manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Hochiki
  6. •
  7. Test Equipment
  8. •
  9. Hochiki TSA-B110 User manual

Hochiki TSA-B110 User manual

Hochiki America Corporation
7051 Village Drive, Suite 100 • Buena Park, CA 90621-2268
Phone: 714/522-2246 • Fax: 714/522-2268
TechnicalSupport:800/845-6692or[email protected] 08/2001
DESCRIPTION
STANDARD FEATURES OPERATION
1. Pull out the measuring unit drawer to expose the
metersand ACplug connector.
2. Remove the AC cord. Connect one end to the AC
plug connector and the other end to a 120VAC
electrical outlet.
3. Turn the AC source switch on. The circulating fan
starts.
4. Allow five minutes for warm-up to ensure stability
of the testing circuits.
5. Open the top cover and locate the wire leads and
clip.
6. If you are using a detector base, connect the wire
leads to this base and mount the base to the
woodeninstallationplate provided.
Terminal Markings: Source cable (not used)
Signal line (+)
Common line (-)
Configuring the TSA-B110
7. Use the photo/ion change-over switch to
choosethe typeof detector(ION orPHOTO) which
is to be tested.
8. Use the voltage adjustment knob to adjust the
voltageto agreewith theratedvoltage ofthe detec-
torbeing tested(for SLK-12use 17.0 VDC).
9. Use the densitometer “0” adjustment knob to
set the pointer to zero (0). Continued on back.
TSA-B110 SMOKE DETECTOR SENSITIVITY TESTER
Specifications subject to change without notice.
SPECIFICATIONS
The Hochiki America TSA-B110 Smoke Detector Sen-
sitivityTesteris designedfor efficientand accuratetest-
ing of the sensitivity of smoke detectors. For ease of
use in field applications the tester is easy to transport
andcompact. Two densitometercircuits allowtheTSA-
B110 Smoke Detector Sensitivity Tester to test both
ionizationand photoelectricsmoke detectors.
TheTSA-B110 SmokeDetector SensitivityTester isa
sensitivepiece ofelectronic equipment.The unitmust
beused inatemperaturerangeof50°Fto 86°F.Sudden
jarring or dropping of the TSA-B110 may damage the
unit. Operation will be affected if proper care is not
taken.
•Tests the sensitivity of Hochiki's previous model
photoelectric and ionization smoke detectors.
•Lightweight and portable for easy use in the field.
•Obscuration/sensitivity testing similar to that of a
UL 268 Smoke Box.
•Voltage Adjustment Knob easily changes tester
voltageto therated voltageofthe detector.
•Indicator lamp automatically lights at completion
oftesting.
RatedVoltage 120 V AC, 50/60 Hz
Source Voltage 108V - 132V AC
SmokeGenerating
Material SM-101-P Punk Stick
OperatingTemperature
Range 50°Fto 86°F
Dimensions 15.74" x 11.02" x 7.87"
Weight 13 Lbs.
firealarmresources.com
Fike Part Number 69-016
Specifications subject to change without notice.
HochikiAmericaCorporation•TSA-B110
OPERATION, continued
Testing a Detector
10. Place a detector to be tested into the base in the sensitivity tester’s smoke chamber and close the lid.
11. Insert an ignited punk stick into the smoke-producing chamber on the lower right side. When the detector
alarms, an indicator lamp lights, the meter locks, and a buzzer sounds.
12. Observe the value indicated by the meter (a holding circuit locks the meter in place for about one minute).
13. Remove the punk stick and open the top cover.
14. Remove the detector. Smoke will be exhausted and the densitometer meter will reset to “0”. The lamp and
buzzer function will clear at this time.
MAINTENANCE
Maintaining the TSA-B110 will assure many years of reliable use. It is recommended the maintenance be
performedby qualifiedpersonnel everytwo years.Consult withyour Hochikidistributor fora technicianin yourarea.
NOTE:Hochiki AmericaCorporation recommendsreturning theTSA-B110to thefactory everytwo yearsfor
calibrationto ensureoptimumperformance.
AC SOURCE SWITCH
VOLTAGEADJUSTMENT
KNOB
DENSITOMETER “0”
ADJUSTMENTKNOBS
PHOTO/ION
CHANGE-OVERSWITCH
SMOKE-PRODUCING
CHAMBER
Repeat Steps 7 through 14 to test additional detectors.
firealarmresources.com

Popular Test Equipment manuals by other brands

UEi DMEG3/IRT3 instruction manual

UEi

UEi DMEG3/IRT3 instruction manual

ABB SACE PR111 manual

ABB

ABB SACE PR111 manual

Mitutoyo SURFTEST SJ-410 user manual

Mitutoyo

Mitutoyo SURFTEST SJ-410 user manual

Spirent XD5 Setup guide

Spirent

Spirent XD5 Setup guide

Velleman VTTEST8 user manual

Velleman

Velleman VTTEST8 user manual

Amptec Research 640N Operation & maintenance manual

Amptec Research

Amptec Research 640N Operation & maintenance manual

Carnage Tools CT210 user manual

Carnage Tools

Carnage Tools CT210 user manual

Tezter TIP-HOL-MT-8 user manual

Tezter

Tezter TIP-HOL-MT-8 user manual

Megger PFL40A instruction manual

Megger

Megger PFL40A instruction manual

Tektronix MSO5000 Series user manual

Tektronix

Tektronix MSO5000 Series user manual

Megger BITE 2 instruction manual

Megger

Megger BITE 2 instruction manual

Michell Instruments S904 user manual

Michell Instruments

Michell Instruments S904 user manual

Pite LB 3980 user manual

Pite

Pite LB 3980 user manual

Henry Schein Helix Test Kit Instructions for use

Henry Schein

Henry Schein Helix Test Kit Instructions for use

palintest DigiPAsS Operation manual

palintest

palintest DigiPAsS Operation manual

Hioki IM9201 instruction manual

Hioki

Hioki IM9201 instruction manual

ATD Tools 5489 user manual

ATD Tools

ATD Tools 5489 user manual

Launch X-431 Throttle III quick start guide

Launch

Launch X-431 Throttle III quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.