HK DPT-DUAL Series User manual

Copyright HK Instruments 2019 www.hkinstruments. Installaon version 8.0 2019
INSTALLATION
INSTRUCTIONS
DIFFERENTIAL PRESSURE TRANSMITTERS
DPT-Dual Series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
SPECIFICATIONS
Thank you for choosing an HK Instruments DPT-Dual series dif-
ferenalpressuretransmier.DPT-Dualcombinestwodierenal
pressuretransmiersintoonedevice.Itoersapossibilitytomeas-
urepressurefromtwodierentpoints.DPT-Dualisdesignedwith
veunitselecons(Pa,kPa,mbar,inchWC,mmWC)andeighteld
selectablemeasurementranges(unidireconalandbi-direconal)to
meet your applicaon requirements. The DPT-Dual series is com-
prisedoftheDPT-Dual-2500withrangesfrom-100–2500Paand
DPT-Dual-7000withrangesfrom0–7000Pa.
DPT-DualseriesdevicesarecommonlyusedinHVAC/R
systems for:
•fan,blowerandltermonitoring
•pressureandowmonitoring
•valveanddampercontrol
SPECIFICATIONS
Performance
Accuracy (from applied pressure):
Model2500:
Pressure<125Pa=1%+±2Pa
Pressure>125Pa=1%+±1Pa
Model7000:
Pressure<125Pa=1.5%+±2Pa
Pressure>125Pa=1.5%+±1Pa
(including:generalaccuracy,linearity,hysteresis,long
termstability,andrepeonerror)
Overpressure:
Proofpressure:25kPa
Burstpressure:30kPa
Zero point calibraon:
Manualpushbuon
Response me:
4.0sor0.8s,selectableviajumper
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
Pa,kPa,mbar,inchWC,mmWC,selectableviajumper
Measuring element:
MEMSnoow-through
Environment:
Operangtemperature:-20...+50°C
Temperaturecompensatedrange0...+50°C
Storagetemperature:-40...+70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:102.0x71.5x36.0mm
Weight:
150g,withaccessories290g
Mounng:
2each4.3mmscrewholes,onesloed
Materials:
Case: ABS
Lid:PC
Pressure inlets: Brass
Ductconnectors:ABS
Tubing:PVC
Protecon standard:
IP54
Display (Oponal)
2-linedisplay(12characters/line)
Line1:acvemeasurement,inletA
Line2:acvemeasurement,inletB
Electrical connecons:
4springloadesterminals,max1.5mm2
Wire:0.2–1.5mm2(12–24AWG)
Cableentry:M20
Pressure ngs:
Maleø5.0mmand6.3mm
Electrical
Voltage:
Circuit:3-wire(VOut,24V,GND)
Input:24VACorVDC,±10%
Output:2x0...5/10V(selectableviajumper)
Powerconsumpon:<1.0W
Resistanceminimum:1kΩ
Conformance
MeetsrequirementsforCEmarking:
EMCDirecve2014/30/EU
RoHSDirecve2011/65/EU
WEEEDirecve2012/19/EU
INTRODUCTION WARNING
APPLICATIONS
RoHS 2
2011/65/EU
COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 = ISO 14001 =

Copyright HK Instruments 2019 www.hkinstruments. Installaon version 8.0 2019
SCHEMATICS
DIMENSIONAL DRAWINGS
INSTALLATION
Figure 1a - Surface mounng
STEP 1: MOUNTING THE DEVICE
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Openthelidandroutethecablethroughthestrainreliefand
connectthewirestotheterminalblock(s)(seestep2).
3)Thedeviceisnowreadyforconguraon.
WARNING!Applypoweronlyaerthedeviceisproperlywired.
1)Selectthemounnglocaon(duct,wall,panel).
2)Usethedeviceasatemplateandmarkthescrewholes.
3)Mountwithappropriatescrews.
Figure 1b - Mounng orientaon
Figure 1c - Applicaon connecons
Display connecon
Output 0–10 V
Output 0–10 V
24 V
GND
LED
Zero buon
Terminal
block
Pressure
sensors
Pressure
inlet A Pressure
inlet B
J1
J2
J3
J4
J5
J6
J7
J8
J9
Jumpers
YES NO NO
Stac pressure Filter/Damper
monitoring
Fan/Blower
monitoring
Not
connected

Copyright HK Instruments 2019 www.hkinstruments. Installaon version 8.0 2019
STEP 2: WIRING DIAGRAMS
ForCEcompliance,aproperlygroundedshieldingcableisrequired.
1)Unscrewthestrainreliefandroutethecable(s).
2)Connectthewiresasshowningure2.
3)Tightenthestrainrelief.
Figure 2 - Wiring diagram
STEP 3: CONFIGURATION
1)Selectthedesiredmeasurementunit.(seestep4)
2)Selectthedesiredmeasurementrange.(seestep5)
3)Selectthedesiredresponseme.(seestep6)
4)Zerothedevice.(seestep7)
5)Connectthepressuretubes.Connectposivepressuretoport
labeled“+”andnegavepressuretoport“-”.
6)Closethelid.Thedeviceisnowreadytobeused.
STEP 5: SELECTING THE MEASUREMENT RANGE
0–10 V
0–10 V
24 V
GND
+Power Supply
24VDC / 24VAC
V
STEP 4: SELECTING THE MEASUREMENT UNIT
1)Tochangethemeasurementunitappearingonthedisplay,installa
jumpertobothpinsofJ8(seeFigure3).
2)Pushdownthezerobuonandthemeasurementunitopons(Pa,
kPa,mbar,inchWC,mmWC)willcycleonthedisplay.
3)Toselectaunitopontodisplay,removethejumperfromJ8
whilethemeasurementunitisvisibleonthedisplay.
SELECTING THE MEASUREMENT UNIT CONTINUED
Figure 3 - Jumper installaon
No jumper
Circuit open
Jumper storedJumper installed
Circuit closed
(Grey colour indicates that a jumper is installed)
Chart 1
Model DPT-Dual-2500
Range 1 Range 2 Range 3 Range 4 Range 5 Range 6 Range 7 Range 8
Pa
kPa
mbar
inchWC
-100–100
-0.10–0.10
-1.00–1.00
-0.40–0.40
0–100
0–0.10
0–1.00
0–0.40
0–250
0–0.25
0–2.50
0–1.00
0–500
0–0.50
0–5.00
0–2.00
0–1000
0–1.00
0–10.0
0–4.00
0–1500
0–1.50
0–15.0
0–6.00
0–2000
0–2.00
0–20.0
0–8.00
0–2500
0–2.50
0–25.0
0–10.00
Model DPT-Dual-7000
Pa
kPa
mbar
inchWC
0–1000
0–1.00
0–10.0
0–4.00
0–1500
0–1.50
0–15.0
0–6.00
0–2000
0–2.0
0–20.0
0–8.00
0–2500
0–2.50
0–25.0
0–10.0
0–3000
0–3.00
0–30.0
0–12.00
0–4000
0–4.00
0–40.0
0–16.00
0–5000
0–5.00
0–50.0
0–20.00
0–7000
0–7.00
0–70.0
0–28.00
Range 1 Range 2 Range 3 Range 4 Range 5 Range 6 Range 7 Range 8
mmWC
mmWC
-10.2–10.2 0–10.2 0–25.5 0–51.0 0–102.0 0–153.0 0–204.0 0–255.0
0–102.0 0–153.0 0–204.0 0–255.0 0–306.0 0–408.0 0–510.0 0–714.0
1)Determinetherangenumber
a.FindthemodelinChart1.
b.Findthemeasurementunit(selectedinstep4).
c.Findtherequiredmeasurementrangeonthesamelineasthe
measurementunit(babove)anddeterminetherangenumberinthe
header.
2)ForinletA:InstalljumpersonJ1,J2andJ3asrequired.
a.Usingtherangenumberfrom1cabove,ndthecorresponding
rangenumberinChart2.
b.InstalljumpersonJ1,J2andJ3ondevice,asshownundertherange
numberinChart2.(Greycolourindicatesthatajumperisinstalled.
Referencegure3forjumperinstallaon.)

Copyright HK Instruments 2019 www.hkinstruments. Installaon version 8.0 2019
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsideredtostartonthedeliverydateoftheproduct.Ifadefectin
rawmaterialsoraproduconawisfound,thesellerisobligated,when
theproductissenttothesellerwithoutdelayorbeforeexpiraonof
thewarranty,toamendthemistakeathis/herdiscreoneitherbyre-
pairingthedefecveproductorbydeliveringfreeofchargetothebuy-
eranewawlessproductandsendingittothebuyer.Deliverycosts
fortherepairunderwarrantywillbepaidbythebuyerandthereturn
costsbytheseller.Thewarrantydoesnotcomprisedamagescausedby
accident, lightning, ood or other natural phenomenon, normal wear
andtear,improperorcarelesshandling,abnormaluse,overloading,im-
properstorage,incorrectcareorreconstrucon,orchangesandinstal-
laonworknotdonebythesellerorhis/herauthorizedrepresentave.
Theseleconofmaterialsfordevicespronetocorrosionisthebuyer’s
responsibility,unlessotherwiseislegallyagreedupon.Shouldtheman-
ufactureralterthestructureofthedevice,thesellerisnotobligatedto
makecomparablechangestodevicesalreadypurchased.Appealingfor
warrantyrequiresthatthebuyerhascorrectlyfullledhis/herdues
arisenfromthedeliveryandstatedinthecontract.Thesellerwillgive
anewwarrantyforgoodsthathavebeenreplacedorrepairedwithin
thewarranty,howeveronlytotheexpiraonoftheoriginalproduct’s
warrantyme.Thewarrantyincludestherepairofadefecvepartor
device, orifneeded,a new partordevice,butnotinstallaonorex-
change costs. Underno circumstanceisthe seller liable fordamages
compensaonforindirectdamage.
SELECTING THE MEASUREMENT RANGE CONTINUED
Chart 2 - Inlet A
Range 7 Range 8Range 1 Range 2 Range 3 Range 4 Range 5 Range 6
Jumper J1
Jumper J2
Jumper J3
(Grey colour indicates that a jumper is installed. Reference Figure 3 and Schemacs for jumper installaon.)
3)ForinletB:InstalljumpersonJ4,J5andJ6asrequired.
a.Usingtherangenumberfrom1cabove,ndthecorresponding
rangenumberinChart3.
b.InstalljumpersonJ4,J5andJ6ondevice,asshownundertherange
numberinChart3.(Greycolourindicatesthatajumperisinstalled.
Referencegure3forjumperinstallaon.)
Chart 3 - Inlet B
Range 7 Range 8Range 1 Range 2 Range 3 Range 4 Range 5 Range 6
Jumper J4
Jumper J5
Jumper J6
(Grey colour indicates that a jumper is installed. Reference Figure 3 and Schemacs for jumper installaon.)
STEP 6: SELECTING THE RESPONSE TIME
Theresponsemeaectshowfastthetransmierreactstochangesin
thesystem.Theresponsemeisthemethedevicetakestoreach63
%ofthemeasuredvalue.Tosmoothoutunstablepressureuctuaons
inairowapplicaons,selectalongerresponseme.
Example:
Selectedresponseme:4.0seconds
Result: Output signal achieves a new value in 20 seconds (Response
me*5)
Tochangeresponseme,installorremovejumperonJ7.
(seeFigure3)
1)InstalljumperonJ7for4.0secondresponseme.
2)RemovejumperfromJ7for0.8secondresponseme.
NOTE:Thiswillchangetheresponsemeforbothdierenalpressure
measurements.
WARRANTY POLICY
STEP 7: ZEROING THE DEVICE
NOTE! Always zero the device before use.
ManualPushbuonzeropointcalibraon:
NOTE: Supply voltage must be connected at least one hour prior to
zeropointadjustment.
a)Disconnectbothpressuretubesfromthepressureportslabeled+
and–.
b)PushdownthezerobuonunltheLEDlight(red)turnsonand
thedisplayreads“zeroing”(displayopononly).(seeFigure4)
c)Thezeroingofthedevicewillproceedautomacally.Zeroingis
completewhentheLEDturnso,andthedisplayreads0(display
opononly).
ZEROING THE DEVICE CONTINUED
d)ReinstallthepressuretubesensuringthattheHighpressuretube
isconnectedtotheportlabeled+,andtheLowpressuretubeis
connectedtotheportlabeled−.
Figure 4
a) Disconnect both pressure tubes from the pressure ports labeled +
and –.
b) Push down the zero buon (joysck) unl the LED light (red)
turns on and the display reads “zeroing” (display opon only). (see
Figure 6)
c) The zeroing of the device will proceed automacally. Zeroing is
complete when the LED turns off, and the display reads 0 (display
opon only).
d) Reinstall the pressure tubes, ensuring the High pressure tube is
connected to the port labeled +, and the Low pressure tube is
connected to the port labeled −.
Press down buon
LED turns ON
Display reads “Zeroing”
LED
RECYCLING/DISPOSAL
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
This manual suits for next models