Configure the System
Specific settings for the thermostat
and heating system can be
configured in the advanced menu.
Press and hold and then
buttons together until the display
changes (approx. 3 seconds).
Parameters
N
o
Description Settings (default in bold)
1 LA
Language
1 = EN
, 2 = NL, 3 = DE, 4 = FR, 5 = ES
4
LL
Lower Temperature Limit
5
- 21 (°C)
5
UL
UpperTemperature Limit 21 -
35
(°C)
6
SO
Schedule options 1 = 7 day (different schedule each day of the week)
2 = 5 + 2 day (weekday + weekend schedule)
3 = 1 day (same schedule every day)
A) Press
and buttons tonavigate
through the parameter list
C) Press buttontosave the change
(orpress to cancel the change)
B) Press
and buttons to
change a parameter
D) Press
button to exitadvanced
menu and save any changes
7
NP
Number of periods per day
4
or 6
8
SS
Wired Remote Sensor
0 = No Remote Sensor
, 1 = Wired Remote Sensor
9
LC
Fail Safe mode
0 = Boiler off
, 1 = Boiler 20% on / 80% off
10
BL
Backlight 0 = Off,
1 = On (only on demand)
11
CL
Clock Format
0 = 24 hr
, 1 = AM/PM
12
DS
Daylight Saving time change 0 = Off,
1 = Auto
13
TO Temperature Display Offset +/-1.5°C
15
SD
Restore Schedule Defaults
0
, 1 = reset
16
FS
Restore Factory Settings
0
, 1 = reset
OpenTherm Data ID's
N
o
Description Settings (default in bold)
Troubleshooting
What’s happening? What itcould mean... How to fixit...
OT1 Low load control 0 = Off, 1 = On
OT2
Control setpoint 5 - 99°C
Thermostat
display is blank
No power to
heating system
Check heating system is powered
OT3
Supply water temperature 5 - 99°C
Faulty wiring connection Check wiring at thermostat
and boiler terminals
OT4
Returnwater temperature 5 - 99°C
OT5
Max. supply water temperature 5 - 99°C
Display =
Faulty temperature
sensor
Replace thermostat or check wiring to
remote temperature sensor if fitted
OT6
Hotwater temperature 5 - 99°C
Thermostat shows
heat demand
Boiler (water) already
at temperature
Normal behaviour - wait for
water temperature to drop
OT7
Hot water setpoint 5 - 99°C
OT8
Actual power 0 - 99%
OT9
Water pressure 0.0 - 9.9
OT10 OTC control 0 = Off, 1 = On
OT11
OTC curve 4 - 40 (
16
)
OT12
Room compensation
0 = Off
, 1 = On
but boiler doesn't
respond
Faulty wiring connection Check wiring at thermostat
and boiler terminals
Conforms to protection requirements of the following directives:
EMC: 2014/30/EU and LVD: 2014/35/EU
ErP: Class VI (+4%), (EU) 811/2013
WEEE Directive 2012/19/EC - Waste Electrical and Electronic Equipment directive
At the end of the product life dispose of the packaging and product in a corresponding recycling
centre. Do not dispose of the unit with the usual domestic refuse. Do not burn the product.