Honeywell Fire-Lite Alarms ECC-50DA User manual

D
P/N LS10027-000FL-E:D ECN 15-270
Document LS10027-000FL-E
5/21/2015 Rev:
Distributed Audio Amplifiers
ECC-50DA/E
ECC-125DA/E
ECC-50BDA
Installation Manual
firealarmresources.com

2ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control panel (FACP) with remote notifi-
cation capability—can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of
an automatic fire alarm system (as described above) and a life
safety communication system that may include an autonomous
control unit (ACU), local operating console (LOC), voice commu-
nication, and other various interoperable communication meth-
ods—can broadcast a mass notification message. Such a
system, however, does not assure protection against property
damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premises following
the recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the
recommendations contained in the Guide for Proper Use of
System Smoke Detectors, which is made available at no charge
to all installing dealers. This document can be found at http://
www.systemsensor.com/appguides/. A study by the Federal
Emergency Management Agency (an agency of the United
States government) indicated that smoke detectors may not go
off in as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not
guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a first-floor
or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, chim-
neys, even wet or humid areas may inhibit particle or smoke
flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets, such as air conditioning vents.
• Smoke particles may be drawn into air returns before reach-
ing the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at var-
ious levels of smoke density. If such density levels are not cre-
ated by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing cham-
bers tend to detect smoldering fires better than flaming fires,
which have little visible smoke. Detectors that have ionizing-type
sensing chambers tend to detect fast-flaming fires better than
smoldering fires. Because fires develop in different ways and
are often unpredictable in their growth, neither type of detector is
necessarily best and a given type of detector may not provide
adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warn-
ing of fires caused by arson, children playing with matches
(especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materi-
als, etc.).
Heat detectors do not sense particles of combustion and alarm
only when heat on their sensors increases at a predetermined
rate or reaches a predetermined level. Rate-of-rise heat detec-
tors may be subject to reduced sensitivity over time. For this
reason, the rate-of-rise feature of each detector should be tested
at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same
room as the control panel and in rooms used by the system for
the connection of alarm transmission wiring, communications,
signaling, and/or power. If detectors are not so located, a devel-
oping fire may damage the alarm system, compromising its abil-
ity to report a fire.
Audible warning devices such as bells, horns, strobes,
speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or
are located on another floor of a building. Any warning device
may fail to alert people with a disability or those who have
recently consumed drugs, alcohol, or medication. Please note
that:
• An emergency communication system may take priority over
a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be designed to meet intelligi-
bility requirements as defined by NFPA, local codes, and
Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis-
seminated on any local displays.
• Strobes can, under certain circumstances, cause seizures in
people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear
a fire alarm signal, do not respond to or comprehend the
meaning of the signal. Audible devices, such as horns and
bells, can have different tonal patterns and frequencies. It is
the property owner's responsibility to conduct fire drills and
other training exercises to make people aware of fire alarm
signals and instruct them on the proper reaction to alarm sig-
nals.
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss.
A life safety system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically compat-
ible with the control panel. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a prem-
ises to a central monitoring station may be out of service or tem-
porarily disabled. For added protection against telephone line
failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is
inadequate maintenance. To keep the entire life safety system in
excellent working order, ongoing maintenance is required per the
manufacturer's recommendations, and UL and NFPA stan-
dards. At a minimum, the requirements of NFPA 72 shall be fol-
lowed. Environments with large amounts of dust, dirt, or high air
velocity require more frequent maintenance. A maintenance
agreement should be arranged through the local manufacturer's
representative. Maintenance should be scheduled monthly or as
required by National and/or local fire codes and should be per-
formed by authorized professional life safety system installers
only. Adequate written records of all inspections should be kept.
Limit-D-1-2013
firealarmresources.com

ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ-
ated equipment may be damaged by removing and/or insert-
ing cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro-
gramming operation or change in site-specific software. Re-
acceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All compo-
nents, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (non-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic com-
ponents may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indi-
cating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Ser-
vices Department if any problems are anticipated or encoun-
tered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-
tightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before han-
dling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interfer-
ence, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Cana-
dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi-
oelectriques depassant les limites applicables aux appa-
reils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
LiteSpeed™, Lite-Connect™, and SWIFT™ are trademarks; and Fire-Lite® Alarms is a registered trademark of Honeywell International Inc. Microsoft®
and Windows® are registered trademarks of the Microsoft Corporation. The Chrome™ browser is a trademark of Google Inc.
©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
firealarmresources.com

4ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a
specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our
online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.T[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.
firealarmresources.com

ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015 5
Table of Contents
Section 1: ECC-50DA Remote Amplifier .................................................................................6
1.1: Installation .....................................................................................................................................................6
1.1.1: Board Layout .......................................................................................................................................6
1.1.2: Mounting the Cabinet ..........................................................................................................................7
1.1.3: Wiring Specifications ..........................................................................................................................8
1.1.4: Speaker Wiring ....................................................................................................................................9
Wiring Lengths.......................................................................................................................................9
Class B (Style Y) ....................................................................................................................................9
Class A (Style Z) ..................................................................................................................................10
1.1.5: Audio Riser Wiring ...........................................................................................................................10
1.1.6: Data BUS Wiring...............................................................................................................................11
1.1.7: Connecting AC Power.......................................................................................................................12
1.1.8: Backup Battery ..................................................................................................................................13
1.1.9: Calculating Current Draw and Standby Battery ................................................................................14
Section 2: ECC-125DA Remote Amplifier .............................................................................16
2.1: Installation ...................................................................................................................................................16
2.1.1: Board Layout .....................................................................................................................................16
2.1.2: Mounting the Cabinet ........................................................................................................................17
2.1.3: Wiring Specifications ........................................................................................................................18
2.1.4: Speaker Wiring ..................................................................................................................................19
Wiring Lengths.....................................................................................................................................19
Class B (Style Y) ..................................................................................................................................19
Class A (Style Z) ..................................................................................................................................20
2.1.5: Audio Riser Wiring ...........................................................................................................................21
2.1.6: Data BUS Wiring...............................................................................................................................22
2.1.7: Connecting AC Power......................................................................................................................23
2.1.8: Backup Battery ..................................................................................................................................24
2.1.9: Calculating Current Draw and Standby Battery ................................................................................25
Section 3: ECC-50BDA Backup Remote Amplifier ..............................................................26
3.1: UL 464 Low Frequency Sounders ...............................................................................................................26
3.2: Installation ...................................................................................................................................................26
3.2.1: Board Layout .....................................................................................................................................27
3.2.2: Mounting the Cabinet ........................................................................................................................28
3.2.3: Installing the Optional ECC-50WBU................................................................................................29
3.2.4: Wiring Specifications ........................................................................................................................30
3.2.5: Speaker Wiring ..................................................................................................................................31
Wiring Lengths.....................................................................................................................................31
Class B (Style Y) ..................................................................................................................................31
Class A (Style Z) ..................................................................................................................................32
Audio Riser Wiring ..............................................................................................................................32
3.2.6: Data Bus Wiring ................................................................................................................................33
3.2.7: Setting the ECC-50BDA Amplifier Mode ........................................................................................34
3.2.8: Test Switch Use.................................................................................................................................34
SW1 - AMPLIFIER A..........................................................................................................................34
SW2 - AMPLIFIER B..........................................................................................................................34
3.2.9: Connecting AC Power.......................................................................................................................34
3.2.10: Backup Battery for ECC-50BDA....................................................................................................35
3.2.11: Calculating Current Draw and Standby Battery ..............................................................................36
firealarmresources.com

6ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015
Section 1: ECC-50DA Remote Amplifier
1.1 Installation
This section provides information on how to install the ECC-50DA for use with the ECC-50/100
Emergency Command Center.
SW2 on the ECC-50/100’s display board must be set to the UP position if any ECC-50DAs are
installed in the system. Refer to the ECC-50/100 Instruction Manual, P/N LS10001-000FL-E, for
more information. The ECC-50DA must also be enabled in user programming. 70 volt operation
of the ECC-50DA is also set up in user programming. Refer to the programming section of the
ECC-50/100 Instruction Manual, LS10001-000FL-E.
1.1.1 Board Layout
Figure 1.1 shows the location of terminals, dip switch, and circuit expander connection, used in the
installation of the ECC-50DA.
NOTE: The term ECC-50DA is used in this manual to refer to both the ECC-50DA (120 VAC
version) and the ECC-50DAE (240 VAC version) amplifier unless specified.
ON
12345
6
BATTERY
+–
OUT
–+
IN
–+ –+AB
SBUS
CIRCUIT 4 CIRCUIT 3
CIRCUIT 2
CIRCUIT 1
IN IN IN IN
++++
––––
OUT OUT OUT OUT
++++
––––
AUDIO EXPANDER
Audio Riser
Out In
Data
Bus
SBUS ID
Dip Switch
Audio
Expander
Connection
Battery
Connector
AC Transformer
Connector
Audio Circuits
Figure 1.1 ECC-50DA Board Layout
ecc-50da.wmf
firealarmresources.com

ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015 7
Installation ECC-50DA Remote Amplifier
1.1.2 Mounting the Cabinet
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry,
vibration-free area where extreme temperatures are not encountered. The area should be readily
accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabi-
net approximately five feet above the floor with the hinge mounting on the left. Determine the
number of conductors required for the devices to be installed. Sufficient knockouts are provided
for wiring convenience. Select the appropriate knockout(s) and pull the required conductors into
the box. Note that knockouts are also located on the back of the cabinet. All wiring should be in
accordance with the National and/or Local codes for fire alarm systems.
The cabinet can be surface or flush-mounted. For flush-mount installation of the cabinet, the hole
for the enclosure should be 14.5" W x 24.75" H x 3.438" D (36.8cm W x 62.9cm H x 8.73cm D).
Do not flush-mount in a wall designated as a fire break. The outside dimensions of the cabinet are
16" W x 26.25" H x 4.125" D (40.64cm W x 66.68cm H x 10.48cm D).
Follow these steps to properly mount the cabinet.
1. Mark and predrill holes for the top two backbox keyhole mounting bolts using the dimensions
shown.
2. Install two upper fasteners in the wall with the screw heads protruding.
3. Using the upper 'keyholes', mount the backbox over the two screws.
4. Mark and drill the lower two holes.
5. Install the remaining fasteners and tighten all fasteners to complete backbox mounting.
keyholes
11” (27.94cm)
bottom mounting
holes
Figure 1.2 Cabinet Flush-Mount Dimensions and Mounting Hole Locations
14.5” (36.83cm)
24.75” (62.87cm)
50dacab.wmf
firealarmresources.com

8ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015
ECC-50DA Remote Amplifier Installation
1.1.3 Wiring Specifications
To avoid induced noise (transfer of electrical energy from one wire to another), keep input wiring
isolated from high-current output and power wiring. Avoid pulling one multiconductor cable for
the entire panel. Power-limited, nonpower-limited, and audio circuit wiring must remain separated
in the cabinet. Maintain at least 0.25” (6.35 mm) spacing. Power-limited, nonpower-limited, and
audio circuit wiring must enter and exit the cabinet through different knockouts and/or conduits.
For the same reasons, wiring within the cabinet should be routed around the perimeter of the cabi-
net. It should not cross the printed circuit board where it could induce noise into the sensitive
microelectronics or pick up unwanted RF noise from the high speed circuits.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can
also be reduced by running the wire through ferrite beads or by wrapping it around a ferrite toroid
core. Figure 1.3 provides an example.
To AC
ON
12345
BATTERY
+–
OUT
–+
IN
–+– +AB
SBUS
CIRCUIT 4 CIRCUIT 3 CIRCUIT 2 CIRCUIT 1
IN IN IN IN
++++
––––
OUT OUT OUT OU T
++++
––––
AUDIO EXPANDER
CIRCUIT 5 CIRCUIT 6
CIRCUIT 8 CIRCUIT 7
+ OUT – + OUT –
+ OUT – + OUT –
+ IN – + IN –
+ IN – + IN –
AUDIO EXPANDER
Figure 1.3 Wire Routing Example for ECC-50DA
Audio Riser/Data Bus
Power-limited Circuits
(Class 2)
Speaker Circuits
Power-limited Circuits
(Class 2)
Speaker Circuits
Power-limited
Circuits
(Class 2)
AC Power
Nonpower-
limited Circuit
50daulpwr.wmf
wire clamp
wire clamp
battery
wire
audio circuit
1 inch
Use a 1” spacer and wire
clamps to ensure 0.25”
spacing between power-
limited and nonpower-
limited wiring.
ECC-50DA
ECC-CE4
Refer to the ECC-CE4 Installation
Instructions, LS10002-000FL-E, for
more information on mounting and
wiring the CE4 Circuit Expander.
The CE4 provides 4 additional
speaker circuits.
firealarmresources.com

ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015 9
Installation ECC-50DA Remote Amplifier
1.1.4 Speaker Wiring
Each ECC-50DA supplies four NAC (Notification Appliance Circuit) for speaker connection. The
speaker circuit can be supervised and wired Class B (Style Y) or Class A (Style Z). The speaker cir-
cuit is capable of 50 watts of power at 25 Vrms or 70.7 Vrms.
Wiring Lengths
Class B (Style Y)
Figure 1.4 illustrates how to wire speakers to the ECC-50/100 using Class B (Style Y) supervision.
Number Of Speakers Total Load Wire Distance in Feet
@1/2 W @1 W Vrms Watts 18 AWG 16 AWG 14 AWG 12 AWG
10 5 25Vrms 5W 3900 6200 9860 15680
70Vrms 25000 39700 63200 100520
20 10 25Vrms 10W 2125 3380 5375 8540
70Vrms 15200 24150 38400 61100
30 15 25Vrms 15W 1460 2320 3690 5870
70Vrms 11000 17500 27800 44200
40 20 25Vrms 20W 1100 1750 2780 4420
70Vrms 8500 13510 21500 34175
52 26 25Vrms 26W 760 1200 1920 3050
70Vrms 6100 9700 15400 24520
80 40 25Vrms 40W 550 875 1390 2200
70Vrms 4100 6500 10360 16480
100 50 25Vrms 50W 450 715 1130 1800
70Vrms 3500 5560 8850 14070
Table 1.1 Wire Lengths
NOTE: The above table assumes a uniform distribution of the speakers, and that a max of 20%
voltage drop on the last speaker is allowed.
BATTERY
+–
CIRCUIT 4 CIRCUIT 3 CIRCUIT 2
CIRCUIT 1
IN IN IN IN++++– –––OUT OUT OUT OUT++++– –––
AUDIO EXPANDER
Figure 1.4 Class B (Style Y) Speaker Configuration
Supervised,
Power-limited
UL-Listed
15KΩELR
50da_b.wmf
firealarmresources.com

10 ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015
ECC-50DA Remote Amplifier Installation
Class A (Style Z)
Figure 1.5 illustrates how to wire speakers to the ECC-50/100 using Class A (Style Z) wiring.
1.1.5 Audio Riser Wiring
The Audio Riser is an analog voice bus that carries the recorded voice messages from the display
board to the ECC-50DAs, or the voice messages generated from a system microphone to the ECC-
50DAs. The maximum resistance on the Audio Riser is 20Ω.
Connect the Audio Riser from TB22 on the ECC-50/100 main control board to the ECC-50DAs as
shown in Figure 1.6.
B
A
T
T
E
R
Y
+
–
IN
OUT
–
AUDIO EXPANDER
Figure 1.5 Class A (Style Z) Speaker Configuration
Supervised,
Power-limited
50da_a.wmf
OUT
–+
IN
–+ –+AB
SBUS
OUT
–+
IN
–+ –+AB
SBUS
ECC-50/100
main control board Supervised,
Power-limited
ECC-50DAECC-50DA
To next ECC-50DA
UL-Listed 15KΩELR
installed at last panel
on the audio riser.
Figure 1.6 ECC-50DA Audio Riser Wiring
50daaudiowire.wmf
firealarmresources.com

ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015 11
Installation ECC-50DA Remote Amplifier
1.1.6 Data BUS Wiring
This section contains information on how to connect ECC-50DAs (up to 8) onto the main control
Data BUS. Refer to the ECC-50/100 and/or FACP Manual for Data BUS specifications. Wire the
Data BUS from TB12 on the main control board to the ECC-50DA shown in Figure 1.7 or
Figure 1.8.
ON
12345
OUT
–+
IN
–+ –+AB
SBUS
5
ECC-50/100
main control board
Supervised,
Power-limited
Figure 1.7 Data BUS Connections of the ECC-50DA
50dadatawire.wmf
ON
12345
OUT
–+
IN
–+ –+AB
SBUS
O
N
1
2
3
4
5
OUT
–+
IN
–+ –+AB
SBUS
Supervised,
Power-limited
To next
ECC-50DA
(max. 8)
Figure 1.8 Connecting Multiple ECC-50DAs to the Data BUS
ECC-50/100
main control board
50damultidata.wmf
firealarmresources.com

12 ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015
ECC-50DA Remote Amplifier Installation
1.1.7 Connecting AC Power
To install the AC transformer into the ECC-50DA cabinet, follow these steps:
1. Open the cabinet door.
2. To access cabinet interior, open the dress panel by removing the upper screw and the mid-door
retaining screw.
3. Mount the transformer onto the threaded cabinet transformer mounting studs using the
supplied locking hex nuts as shown in Figure 1.9.
Module Voltage
Transformer
P/N
Standby
Current Alarm Current
ECC-50DA 25V 120 VAC, 60 Hz 115061 350 mA 1100 mA
ECC-50DAE 25V 230 VAC, 50 Hz 115031 200 mA 600 mA
ECC-50DA 70V 120 VAC, 60 Hz 115061 350 mA 1200 mA
ECC-50DAE 70V 230 VAC, 50 Hz 115031 200 mA 600 mA
Table 1.2 ECC-50DA AC Current Draw
ON
12345
BATTERY
+
–
OUT
–+
IN
–+–+AB
SBUS
CIRCUIT 4 CIRCUIT 3 CIRCUIT 2
CIRCUIT 1
IN
IN IN
IN+
++
+–
––
–OUT
OUT OUT
OUT+
++
+–
––
–
AUDIO EXPANDER
Figure 1.9 Transformer Mounting
Threaded
mounting studs
50daxfmr.wmf
firealarmresources.com

ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015 13
Installation ECC-50DA Remote Amplifier
4. Connect AC power to the transformer, making sure to properly ground the unit. Then, plug the
transformer output to the AC connector on the control panel. See Figure 1.10 below. .
1.1.8 Backup Battery
The following steps explain how to connect the batteries (refer to Figure 1.11):
1. Connect the black wire of the battery harness to the negative (-) side of battery #2.
2. Connect the jumper wire provided from the positive (+) side of battery #2 to the negative side
(-) of battery #1.
CIRCUIT 4 CIRCU
IN IN
++
––
OUT+–
black
green
white
Figure 1.10 AC Connections
50daAC.wmf
firealarmresources.com

14 ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015
ECC-50DA Remote Amplifier Installation
3. Connect the red wire from the battery harness to the positive (+) side of battery #1.
1.1.9 Calculating Current Draw and Standby Battery
This section helps determine the current draw and standby battery needs for your installation (18
Ampere Hours max. will fit in cabinet). Complete the remaining instructions in Table 1.3.
For batteries larger than 18 AH, use the BB-26 or BB-55F Battery Box. A maximum of 33 Ampere
Hours is allowed per system.
+–
CIRCUIT 4 CIRCUIT 3 CIRCUIT 2 CIRCUIT 1
IN IN IN IN++++– –––OUT OUT OUT OUT++++– –––
AUDIO EXPANDER
BATTERY
Figure 1.11 Battery Connections to the ECC-50DA
Battery 1 Battery 2
Note: Batteries have been
rotated to show the top sides
for illustration purposes only.
50dabatt.wmf
Device No. of
Devices Current Per Device Standby
Current
Alarm
Current
ECC-50DA (25V system) 1
Standby: 85 mA 85 mA
Alarm: 525 mA 525 mA
ECC-50DA (70.7V system) 1
Standby: 100 mA 100 mA
Alarm: 580 mA 580 mA
ECC-CE4 0 or 1
Standby: 20 mA
Alarm (All Channels): 180 mA mA
ACurrent Subtotals: mA mA
Notification Devices Refer to device manual for number of devices and current ratings.
BCurrent Subtotals: mA mA
CTotal current rating of all devices in system (Line B) X .001 A A
DNumber of standby hours (24 or 60 for NFPA 72) H
E Multiply line C (standby current) and D: Total standby AH AH
F Alarm sounding period in hours (For example, 5 minutes = .0833 hours): H
G Multiply line C (alarm current) and F: Total alarm AH AH
H Add lines E and G (AH = Ampere Hours): Total AH required AH
Table 1.3 Current Draw Calculations
firealarmresources.com

ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015 15
Notes
firealarmresources.com

16 ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015
Section 2: ECC-125DA Remote Amplifier
2.1 Installation
This section provides information on how to install the ECC-125DA for use with the ECC-50/100
Emergency Command Center.
SW2 on the ECC-50/100’s display board must be set to the UP position if any ECC-125DAs are
installed in the system. Refer to the ECC-50/100 Instruction Manual for more information. The
ECC-125DA must also be enabled in user programming. Refer to the programming section of the
ECC-50/100 Instruction Manual, LS10001-000FL-E.
2.1.1 Board Layout
Figure 2.1 shows the location of terminals, dipswitches, and expander connection, used in the
installation of the ECC-125DA.
NOTE: The term ECC-125DA is used in this manual to refer to both the ECC-125DA (120 VAC
version) and the ECC-125DAE (240 VAC version) amplifier unless specified.
ON
12345
CIRCUIT 4 CIRCUIT 3 CIRCUIT 2 CIRCUIT 1
IN IN IN IN++++– –––OUT OUT OUT OUT++++– –––
AUDIO EXPANDER
B
A
T
T
E
R
Y
+
–
BGW
AC Connector
VBUS
Out
VBUS
In
SBUS
Audio
Expander
Connection
Figure 2.1 Components Layout of ECC-125DA
SBUS ID
Dip Switch
Battery
Connector
Audio Circuits
ecc-125da.wmf
firealarmresources.com

ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015 17
Installation ECC-125DA Remote Amplifier
2.1.2 Mounting the Cabinet
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry,
vibration-free area where extreme temperatures are not encountered. The area should be readily
accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabi-
net approximately five feet above the floor with the hinge mounting on the left. Determine the
number of conductors required for the devices to be installed. Sufficient knockouts are provided
for wiring convenience. Select the appropriate knockout(s) and pull the required conductors into
the box. Note that knockouts are also located on the back of the cabinet. All wiring should be in
accordance with the National and/or Local codes for fire alarm systems.
The cabinet can be surface or flush-mounted. For flush-mount installation of the cabinet, the hole
for the enclosure should be 14.5" W x 24.75" H x 3.438" D (36.8cm W x 62.9cm H x 8.73cm D).
Do not flush-mount in a wall designated as a fire break. The outside dimensions of the cabinet are
16" W x 26.25" H x 4.125" D (40.64cm W x 66.68cm H x 10.48cm D).
Follow these steps to properly mount the cabinet.
1. Mark and predrill holes for the top two backbox keyhole mounting bolts using the dimensions
shown.
2. Install two upper fasteners in the wall with the screw heads protruding.
3. Using the upper 'keyholes', mount the backbox over the two screws.
4. Mark and drill the lower two holes.
5. Install the remaining fasteners and tighten all fasteners to complete backbox mounting.
keyholes
11” (27.94cm)
bottom mounting
holes
Figure 2.2 Cabinet Flush-Mount Dimensions and Mounting Hole Locations
14.5” (36.83cm)
24.75” (62.87cm)
125dacab.wmf
firealarmresources.com

18 ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015
ECC-125DA Remote Amplifier Installation
2.1.3 Wiring Specifications
To avoid induced noise (transfer of electrical energy from one wire to another), keep input wiring
isolated from high-current output and power wiring. Avoid pulling one multiconductor cable for
the entire panel. Power-limited, nonpower-limited, and audio circuit wiring must remain separated
in the cabinet. Maintain at least 0.25” (6.35 mm) spacing. Power-limited, nonpower-limited, and
audio circuit wiring must enter and exit the cabinet through different knockouts and/or conduits.
For the same reasons, wiring within the cabinet should be routed around the perimeter of the cabi-
net. It should not cross the printed circuit board where it could induce noise into the sensitive
microelectronics or pick up unwanted RF noise from the high speed circuits.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can
also be reduced by running the wire through ferrite beads or by wrapping it around a ferrite toroid
core. Figure 2.3 provides an example.
CIRCUIT5 CIRCUIT6
CIRCUIT 8 CIRCUIT 7
+ OUT – + OUT–
+ OUT – + OUT –
+ IN – + IN –
+ IN – + IN –
AUDIO EXPANDER
Figure 2.3 Wire Routing Example for ECC-125DA
Audio Riser/Data Bus
Power-limited Circuits
(Class 2)
Speaker Circuits
Power-limited
Circuits
(Class 2)
Speaker Circuits
Power-limited
Circuits
(Class 2)
AC Power
Nonpower-
limited Circuit
125daulpwr.wmf
Speaker Circuits
Power-limited
Circuits
(Class 2)
ECC-125DA ECC-CE4 Refer to the ECC-CE4 Installation
Instructions, LS10002-000FL-E, for
more information on mounting and
wiring the CE4 Circuit Expander.
The CE4 provides 4 additional
speaker circuits.
firealarmresources.com

ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015 19
Installation ECC-125DA Remote Amplifier
2.1.4 Speaker Wiring
Each ECC-125DA supplies four NAC (Notification Appliance Circuit) for speaker connection. The
speaker circuit can be supervised and wired Class B (Style Y) or Class A (Style Z). Speaker circuit
1 is capable of 100 watts of power at 25 Vrms. Speaker circuit 2-4 are capable of 50 watts (each) at
25 Vrms.
Wiring Lengths
Class B (Style Y)
Figure 2.4 illustrates how to wire speakers to the control panel using Class B (Style Y) supervision.
Number Of Speakers Total Load Wire Distance in Feet
@1/2 W @1 W Vrms Watts 18 AWG 16 AWG 14 AWG 12 AWG
10 5 25Vrms 5W 3900 6200 9860 15680
20 10 25Vrms 10W 2125 3380 5375 8540
30 15 25Vrms 15W 1460 2320 3690 5870
40 20 25Vrms 20W 1100 1750 2780 4420
52 26 25Vrms 26W 760 1200 1920 3050
80 40 25Vrms 40W 550 875 1390 2200
100 50 25Vrms 50W 450 715 1130 1800
150 75 25Vrms 75W 300 476 753 1200
200 100 25Vrms 100W 225 357 565 900
250 125 25Vrms 125W 180 285 452 720
Table 2.1 Wire Lengths
NOTE: The above table assumes a uniform distribution of the speakers, and that a max of 20%
voltage drop on the last speaker is allowed.
BATTERY
+–
CIRCUIT 4 CIRCUIT 3
CIRCUIT 2
CIRCUIT 1
IN IN IN IN
++++
––––
OUT OUT OUT OUT
++++
––––
AUDIO EXPANDER
UL-Listed
15K ΩELR
Figure 2.4 Class B (Style Y) Speaker Configuration
Supervised,
Power-limited
125da_b.wmf
firealarmresources.com

20 ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015
ECC-125DA Remote Amplifier Installation
Class A (Style Z)
Figure 2.5 illustrates how to wire speakers to the control panel using Class A (Style Z) wiring.
BATTERY
CIRCUIT 4
CIRCUIT 3
CIRCUIT 2
IN IN IN
+++
–––
OUT OUT OUT
+++
–––
AUDIO EXPANDER
+
–
CIRCUIT 1
IN+– OUT+–
Supervised,
Power-limited
Figure 2.5 Class A (Style Z) Speaker Configuration
125da_a.wmf
firealarmresources.com
This manual suits for next models
4
Table of contents
Other Honeywell Amplifier manuals

Honeywell
Honeywell NOTIFIER AA Series User manual

Honeywell
Honeywell X-DA1500EN User manual

Honeywell
Honeywell BENDIX/KING KMA28 User manual

Honeywell
Honeywell Gamewell-FCI AA-100 User manual

Honeywell
Honeywell R7824 Operation manual

Honeywell
Honeywell AA919 User manual

Honeywell
Honeywell X-618 Quick start guide

Honeywell
Honeywell GENT COMPACT-DAU User manual

Honeywell
Honeywell X-DA4125 User manual

Honeywell
Honeywell X-618 User manual