Hochiki America Corporation
7051 Village Drive, Suite 100 • Buena Park, CA 90621-2268
Phone: 714/522-2246 • Fax: 714/522-2268
DESCRIPTION
STANDARD FEATURES OPERATION
1. Pull out the measuring unit drawer to expose the
metersand ACplug connector.
2. Remove the AC cord. Connect one end to the AC
plug connector and the other end to a 120VAC
electrical outlet.
3. Turn the AC source switch on. The circulating fan
starts.
4. Allow five minutes for warm-up to ensure stability
of the testing circuits.
5. Open the top cover and locate the wire leads and
clip.
6. If you are using a detector base, connect the wire
leads to this base and mount the base to the
woodeninstallationplate provided.
Terminal Markings: Source cable (not used)
Signal line (+)
Common line (-)
Configuring the TSA-B110
7. Use the photo/ion change-over switch to
choosethe typeof detector(ION orPHOTO) which
is to be tested.
8. Use the voltage adjustment knob to adjust the
voltageto agreewith theratedvoltage ofthe detec-
torbeing tested(for SLK-12use 17.0 VDC).
9. Use the densitometer “0” adjustment knob to
set the pointer to zero (0). Continued on back.
TSA-B110 SMOKE DETECTOR SENSITIVITY TESTER
Specifications subject to change without notice.
SPECIFICATIONS
The Hochiki America TSA-B110 Smoke Detector Sen-
sitivityTesteris designedfor efficientand accuratetest-
ing of the sensitivity of smoke detectors. For ease of
use in field applications the tester is easy to transport
andcompact. Two densitometercircuits allowtheTSA-
B110 Smoke Detector Sensitivity Tester to test both
ionizationand photoelectricsmoke detectors.
TheTSA-B110 SmokeDetector SensitivityTester isa
sensitivepiece ofelectronic equipment.The unitmust
beused inatemperaturerangeof50°Fto 86°F.Sudden
jarring or dropping of the TSA-B110 may damage the
unit. Operation will be affected if proper care is not
taken.
•Tests the sensitivity of Hochiki's previous model
photoelectric and ionization smoke detectors.
•Lightweight and portable for easy use in the field.
•Obscuration/sensitivity testing similar to that of a
UL 268 Smoke Box.
•Voltage Adjustment Knob easily changes tester
voltageto therated voltageofthe detector.
•Indicator lamp automatically lights at completion
oftesting.
RatedVoltage 120 V AC, 50/60 Hz
Source Voltage 108V - 132V AC
SmokeGenerating
Material SM-101-P Punk Stick
OperatingTemperature
Range 50°Fto 86°F
Dimensions 15.74" x 11.02" x 7.87"
Weight 13 Lbs.