40 6.7 - 6.4 -
3.68 A
(2.20-8.00) (2.40-9.50)
3.24 A
(2.20-8.00) (2.40-9.50)
10.0 6.80 9.6 - 9.2 - 8.8
- 9.7
10.6 - 10.1 - 9.7
3.68 A3.24 A 10.6 - 10.18.5 6.80 9.6 - 9.2 - 8.8
3.68 A
(2.20-8.00) (2.40-9.50)
3.24 A
(2.20-7.80) (2.40-9.50)
9.0 6.80 9.6 - 9.2 - 8.8
- 9.6
10.6 - 10.1 - 9.7
3.71 A3.24 A 10.5 - 10.1
A
(1.50-7.00) (2.40-9.50)
7.5 6.80 9.6 - 9.2 - 8.8
- 10.1 - 9.6 3.718.5 3.22 A 10.56.5 6.50 9.3 - 8.9 -
(2.20-7.50) (2.40-9.50) - 9.6 3.71 A3.24 A 10.5 - 10.1
(2.20-7.50) (2.40-9.50)
8.3 6.80 9.6 - 9.2 - 8.8
10.1 - 9.6 3.71 A3.24 A 10.5 -
A
(2.20-6.30) (2.40-9.50)
6.8 6.80 9.6 - 9.2 - 8.8
- 9.4 - 9.0 3.677.6 3.22 A 9.95.8 5.80 8.3 - 7.9 -
3.68 A
(2.20-5.60) (2.20-9.30)
3.29 A5.1 5.10 7.1 - 6.8 - 6.5 8.7 - 8.3 - 8.0
A
(2.20-7.50) (2.40-9.50) - 10.1 - 9.7 3.708.8 3.24 A 10.68.0 6.80 9.6 - 9.2 -
3.67 A
(2.20-7.00) (2.40-9.50)
3.23 A
(2.20-6.00) (2.20-9.30)
6.5 6.50 9.2 - 8.8 - 8.5
- 8.5
10.4 - 9.9 - 9.5
3.68 A3.27 A 9.2 - 8.8
A
(2.20-5.50) (2.40-7.00)
5.5 5.50 7.7 - 7.4 - 7.1
- 7.7 - 7.4 3.716.2 3.24 A 8.0
3.64 A
(2.20-5.00) (2.40-6.50)
4.8 4.80 6.8 - 6.5 -
7.6 - 7.2 - 6.95.9 3.21 A 6.004.5 4.50 6.4 - 6.1 -
THREE UNITS
A
(2.00-8.00) (2.20-9.50) - 10.3 - 9.9 3.628.7 3.30 A 10.810.0 6.80 9.5 - 9.0 -
3.62 A
(2.00-7.50) (2.20-9.50) 10.8 - 10.3 - 9.98.7 3.30 A 8.50
3.62 A
(2.00-7.40) (2.20-9.50)
8.5 6.80 9.5 - 9.0 -
10.8 - 10.3 - 9.98.7 3.30 A 8.507.0 6.80 9.5 - 9.0 -
3.62 A
(2.00-7.50) (2.20-9.50) 10.8 - 10.3 - 9.98.7 3.30 A 8.50
3.63 A
(2.00-6.60) (2.20-9.50)
7.5 6.80 9.5 - 9.0 -
9.7 - 9.3 - 8.97.8 3.24 A 7.70
3.40 B
(2.00-5.50) (2.20-9.50)
6.0 6.00 8.5 - 8.1 -
9.2 - 8.8 - 8.45.9 3.55 A 6.805.0 5.00 6.5 - 6.2 -
3.62 A
(2.00-7.10) (2.20-9.50) 10.8 - 10.3 - 9.98.6 3.32 A 8.50
3.68 A
(2.00-5.80) (2.20-7.20)
6.8 6.80 9.4 - 9.0 -
8.5 - 8.1 - 7.86.7 3.31 A 6.80
3.66 A
(2.00-4.70) (2.20-7.20)
5.3 5.30 7.3 - 7.0 -
7.4 - 7.1 - 6.84.7 3.84 A 5.90
3.62 A
(2.00-4.00) (2.20-6.40)
4.3 4.30 5.1 - 4.9 -
6.3 - 6.1 - 5.84.3 3.53 A 5.003.6 3.60 4.7 - 4.5 -
9.7 - 9.3 3.86 A3.33 A 10.1 -
(2.20-7.20)
6.5 9.0 - 8.6 - 8.2
(1.50-5.90)
7.3 - 7.0 3.80 A3.45 A 7.6 -
(2.20-7.20)
5.0 6.7 - 6.4 - 6.1
(1.50-5.20)
6.4 - 6.1 3.72 A3.48 A 6.7 -
(2.20-6.40)
4.0 5.3 - 5.1 - 4.8
(1.50-4.00)
- 5.1 3.75 A
(1.50-3.50) (2.20-5.20)
3.47 A 5.5 - 5.3
A
(1.50-2.80) (2.20-4.70) - 4.7 -
3.3 4.4 - 4.2 - 4.0
4.5 3.703.7 3.45 A 5.03.0 3.00 4.0 - 3.8 -
TWO UNITS
8.9 - 8.5 3.20 C
6.50 6.50 9.3 -
(1.80-7.20)
6.4 - 6.1 3.45 A5.0 5.0 5.00 5.00 6.7 -
(1.50-5.60)
5.1 - 4.8 3.74 A
4.30 4.30 5.3 -
(1.80-5.80)
4.5 - 4.3 3.40 A3.5 3.5 3.50 3.50 4.7 -
(1.50-3.90)
4.3 - 4.1 3.47 B
3.40 3.40 4.5 -
(1.80-4.70)
2.9 - 2.7 3.85 A2.5 2.5 2.50 2.50 3.0 -
(1.50-2.80)
3.0 3.47 B
(1.50-2.00) (1.80-3.50)
2.50 2.50 3.3 -2.0 - 3.2 -1.9 4.00 A1.8 1.8 1.80 1.80 2.1 -
- 2.4 3.57 B
(1.00-1.60) (1.10-2.20)
2.00 2.6 - 2.51.8 - 1.7 3.75 A1.5 1.5 1.50 1.8 -
COP
energy
efficie
ncy
class
RATING (kW) AMPERE (A) at RATING (kW) AMPERE (A) at
(RANGE) (RANGE)
POSSIBLE COMBINATIONS TO
OPERATE
COOLING HEATING
CAPACITY OUTDOOR UNIT
EER
energy
efficie
ncy
class
CAPACITY OUTDOOR UNIT
– 9 –
TRIPLE SYSTEM MULTI R.A.C. RAM-68NP3B INDOOR UNITS
COMBINATIONS TO BE ABLE TO INSTALL
Two or three indoor units can be installed with one outdoor unit. And
total nominal cooling capacity should not be more than 11.0kW
Be sure to connect two or three indoor units to this outdoor unit. If not, condensed water may drop,
resulting in trouble.
– 10 –
TRIPLE RAM-68NP3B
No.1 No.2 No.3
6.35/9.52D 6.35/9.52D 6.35/9.52D
1.5 1.5
1.5 1.8
1.5 2.5
1.5 3.5
1.5 ⊙ 5.0
1.8 1.8
1.8 2.5
1.8 3.5
1.8 ⊙ 5.0
2.5 2.5
2.5 3.5
2.5 ⊙ 5.0
3.5 3.5
3.5 ⊙ 5.0
⊙ 5.0 ⊙ 5.0
1.5 1.5 1.5
1.5 1.5 1.8
1.5 1.5 2.5
1.5 1.5 3.5
1.5 1.5 ⊙ 5.0
1.5 1.8 1.8
1.5 1.8 2.5
1.5 1.8 3.5
1.5 1.8 ⊙ 5.0
1.5 2.5 2.5
1.5 2.5 3.5
1.5 2.5 ⊙ 5.0
1.5 3.5 3.5
1.5 3.5 ⊙ 5.0
1.8 1.8 1.8
1.8 1.8 2.5
1.8 1.8 3.5
1.8 1.8 ⊙ 5.0
1.8 2.5 2.5
1.8 2.5 3.5
1.8 2.5 ⊙ 5.0
1.8 3.5 3.5
1.8 3.5 ⊙ 5.0
2.5 2.5 2.5
2.5 2.5 3.5
2.5 2.5 ⊙ 5.0
2.5 3.5 3.5
2.5 3.5 ⊙ 5.0
3.5 3.5 3.5
CONNECTING POSITION ON OUTDOOR
UNIT (VALVE DIAMETER)(mm)
2.5 3.5 5.0 (8 ~ 12) (9 ~ 15) (14 ~ 21)
3.5 3.5 3.5 (11 ~ 16) (11 ~ 16) (11 ~ 16)
2.5 2.5 5.0 (8 ~ 12) (8 ~ 12) (16 ~ 24)
2.5 3.5 3.5 (8 ~ 13) (11 ~ 17) (11 ~ 17)
2.5 2.5 2.5 (11 ~ 16) (11 ~ 16) (11 ~ 16)
2.5 2.5 3.5 (9 ~ 14) (9 ~ 14) (12 ~ 19)
1.8 3.5 3.5 (7 ~ 11) (12 ~ 19) (12 ~ 19)
1.8 3.5 5.0 (6 ~ 10) (11 ~ 16) (15 ~ 23)
1.8 2.5 3.5 (8 ~ 12) (9 ~ 15) (14 ~ 21)
1.8 2.5 5.0 (7 ~ 11) (8 ~ 13) (17 ~ 25)
1.8 1.8 5.0 (7 ~ 11) (7 ~ 11) (18 ~ 27)
1.8 2.5 2.5 (8 ~ 12) (11 ~ 17) (11 ~ 17)
1.8 1.8 2.5 (8 ~ 12) (8 ~ 12) (11 ~ 17)
1.8 1.8 3.5 (8 ~ 12) (8 ~ 12) (15 ~ 23)
1.5 3.5 5.0 (6 ~ 9) (16 ~ 24) (16 ~ 24)
1.8 1.8 1.8 (8 ~ 12) (8 ~ 12) (8 ~ 12)
1.5 2.5 5.0 (6 ~ 10) (8 ~ 13) (18 ~ 26)
1.5 3.5 3.5 (6 ~ 10) (12 ~ 19) (12 ~ 19)
1.5 2.5 2.5 (8 ~ 12) (11 ~ 17) (11 ~ 17)
1.5 2.5 3.5 (7 ~ 11) (11 ~ 16) (14 ~ 22)
1.5 1.8 3.5 (8 ~ 12) (8 ~ 12) (16 ~ 24)
1.5 1.8 5.0 (7 ~ 10) (8 ~ 12) (19 ~ 28)
1.5 1.5 5.0 (7 ~ 11) (7 ~ 11) (20 ~ 29)
1.5 1.8 1.8 (8 ~ 12) (8 ~ 12) (8 ~ 12)
1.5 1.8 2.5 (8 ~ 12) (8 ~ 12) (11 ~ 17)
THREE UNITS
1.5 1.5 1.5 (8 ~ 12) (8 ~ 12) (8 ~ 12)
1.5 1.5 1.8 (8 ~ 12) (8 ~ 12) (8 ~ 12)
1.5 1.5 2.5 (8 ~ 12) (8 ~ 12) (11 ~ 17)
3.5 5.0 (12 ~ 19) (19 ~ 27)
5.0 5.0 (16 ~ 24) (16 ~ 24)
2.5 5.0 (9 ~ 15) (22 ~ 31)
3.5 3.5 (16 ~ 24) (16 ~ 24)
1.5 1.5 3.5 (8 ~ 12) (8 ~ 12) (16 ~ 24)
2.5 2.5 (11 ~ 17) (11 ~ 17)
2.5 3.5 (11 ~ 17) (16 ~ 24)
1.8 3.5 (8 ~ 12) (16 ~ 24)
1.8 5.0 (8 ~ 12) (23 ~ 34)
1.8 1.8 (8 ~ 12) (8 ~ 12)
1.8 2.5 (8 ~ 12) (11 ~ 17)
1.5 3.5 (8 ~ 12) (16 ~ 24)
1.5 5.0 (8 ~ 12) (23 ~ 34)
1.5 1.8 (8 ~ 12) (8 ~ 12)
1.5 2.5 (8 ~ 12) (11 ~ 17)
POSSIBLE COMBINATIONS TO
INSTALL (kW) SUITABLE ROOM SIZE TO INSTALL (m²)
TWO UNITS
1.5 1.5 (8 ~ 12) (8 ~ 12)
1.5, 2.5, 3.5 & 5.0
– 11 –



– 12 –
– 13 –
– 14 –
– 15 –
three
– 16 –
One unit of 1.5kW, 1.8kW, 2.5kW, 3.5kW or 5.0kW
(5kW unit: Optional flare adaptor for piping is
necessary.)
One unit of 1.5kW, 1.8kW, 2.5kW, 3.5kW or 5.0kW
(5kW unit: Optional flare adaptor for piping is
necessary.)
One unit of 1.5kW, 1.8kW, 2.5kW, 3.5kW or 5.0kW
(5kW unit: Optional flare adaptor for piping is
necessary.)
– 17 –
– 19 –
1 2 3 1 2 3 1 2 3
RAM-68NP3B
– 19 –
RAM-68NP3B
– 20 –
9a&'
:
0
RAM-68NP3B

Other manuals for RAM-68NP3B

1

Other Hitachi Air Conditioner manuals

Hitachi RAS-S10H2 User manual

Hitachi

Hitachi RAS-S10H2 User manual

Hitachi RAS-25WX8 User manual

Hitachi

Hitachi RAS-25WX8 User manual

Hitachi RAS-07CH6 User manual

Hitachi

Hitachi RAS-07CH6 User manual

Hitachi RAS-24MH1 User manual

Hitachi

Hitachi RAS-24MH1 User manual

Hitachi RAK-AH05PCASN User manual

Hitachi

Hitachi RAK-AH05PCASN User manual

Hitachi air365 Max Series Instruction Manual

Hitachi

Hitachi air365 Max Series Instruction Manual

Hitachi RAC-AH10PCASM User manual

Hitachi

Hitachi RAC-AH10PCASM User manual

Hitachi YUTAKI Series Manual

Hitachi

Hitachi YUTAKI Series Manual

Hitachi RAS-10QH5E User manual

Hitachi

Hitachi RAS-10QH5E User manual

Hitachi RAI-25NH5 User manual

Hitachi

Hitachi RAI-25NH5 User manual

Hitachi RAM-90QH5 User manual

Hitachi

Hitachi RAM-90QH5 User manual

Hitachi RAS-10JH1 User manual

Hitachi

Hitachi RAS-10JH1 User manual

Hitachi RPI-0.8FSNQL(H) Instruction Manual

Hitachi

Hitachi RPI-0.8FSNQL(H) Instruction Manual

Hitachi CJ Series User manual

Hitachi

Hitachi CJ Series User manual

Hitachi RAS-S33H2A User manual

Hitachi

Hitachi RAS-S33H2A User manual

Hitachi RAC-25RPA User manual

Hitachi

Hitachi RAC-25RPA User manual

Hitachi YUTAKI RAS-5WHVNPE User manual

Hitachi

Hitachi YUTAKI RAS-5WHVNPE User manual

Hitachi RAK-18NH6AS User manual

Hitachi

Hitachi RAK-18NH6AS User manual

Hitachi RAC-18WED User manual

Hitachi

Hitachi RAC-18WED User manual

Hitachi RAC-L24GHZ User manual

Hitachi

Hitachi RAC-L24GHZ User manual

Hitachi RAS-25CNH2 User manual

Hitachi

Hitachi RAS-25CNH2 User manual

Hitachi RAC-70YHA1 User manual

Hitachi

Hitachi RAC-70YHA1 User manual

Hitachi RPC-1.5FSR Owner's manual

Hitachi

Hitachi RPC-1.5FSR Owner's manual

Hitachi RAS-08HT User manual

Hitachi

Hitachi RAS-08HT User manual

Popular Air Conditioner manuals by other brands

Retro Aire R30C Installation, operation & maintenance manual

Retro Aire

Retro Aire R30C Installation, operation & maintenance manual

Mitsubishi Heavy Industries DXK05ZTLA-WF user manual

Mitsubishi Heavy Industries

Mitsubishi Heavy Industries DXK05ZTLA-WF user manual

Celair Profile Series owner's manual

Celair

Celair Profile Series owner's manual

Mitsubishi Electric MSZ-LN18VG2W operating instructions

Mitsubishi Electric

Mitsubishi Electric MSZ-LN18VG2W operating instructions

Webasto Frigo Top 25 DS Instructions for use

Webasto

Webasto Frigo Top 25 DS Instructions for use

Toshiba RAC-PD0811CRU user manual

Toshiba

Toshiba RAC-PD0811CRU user manual

Haier HC1891VAR Installation & operation manual

Haier

Haier HC1891VAR Installation & operation manual

Honeywell CL20AE user manual

Honeywell

Honeywell CL20AE user manual

ACS Marvair 8AA1024A-8AA1060A product manual

ACS

ACS Marvair 8AA1024A-8AA1060A product manual

Mitsubishi Electric PLA-SP BA Series Operation manual

Mitsubishi Electric

Mitsubishi Electric PLA-SP BA Series Operation manual

Haier AU362XHERA installation manual

Haier

Haier AU362XHERA installation manual

Frigidaire LRA257ST21 Use & care guide

Frigidaire

Frigidaire LRA257ST21 Use & care guide

Gree GWHD(14)NK6OO(LC)(LH) Service manual

Gree

Gree GWHD(14)NK6OO(LC)(LH) Service manual

GREE ELECTRIC GWH09TA-S3DNA1C Service manual

GREE ELECTRIC

GREE ELECTRIC GWH09TA-S3DNA1C Service manual

nedis ACMB1WT9 quick start guide

nedis

nedis ACMB1WT9 quick start guide

Mitsubishi PQHY-P200YGM-A installation manual

Mitsubishi

Mitsubishi PQHY-P200YGM-A installation manual

Carrier ROOM AIR CONDITIONER operating manual

Carrier

Carrier ROOM AIR CONDITIONER operating manual

Mars COMFORT-AIRE PS-81G Owner's manual & installation manual

Mars

Mars COMFORT-AIRE PS-81G Owner's manual & installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.