sory supply and ground. Otherwise, each monitor oper-
ates independently from the others. Each module has its
own unique address.
A pair of rotary code switches is used to set the address
of the first module from 01 to 90. The remaining modules
are automatically assigned to the next nine higher ad-
dresses. Provisions are included for disabling a maximum
of two unused modules to release the addresses to be
used elsewhere. Each module also has panel controlled
green LED indicators. The panel can cause the LEDs to
blink, latch on, or latch off.
Shipped on Board:
(1) Shunt in Class A/B position
(Shipped in Class B position, remove shunt for Class A)
Included:
(6) 1 x 4 Terminal Blocks (2) 11/4˝ (32mm) Stand offs
(4) Machine Screws (3) Shunts (10) 47k Ohm
End of Line Resistors
(2) Nuts
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be con-
nected to a compatible Silent Knight system control panel.
COMPONENTS
The following is a description of the IDP-Monitor-10
mounting framework:
• One or two IDP-Monitor-10 modules can be
installed in a IDP-ACB cabinet.
The IDP-ACB cabinet has a built-in chassis that will ac-
commodate one or two IDP-Monitor-10 modules.
0
1
2
3
456789
0
78
6
5
4
3
21
910
11
12
13
14
15
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
0
1
2
3
456789
0
78
6
5
4
3
21
9
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
Figure 1: IDP-ACB Cabinet
The front IDP-Monitor-10 module positions of each chassis
are offset below the rear IDP-Monitor-10 module positions
so that all of the status indicators are visible. For cabinet
dimensions refer to the IDP-ACB instruction manual.
K200-14-00 1 I56-2731-003
INSTALLATION AND
MAINTENANCE INSTRUCTIONS
IDP-Monitor-10
Ten Input Monitor Module
SPECIFICATIONS
Normal Operating Voltage: 15-32 VDC
Stand-By Current: 3.5 mA
Alarm Current: 55 mA (assumes all ten
LEDs solid on)
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10 to 93% Non-condensing
Dimensions: 6.8˝ H x 5.8˝ W x 1.25˝ D
Accessories: IDP-ACB Cabinet and Chassis
Wire Gauge: 12-18 AWG
Maximum SLC
Wiring Resistance: 40 Ohms
Maximum IDC
Wiring Resistance: 1500 Ohms
Maximum IDC Voltage: 10.2 VDC
Maximum IDC Current: 240 µA (each circuit)
C0202-00
BEFORE INSTALLING
If the modules will be installed in an existing operational
system, inform the operator and local authority that the
system will be temporarily out of service. Disconnect the
power to the control panel before installing the modules.
This system contains static sensitive components. Always
ground yourself with a proper wrist strap before handling
any circuits so that static charges are removed from the
body. The housing cabinet should be metallic and suit-
ably grounded.
NOTICE: This manual should be left with the owner/
user of this equipment.
GENERAL DESCRIPTION
The IDP-Monitor-10 Ten Input Monitor Module is in-
tended for use in an intelligent alarm system. Each moni-
tor module is intended to interface between a control
panel and normally open contact devices, such as pull
stations. A common SLC input is used for all modules,
and the initiating device loops share a common supervi-
C0234-03
firealarmresources.com
1
Figure 4a: Installation of IDP-Monitor-10 module in a
rear chassis position, method two
Step 1: Insert the bottom edge of the IDP-Monitor-10
module down into a rear slot of the chassis.
Step 2: Carefully swing the upper edge of the board
towards the back of the chassis until it touches
the short standoff attached to the chassis.
Step 3: Align the long standoff with the short stand off
and tighten.
2
3
1
Figure 4b: Installation of IDP-Monitor-10 module in
front chassis position
Step 1: Insert the bottom edge of the IDP-Monitor-10
module down into a front slot of the chassis.
Step 2: Carefully swing the upper edge of the board
towards the back of the chassis until it touches
the 11⁄4˝ (31.75mm) standoffs installed on the
rear module.
Step 3: Align two 4-40 screws with the two standoffs
and tighten.
Step 4: Address and wire the modules according to the
instructions in this manual.
INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the
four holes provided in the back surface of the cabinet
(Figure 2).
Figure 2: Typical mounting hole locations
2. Module Installation
There are two methods for installing a module in the
rear position of a chassis. Method one is for installa-
tion of a rear module only, when no module will be in-
stalled in front of it. Refer to Figure 3 for instructions.
Method two is for installation of a rear module when
another module will be installed in the chassis position
in front of it. Refer to Figures 4a and 4b for method
two. All necessary screws and standoffs are supplied
with the modules.
23
1
Figure 3: Installation of rear module only, method one
Step 1: Insert the bottom of the IDP-Monitor-10 module
down into a rear slot on the chassis.
Step 2: Carefully swing the upper edge of the board
back towards the back of the chassis until it
touches the two standoffs.
Step 3: Align two 4-40 screws with the two standoffs
and tighten.
Step 4: Address and wire the modules according to the
instructions in this manual.
The steps in Figures 4a and 4b describe and illustrate mod-
ule installation when the rear chassis position and the posi-
tion in front of it will be filled. Front position installation
is possible only if the rear position is filled with a module.
K200-14-00 2 I56-2731-003
C0237-00
C0235-00
C0225-00
Backbox
Mounting
Holes
C0226-00
firealarmresources.com
WIRING
NOTE: All wiring must conform to applicable local
codes, ordinances, and regulations.
1. Install module wiring in accordance with the job draw-
ings and appropriate wiring diagrams.
2. All wiring to the IDP-Monitor-10 is done via terminal
blocks. In order to properly make electrical connec-
tions strip approximately 1⁄4˝ of insulation from the
end of wire, sliding the bare end of the wire under the
clamping plate screw.
3. Set the address on the modules per the job drawing. Use
the rotary code switches to set the address of the first
module (between 01 and 90).
In Class B operation, the remaining modules are automati
cally assigned to the next nine higher addresses. For
example, if the base address switch is set to 28, the next
nine modules will be addressed to 29, 30, 31, 32, 33, 34,
35, 36, and 37.
The module is shipped in Class B position, remove
shunt for Class A. When operating in Class A, alternate
modules are paired together (+0/+1, +2/+3, +4/+5, +6/+7,
+8/+9), resulting in a total of five modules. For example,
if the base address switch is set to 28, then 30, 32, 34
and 36 will be automatically assigned to the modules
while 29, 31, 33, 35 and 37 are available to be used for
other modules on the SLC. For Class A and B operation,
DO NOT set the lowest address above 90, as the other
modules will be assigned to nonexistent addresses.
NOTE: The IDP-Monitor-10 must have power cycled for
shunt changes to take effect.
K200-14-00 3 I56-2731-003
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful in-
terference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment
generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
4. A shunt is provided to disable a maximum of two un-
used modules in Class B operation and one unused
module in Class A operation. Modules are disabled
from the highest address and work downward. If two
modules are disabled, the lowest eight addresses will
be functional, while the highest two will be disabled.
For example, in Class B operation, if the shunt for
Address Disable is placed on “two” and the base switch
is set to 28, the modules will be assigned to 28, 29, 30,
31, 32, 33, 34 and 35 while disabling the highest two
positions.
5. A communications loss feature is available on some
panels. Upon a communication loss, due to a micro-
processor failure at the control unit, the IDP-Monitor-
10 will send a signal to the control unit to activate the
notification device circuits upon initiating of an alarm
on the IDP-Monitor-10. A single shunt is used to en-
able (shunt on) or disable (shunt off) this feature for all
modules on the board.
NOTE: Place unused shunts on single pin to store on
board for future use.
WIRING NOTES
• Power-limited circuits must employ type FPL, FPLR,
or FPLP cable as required by Article 760 of the NEC.
PROGRAMMING
The modules are programmed as devices in each system
according to the programming instructions in the appro-
priate FACP manual.
firealarmresources.com
K200-14-00 4 I56-2731-003
0
1
2
3
4
5 6 7 8 9
BASE ADDRESS
TO NEXT
DEVICE
–
STATUS
INDICATORS
—
+
—
+
—
+
—
+
—
+
—
+
IDC
ADDRESS
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
47K
EOL
RESISTOR
ELR-47K
CONNECT MODULES TO
LISTED COMPATIBLE
SILENT KNIGHT CONTROL
PANELS ONLY
SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
CLASS B IDC (TYPICAL)
—
+
—
+
A/B SLCT
COM LOSS
DISABLE 1
DISABLE 2
0
1
2
3
4
5 6 7 8 9
POWER LIMITED
AND SUPERVISED
NOTE: Any number of UL listed contact closure devices
may be used. DO NOT mix fire alarm initiating and
supervisory devices on the same initiating device circuit.
Install contact closure devices per manufacturer’s
installation instructions.
NOTE: Any number of UL listed contact closure devices
may be used. DO NOT mix fire alarm initiating and
supervisory devices on the same initiating device circuit.
Install contact closure devices per manufacturer’s
installation instructions.
BASE ADDRESS
TO NEXT
DEVICE
–
STATUS
INDICATORS
—
+
—
+
—
+
—
+
—
+
—
+
IDC
ADDRESS
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO
LISTED COMPATIBLE
SILENT KNIGHT CONTROL
PANELS ONLY
SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
CLASS A IDC (TYPICAL)
—
+
—
+
A/B SLCT
COM LOSS
DISABLE 1
DISABLE 2
IDC 2
IDC 3
IDC 4
IDC 5
0
1
2
3
4
5 6 7 8 9
0
1
2
3
4
5 6 7 8 9
POWER LIMITED
AND SUPERVISED
REMOVE SHUNT FOR CLASS A.
Figure 5: Typical Initiating Device Circuit
Configuration – Class B, Style B.
Figure 6: Typical Fault Tolerant Initiating Device
Circuit Configuration – Class A, Style D
C0811-01
C0810-01
7550 Meridian Circle
Maple Grove, MN 55369-4927
763-493-6455; 800-328-0103
Fax: 763-493-6475
http://www.silentknight.com
© 2006 Silent Knight 2/06
firealarmresources.com

Other Honeywell Monitor manuals

Honeywell PTI-610 User manual

Honeywell

Honeywell PTI-610 User manual

Honeywell Bendix/King KMD 550 Installation and operating instructions

Honeywell

Honeywell Bendix/King KMD 550 Installation and operating instructions

Honeywell S7999D1048 User manual

Honeywell

Honeywell S7999D1048 User manual

Honeywell Multi-Mon User manual

Honeywell

Honeywell Multi-Mon User manual

Honeywell BW RigRat User manual

Honeywell

Honeywell BW RigRat User manual

Honeywell HMLCD17E2 User manual

Honeywell

Honeywell HMLCD17E2 User manual

Honeywell Notifier LCD2-80 User manual

Honeywell

Honeywell Notifier LCD2-80 User manual

Honeywell Fire-lite Alarms ANN-80-W Technical manual

Honeywell

Honeywell Fire-lite Alarms ANN-80-W Technical manual

Honeywell HMLCD17L User manual

Honeywell

Honeywell HMLCD17L User manual

Honeywell HMLCD17L User manual

Honeywell

Honeywell HMLCD17L User manual

Honeywell Bendix/King KMD 550 Installation and operating instructions

Honeywell

Honeywell Bendix/King KMD 550 Installation and operating instructions

Honeywell IAQPoint User manual

Honeywell

Honeywell IAQPoint User manual

Honeywell NOTIFIER FMM-1 User manual

Honeywell

Honeywell NOTIFIER FMM-1 User manual

Honeywell 7800 SERIES Operation manual

Honeywell

Honeywell 7800 SERIES Operation manual

Honeywell RDD100 User manual

Honeywell

Honeywell RDD100 User manual

Honeywell S7999D SOLA User manual

Honeywell

Honeywell S7999D SOLA User manual

Honeywell E3Point User manual

Honeywell

Honeywell E3Point User manual

Honeywell SV2 Series User manual

Honeywell

Honeywell SV2 Series User manual

Honeywell HMC14 User manual

Honeywell

Honeywell HMC14 User manual

Honeywell RDD100 User manual

Honeywell

Honeywell RDD100 User manual

Honeywell GAMEWELL LCD-SLP Technical manual

Honeywell

Honeywell GAMEWELL LCD-SLP Technical manual

Honeywell C7355A User manual

Honeywell

Honeywell C7355A User manual

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell SC500 User manual

Honeywell

Honeywell SC500 User manual

Popular Monitor manuals by other brands

CASP ELEKTRONIK MAL 15776G user manual

CASP ELEKTRONIK

CASP ELEKTRONIK MAL 15776G user manual

LG 24GM79G-B owner's manual

LG

LG 24GM79G-B owner's manual

Lumel DL11 user manual

Lumel

Lumel DL11 user manual

IriSys SafeCount IWC6254 installation guide

IriSys

IriSys SafeCount IWC6254 installation guide

Compaq V40 user guide

Compaq

Compaq V40 user guide

wtw pH 171 R operating manual

wtw

wtw pH 171 R operating manual

Acnodes KDW 5170 Specifications

Acnodes

Acnodes KDW 5170 Specifications

Lorex LW2310 Series instruction manual

Lorex

Lorex LW2310 Series instruction manual

Pro-face SP5000 Series Hardware manual

Pro-face

Pro-face SP5000 Series Hardware manual

Data Video TLM-434H instruction manual

Data Video

Data Video TLM-434H instruction manual

Superb 900020000140 quick start guide

Superb

Superb 900020000140 quick start guide

Barco AMM215WTTP user guide

Barco

Barco AMM215WTTP user guide

Philips 300WN5QS/97 Service manual

Philips

Philips 300WN5QS/97 Service manual

HIK VISION DS-D4237FI-CAF quick start guide

HIK VISION

HIK VISION DS-D4237FI-CAF quick start guide

Totevision LCD-1540HD owner's manual

Totevision

Totevision LCD-1540HD owner's manual

Totevision LCD-642 Specification sheet

Totevision

Totevision LCD-642 Specification sheet

Panasonic TH-50LFE6U Operating insructions

Panasonic

Panasonic TH-50LFE6U Operating insructions

Acer B326HUL quick guide

Acer

Acer B326HUL quick guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.