EnglishDeutsch
 logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Accessories
  8. •
  9. Honeywell CTS-V Series User manual

Honeywell CTS-V Series User manual

This manual suits for next models

5

Other Honeywell Accessories manuals

Honeywell NAHA003WK01 User manual

Honeywell

Honeywell NAHA003WK01 User manual

Honeywell Howard Leight VeriPRO User manual

Honeywell

Honeywell Howard Leight VeriPRO User manual

Honeywell C7110C1001A User manual

Honeywell

Honeywell C7110C1001A User manual

Honeywell DC915 series User manual

Honeywell

Honeywell DC915 series User manual

Honeywell NOTIFIER FSV-951 User manual

Honeywell

Honeywell NOTIFIER FSV-951 User manual

Honeywell 40003916 Powerhead User manual

Honeywell

Honeywell 40003916 Powerhead User manual

Honeywell RPW201A User guide

Honeywell

Honeywell RPW201A User guide

Honeywell SS431P User manual

Honeywell

Honeywell SS431P User manual

Honeywell RPWL303A User manual

Honeywell

Honeywell RPWL303A User manual

Honeywell RPW210 User guide

Honeywell

Honeywell RPW210 User guide

Honeywell RPWL301A User manual

Honeywell

Honeywell RPWL301A User manual

Honeywell 5800PIR-RES User manual

Honeywell

Honeywell 5800PIR-RES User manual

Honeywell Silent Knight SK-Photo User manual

Honeywell

Honeywell Silent Knight SK-Photo User manual

Honeywell DirectLine DL422 User manual

Honeywell

Honeywell DirectLine DL422 User manual

Honeywell CTP-20 User manual

Honeywell

Honeywell CTP-20 User manual

Honeywell DC315 series User manual

Honeywell

Honeywell DC315 series User manual

Honeywell RDWL515A2000 Operating instructions

Honeywell

Honeywell RDWL515A2000 Operating instructions

Honeywell IDENTLOC 032236.17 Instruction manual

Honeywell

Honeywell IDENTLOC 032236.17 Instruction manual

Honeywell FIRE-LITE ALARMS AD365-IV User manual

Honeywell

Honeywell FIRE-LITE ALARMS AD365-IV User manual

Honeywell Dual Tec DT-500 User manual

Honeywell

Honeywell Dual Tec DT-500 User manual

Honeywell 5870API Assembly instructions

Honeywell

Honeywell 5870API Assembly instructions

Honeywell NOTIFIER SMART 2 NFX-SMT2 User manual

Honeywell

Honeywell NOTIFIER SMART 2 NFX-SMT2 User manual

Honeywell 2450Cm Series User manual

Honeywell

Honeywell 2450Cm Series User manual

Honeywell RPW310 Manual

Honeywell

Honeywell RPW310 Manual

Popular Accessories manuals by other brands

Hillco 2810 Operator's manual

Hillco

Hillco 2810 Operator's manual

Siemens QSA2700D Basic documentation

Siemens

Siemens QSA2700D Basic documentation

Contours ZY024 manual

Contours

Contours ZY024 manual

Saivod VS621 manual

Saivod

Saivod VS621 manual

SCE ENVIRO-THERM SCE-TE170B24VSS user manual

SCE

SCE ENVIRO-THERM SCE-TE170B24VSS user manual

Z-Wave HSD-200Z user manual

Z-Wave

Z-Wave HSD-200Z user manual

turck FMX-IM-2UPLI63FX quick start guide

turck

turck FMX-IM-2UPLI63FX quick start guide

Decagon Devices 10HS manual

Decagon Devices

Decagon Devices 10HS manual

UPPAbaby Cup Holder user manual

UPPAbaby

UPPAbaby Cup Holder user manual

Elko SmartSensor Leakage Wireless manual

Elko

Elko SmartSensor Leakage Wireless manual

Grizzly H8371 instructions

Grizzly

Grizzly H8371 instructions

Panasonic HG-T Series user manual

Panasonic

Panasonic HG-T Series user manual

IFM Electronic Efector 250 Series Brief instructions

IFM Electronic

IFM Electronic Efector 250 Series Brief instructions

Virtuox VirtuCLEAN 2.0 user manual

Virtuox

Virtuox VirtuCLEAN 2.0 user manual

DigiDesign 888/24 I/O installation guide

DigiDesign

DigiDesign 888/24 I/O installation guide

PROZIS QUAY user manual

PROZIS

PROZIS QUAY user manual

patagonia PSI Vest user manual

patagonia

patagonia PSI Vest user manual

SFC Energy EFOY GO! manual

SFC Energy

SFC Energy EFOY GO! manual

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2026 Manuals.Online. All Rights Reserved.

INSTALLATION INSTRUCTIONS
31-00144-02
20
Solid and Split Core 0-5/10Vdc
Output Current Sensors
CTS-V AND CTP-V SERIES
APPLICATION
The 0-5/10Vdc Output Solid and Split Core Current
Sensors are designed for use in any AC current
monitoring application in which you are looking to
monitor a particular piece of equipment.
SPECIFICATIONS
Monitored Current Type: AC Current
Maximum AC Voltage: 600 VAC
Isolation Voltage: 2200 VAC
Supply Voltage:
Induced from the Monitored Conductor (Insulated
Conductors only)
150-Amp Sensors: 0 to 10 VDC
Operating Temperature Range: 5 to 104ºF (-15 to
40ºC)
Operating Humidity Range: 0 to 95%, non-con-
densing
Storage Temperature: 41 to 95°F (5 to 35°C)
RH Range: 40% to 85% RH, non-condensing
Wire Recommendations: 2 Conductor (Shielded
Cable)
Wire Size:
18 to 24 AWG (0.823 mm2to 0.205 mm) Copper
Wires only
Terminal Block Torque Rating: 4.43 to 5.31 in-lbs.
(0.5 to 0.6 Nm)
Minimum Mounting Distance:
1” (2.6 cm) between current sensor & other magnetic
devices (Relays, Contactors, Transformers)
Agency Approvals:
UL/CUL US Listed (UL 508) Ind. Control Equipment
(File # E309723), CE, RoHS2, WEEE
STANDARD ORDERING
Table 1. Standard Ordering.
WARNING
This product is not intended to be used for
Life or Safety applications.
This product is not intended for use in any
hazardous or classified locations. The CTS-V
and CTP-V Series Current Sensors must be
used on Insulated Conductors Only!
WARNING
Electrical shock hazard.
Disconnect and lock out all power sources
before installation as severe injury or death
may result from electrical shock due to
contact with high voltage wires.
Model # Selectable Ranges Measurement AC Waveform Solid-Core Split-Core
Output
Signal
CTS-V-50 0 to 10/20/50A Average Pure Sinusoidal • 0 to 5 VDC
CTS-V-150 0 to 50/100/150 Average Pure Sinusoidal • 0 to 10 VDC
CTP-V-50 0 to 10/20/50A Average Pure Sinusoidal • 0 to 10 VDC
CTP-V-150 0 to 50/100/150 Average Pure Sinusoidal • 0 to 10 VDC
SOLID AND SPLIT CORE 0-5/10VDC OUTPUT CURRENT SENSORS
31-00144—02 2
INSTALLATION
Make sure that all installations are in compliance with
all national and local electrical codes. Only qualified
individuals that are familiar with codes, standards,
and proper safety procedures for high-voltage
installations should attempt installation. The current
sensor will not require external power, since the power
for the current sensor is induced from the conductor
being monitored.
The current sensor may be mounted in any position
using the two #8 x ¾” Tek screws and the mounting
holes in the base, or snapped directly on to the 35mm
DIN rail (See Fig. 1). Leave a minimum distance of 1”
(3 cm) between the current sensor and any other
magnetic devices such as contactors and
transformers.
Fig. 1. Sensor Placed on Rail.
Latch Operation for CTP-V Series
Press down on the side tab and swing the top of the
unit up to open the split core current sensor as shown
in Figure 2. Press down firmly on the cover to close the
current sensor. An audible “click” will be heard as the
tab slides over the tongue on the base.
CAUTION
Mating surfaces of the magnetic core are
exposed when the sensor is open.
Electrical contact grease, present on the cores
to prevent corrosion, can capture grit and dirt if
care is not exercised. Operation can be
impaired if anything prevents good contact
between pole pieces. Visually check the mating
parts of the core before closing the current
sensor.
Fig. 2. Opening CTP-V Series.
Current Sensor Setup
The amperage range selected represents the
maximum current that can be applied to the
conductor being monitored, Do not exceed! All current
sensors with selectable ranges will have the range
selection jumper factory set on the high range. For
models with field selectable amperage ranges, select
the correct amperage range using the range selection
jumper.
WIRING
We recommend the use of a two conductor 16 to 22
AWG shielded cable, copper wire only, for all Analog
current sensor installations. A maximum wire length
of less than 30 meters (98.4 feet) should be used
between the current sensors and the Building
Management System or controller.
M37377
+
–
M37359
SOLID AND SPLIT CORE 0-5/10VDC OUTPUT CURRENT SENSORS
331-00144—02
NOTE: When using a shielded cable, be sure to con-
nect only (1) end of the shield to ground at the
controller. Connecting both ends of the shield
to ground may cause a ground loop.
When removing the shield from the sensor end, make
sure to properly trim the shield to prevent any chance
of shorting. The current sensor terminals are polarity
sensitive and represent a linear 0 to 5 or 0 to 10 VDC
output signal. Tighten the screws at the terminal block
connections to the recommended torque of 0.5 to 0.6
Nm (4.43 to 5.31 in-lbs.). The aperture (hole) size of
the current sensor is 0.75” (1.90 cm).
Wiring Example
Fig. 3. Analog Circuit.
TROUBLESHOOTING
Current Conversion Formulas
To convert the current sensor output signal to a current reading.
4-20mA output to Current reading (4mA = 0 Amps and 20mA)
Example: 12mA current sensor output signal
Total Span = 250 Amps
Multiplier = 20mA-4mA/Total Span = 0.064
(12mA-4mA)/0.064= 125 Amps
WEEE Directive
At the end of their useful life the packaging and product should be disposed of via a suitable recycling center. Do
not dispose of with household waste. Do not burn.
M37360
SHIELDED CABLE
(–) SIGNAL COMMON
+0-5 0-10 VDC
ANALOG INPUT
GND (SHIELD)
PLC, DDC OR DATA
ACQUISITION SYSTEMS
Problem Solution
No reading •Verify that there is current flowing through the conductor being monitored
with a clamp-on current probe. The power for the current sensor is induced
from the conductor being monitored.
•Check the polarity of the circuit.
•Verify that the terminals are screwed down, wires are firmly in place.
•Disconnect the wires from the current sensor output. Measure the voltage
across the current sensor output with a Voltmeter to verify that the sensor
is working properly.
Erratic readings •Verify that the wires are terminated properly.
•In areas of high RF interference, shielded cable may be necessary to
stabilize signal.
Inaccurate readings •If you suspect that the current sensor is not reading within the accuracy
specifications, please contact the factory for assistance.
Current Sensor is operating at a
low-level current or failing to
operate within the accuracy
specifications.
•Visually check the mating parts of the core to ensure there is no debris
between the split contacts. See Figure 2.
•Remove all debris or dust manually and close the current sensor.
•Continue to retest the sensor in your application.
SOLID AND SPLIT CORE 0-5/10VDC OUTPUT CURRENT SENSORS
Home and Building Technologies
In the U.S.:
Honeywell
715 Peachtree Street NE
Atlanta, GA 30308
customer.honeywell.com
® U.S. Registered Trademark
© 2018 Honeywell International Inc.
31-00144—02 M.S. Rev. 05-18
Printed in United States
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of
your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries,
from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any
modification to the literature by you.
CHINA ROHS COMPLIANCE INFORMATION
ENVIRONMENT-FRIENDLY USE PERIOD (EFUP) TABLE
󴉆󸀮󴏵󱡽󳮹 SJ/T 11364 󵵙󸊿󲷢󶴹󱳷
O: 󸀮󶆺󸛋󴈄󲸓󵙀󸢹󲔩󸛋󸽩󱝾󳧟󴈄󲕓󸢹󴉿󳾒󱙆󵵙󲀯󹄡󲕓󲔩 GB/T 26572 󸊿󲷢󵵙󹢔󹄡󸉔󴭁󱝥󱘕
X: 󸀮󶆺󸛋󴈄󲸓󵙀󸢹󷋼󲻒󲔩󸛋󸽩󱝾󵵙󴍅󱘈󲕓󸢹󴉿󳾒󱙆󵵙󲀯󹄡󸤥󱲡 GB/T 26572 󸊿󲷢󵵙󹢔󹄡󸉔󴭁
This table is prepared in accordance with the provisions of SJ/T 11364.
O: Indicates that said hazardous substance contained in all of the homogeneous materials for this part is below
the limit requirement of GB/T 26572.
X: Indicates that said hazardous substance contained in all of the homogeneous materials for this part is above
the limit requirement of GB/T 26572.
󴉃󱳊󱮧󸀮󱯜󵵙󱯇󱝎󸽩󱝾󽘜󵵜󱘗󲀯󱞄󱠇󸤥󱲡󹢔󹄡󸉔󴭁󵵙󹢔󱳷󱡋󵫞󵙀󸢹
All other components, not listed in the table, do not contain restricted substances above the threshold level.
REGULATORY INFORMATION
FCC REGULATIONS: § 15.19 (A)(3)
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference,
and
2. This device must accept any interference
received, including interference that may cause
undesired operation.
IC REGULATIONS: RSS-GEN
This device complies with Industry Canada’s license-
exempt RSSs.
Operation is subject to the following two conditions:
1. This device may not cause interference; and
2. This device must accept any interference,
including interference that may cause unde-
sired operation of the device.
Le présent appareil est conforme aux CNR d’Industrie
Canada applicables aux appareils radio exempts de
licence. L’exploitation est autorisée aux deux
conditions suivantes :
1. l’appareil ne doit pas produire de brouillage;
2. l’utilisateur de l’appareil doit accepter tout
brouillage radioélectrique subi, même si le
brouillage est susceptible d’en compromettre le
fonctionnement.
FCC WARNING (PART 15.21) (USA ONLY)
Changes or modifications not expressly approved by
the party responsible for compliance could void the
user’s authority to operate the equipment.
󸽩󱝾󱿽󶌇
Component
Name
󴈄󲸓󵙀󸢹 - Hazardous Substances
󹚮(Pb)
Lead (Pb)
󴭰(Hg)
Mercury (Hg)
󹜲(Cd)
Cadmium (Cd)
󱮺󱞀󹛕 (Cr6+)
Chromium VI
Compounds
(Cr6+)
󲡕󴼤󶾌󷔦 (PBB)
Polybrominate
d Biphenyls
(PBB)
󲡕󴼤󱛔󷔦󹂮
(PBDE)
Polybrominated
Diphenyl Ethers
(PBDE)
Assorted
capacitors
OO O O O O
Assorted
resistors
OO O O O O
Core O O O O O O
Screw O O O O O O