1I56-3506-005
5/23/2022
Listed to: UL 864 and UL 2610
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the appropriate Notifier control panel installation manual for detailed system
information. If the modules will be installed in an existing operational system,
inform the operator and local authority that the system will be temporarily
out of service. Disconnect power to the control panel before installing the
modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The FMM-1 Monitor Module is intended for use in intelligent, two-wire sys-
tems, where the individual address of each module is selected using the built-
in rotary switches. It provides either a 2-wire or 4-wire fault tolerant initiating
device circuit (IDC) for normally open contact fire alarm and supervisory de-
vices, or either normally open or normally closed security devices. The mod-
ule has a panel controlled LED indicator. The FMM-1 can be used to replace
an MMX-1 module in existing systems. FMM-1 is also UL Listed as a com-
mercial proprietary burglar alarm accessory and a commercial central station
burglar alarm accessory.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
NOTIFIER system control panel (list available from NOTIFIER).
FIGURE 1. CONTROLS AND INDICATORS
C1067-00
I56-3506-005
INSTALLATION AND MAINTENANCE INSTRUCTIONS
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 5.0 mA (LED on)
Average Operating Current: 375 µA (group poll); 350 µA (direct poll); 600 µA Max. (Communicating, IDC Shorted)
EOL Resistance: 47K Ohms
Maximum IDC Wiring Resistance: 1,500 Ohms
Maximum IDC Voltage: 11 Volts
Maximum IDC Current: 450µA
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% Non-condensing
Dimensions: 41⁄2˝ H x 4˝ W x 1
1⁄4˝ D (Mounts to a 4˝ square by 21⁄8˝ deep box.)
Accessories: SMB500 Series Electrical Box
MOUNTING
The FMM-1 mounts directly to 4-inch square electrical boxes. (See Figure
2). The box must have a minimum depth of 21
/8inches (54 mm). Surface
mounted electrical boxes (SMB500-WH) are available from NOTIFIER.
FIGURE 2. MODULE MOUNTING
NOTE: For UL Listed security installations, the FMM-1 must be mounted
within the control panel enclosure.
ISOLATED
QUADRANT
C1066-00
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer). See Figure 2.
NOTE: All references to power limited represent “Power Limited (Class 2)”.
NOTE: Dispose electronic waste following national and/or local regulations.