manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Security Sensor
  8. •
  9. Honeywell 5800COMBO Assembly instructions

Honeywell 5800COMBO Assembly instructions

FEATURES
•Multi-Criteria Sensing: uses four
sensing elements to react faster
while minimizing false alarms:
- Photoelectric smoke sensor
detects airborne smoke particles
- Carbon Monoxide (CO) sensor
detects smoldering fires
- Infrared (IR) sensor measures
ambient light and flame
signatures, such as flame flicker
- Thermal detection monitors for
dangerous rise in temperature
•Low Temperature sensing:
senses ambient temperature
and reports if temperature goes
below 41°F (5°C).
•CO Detector End-of-Life
reporting (detector needs
replacing)
•Smoke detector maintenance
reporting (detector needs
cleaning)
•Low Battery Detection
Table 1: Operation Modes
MODE Status LED
(Top)
LED Windows
(Side)
Sounder Speaker
Power Up Blink Green,
every 2 secs Dark Silent
Voice welcome,
instructions
after first
time power up or
after default
Normal
(Standby)
Single Blink
Green every
10 secs
Dark Silent Silent
Smoke
Alarm
Blink Red
every 10 secs
Blink red Temp-3
Voice smoke
warning
Thermal
Alarm
Blink Red
every 10 secs
Blink red Temp-3
Voice smoke
warning
CO Alarm
Blink Red
every 10 secs
Blink blue Temp-4
Voice CO
warning
Powered
Down
Dark Dark Silent Silent
POWER UP and LANGUAGE SELECTION
•Remove battery pull tabs. Be sure batteries are seated
properly to avoid a low battery condition after 15 seconds.
•Upon power up,
Green LED Blinks every 2 secs / Sounder
is Silent. After power up, the detector prompts for
language selection.
•Select the desired language.
English: Press the Smoke (•) test button
Spanish: Press the CO (••) test button
RESETTING THE LANGUAGE
1. Press and hold both the Smoke and CO test
switches simultaneously for 10 seconds, then
release. The green light flashes rapidly.
2. Press and hold both buttons again for one
second and release. The sensor begins
speaking a Welcome message.
3. Select the desired language by pressing the
corresponding Smoke (English) or CO
(Spanish) test button.
ENROLLMENT
IMPORTANT:
The Smoke and Carbon Monoxide (CO) sensors each have unique serial numbers and must be enrolled in separate zones.
Enroll the Smoke Sensor
1. Remove the detector from the base plate (tamper switch must be faulted
when enrolling).
2. Put the control panel in Zone Programming mode.
3. Assign a zone number for the smoke detector zone.
Loop = 1; Zone Type = 09 (Fire) or 16 (Fire with Verification)
Input Type = 03 (Supervised RF)
When prompted for the serial number, press and release the Smoke Test
button for 1 second. The sensor sends two transmissions for enrollment.
Alternatively, you can manually enter the smoke sensor serial number
found on the unit’s label.
4. If Maintenance monitoring is desired:
VISTA-15P/20P/21iP, LYNX Touch, & Lyric: Assign a separate zone number
using the Smoke Detector serial number.
Loop = 2 (maintenance); Zone Type = choose a zone type based on
desired operation (ex.24 hr Trouble, Monitor, or Auxiliary)
Input Type = 03 (Supervised RF)
VISTA-128/250 Series: Enable “Smart Contact” option in zone
programming menu for the assigned smoke detector zone.
5. If Low Temperature reporting is desired, program a separate zone for this
smoke detector serial number
Loop = 3; Zone Type = choose a zone type based on desired
operation (ex.24 hr Trouble, Monitor, or Auxiliary);
Input Type = 03 (Supervised RF).
WARNING:The fire protection zone must always be enrolled as Loop 1.
Otherwise, fire alarms will not be reported by the control.
Enroll the CO Sensor
1. Remove the detector from the base plate.
2. With the control panel in Zone Programming mode, assign a zone
number for the CO detector zone.
Loop = 1; Zone Type =14 (CO alarm);
Input Type = 3 (Supervised RF)
When prompted for the serial number, press and release the CO Test
button for 1 second. The sensor sends two transmissions for
enrollment. Alternatively, you can manually enter the CO sensor serial
number, which is the smoke serial number plus 1 (ex. if smoke s/n is
0000781, the CO s/n is 0000782).
3. If End-of-Life monitoring is desired:
VISTA-15P/20P/21iP, LYNX Touch, & Lyric: automatically sent
VISTA-128/250 Series: program a separate zone for the CO serial no.
Loop = 2; Zone Type = choose a zone type based on desired
operation (ex.24 hr Trouble or Auxiliary); Input Type = 03 (Supervised RF)
5800COMBO - Combination Smoke/Carbon Monoxide (CO) Detector w/Built-in Wireless Transmitter
(features voice and 360 degree viewable LED ring)
INSTALLATION AND SETUP GUIDE
This device is intended for use with Honeywell control panels that support 5800 series devices. Before installing detectors, please
thoroughly read these installation instructions and read the Limitations of Fire Alarm Systems Insert (P/N 800-15144 5/13) and System
Smoke Detectors Application Guide (P/N SPAG9101 7/12).
MOUNTING
After enrolling and before mounting permanently, conduct Go/No Go test (see controller’s
instructions) to verify adequate signal strength. Adjust the device location as necessary.
1. Using two supplied screws and anchors, mount the base.
2. Attach the smoke detector to the mounting base with a clockwise motion.
3. Test each detector as described in the Testing section.
4. Confirm all desired signals have been received by the Central Station.
NOTE: NFPA 72 recommends the installation of detectors only after completing
construction or any other dust producing activity.
TESTING
Test communications between the detector and the control panel.
The detector mode has two test buttons; one for smoke testing and
one for CO testing.
The detector may also be functionally tested using canned smoke
and canned CO. If the detector fails any of the test methods, the
detector should be replaced.
NOTE: Testing the detector will activate the alarm and send a signal to
the panel. Before testing, notify the proper authorities to avoid any
false alarms.
Smoke Test (Alarm Test)
Press and hold the Smoke Test button for 1 to 2 seconds. The
detector will sound and illuminate per Table 2 and send a smoke
alarm signal to the control panel (all programmed smoke detector
loops are signaled). Verify that the smoke alarm signal was
received at the control panel.
Smoke System Test (Functional Smoke Test)
Press and hold the Smoke Test button for 3 to 5 seconds to enter
the functional smoke test mode. See Functional Smoke Test section.
NOTE: Detector sounds an alarm when using canned smoke only when in
Functional Test mode (canned smoke does not cause alarm
sounding when in normal mode).
Functional Smoke Test
With the detector in smoke system (functional) test mode, spray
canned smoke into the detector. The canned smoke that can be
used and is approved for test include: Home Safeguard Industries
25S, SDi CHEK02 and CHEK06, SDi SOLOA4, and SDi
SMOKESABRE.
1. The detector will sound and illuminate per Table 2 and a smoke
alarm signal will be sent to the panel.
2. Verify the smoke alarm signal was received by the control panel.
CO Test (Alarm Test)
Press and hold the CO Test button for 1 to 2 seconds. The control
panel should display and sound a CO alarm (all programmed CO
detector loops are sent).
CO System Test (Functional CO Test)
Press and hold the CO Test button for 3-5 seconds to enter the
functional gas test mode. See Functional Gas Test section below.
Functional Gas Test
Solo C6 brand canned CO may be used to verify the detector’s
ability to sense CO by utilizing the RealTest® feature as follows:
1. Press and hold the CO test button for 3 to 5 seconds. The green
LED will start blinking once per second indicating the detector is
in RealTest® mode. (If the detector will not go into RealTest®
mode, the CO sensor may be in fault or at end-of-life.)
2. While the green LED is blinking once per second, spray a small
amount of canned CO directly into the CO gas entry port.
3. Upon successful gas entry and if functioning properly, the
detector will go into CO alarm and send an alarm to the control
panel.
4. The CO test will automatically clear when the CO clears from the
sensor or in 30 seconds if no CO was introduced.
Table 2: LED Indication & Sounder during Test and Trouble
MODE
Status LED
(Top)
Side LED
Windows
Sounder Speaker
Smoke Test
Blink Red
once every
second
Dark Temp-3
Warning of alarm
signal transmission.
Voice smoke
warning
Smoke System
(functional) Test
Blink Red
once every 10
secs
Blink once
every
10 secs
CO Test
Blink Red
once every
second
Dark Temp-3
Warning of alarm
signal transmission.
Voice smoke
warning
RealTest™
F
unctional CO gas entry
test – Waiting for gas
entry
Blink Green
once per
second
Dark Silent
Voice instructions for
testing; warning of
alarm signal
RealTest™
Functional CO gas entry
test -Upon successful
gas entry
Blink Red
once every
10 secs
Blink blue
every
10 secs
Modified
Temp-4
Voice carbon
monoxide warning
Low Battery
Blink Amber
every
10 secs
Dark
Chirp every 45
secs after
7 days
Voice instructions
when chirp is
hushed by pressing
either test button
Smoke Maintenance Blink Amber
every 5 secs Dark Silent
Voice smoke
maintenance
instructions if either
test button is pressed
CO Trouble
Double
Blink Amber
every 5 secs
Dark Silent
CO End of Life – First
29 days
Double
Blink Amber
every 3 secs
Dark Silent
Voice end-of- life
instructions
when either test
button
is pressed
CO End of Life – after
30 days
Double
Blink Amber
every 3 secs
Dark Chirp every
45 secs
Voice end-of-life
instructions when
either test button
is pressed
Power Up
Blink Green, for
30 secs Dark Silent
Language set
instructions only on
first time power-up
Normal (Standby)
Single Blink
Green every 10
secs
Dark Silent Silent
Freeze Warning (low
temp)
Blink Red
every
10 secs
HUSH FEATURE / ALARM SILENCE
If required, the audible alarm for smoke and CO conditions can be
silenced for 5 minutes by pushing the “Test/Hush” button. In addition, low
chirping can be silenced for 12 hours when the Test/Hush button is
pressed.
During a Smoke alarm, if an alarm condition still exists after the 5 minute
hush period, the alarm will sound. The hush feature will not operate at
levels above 4%/ft smoke concentration.
During a CO alarm, if carbon monoxide is still present after the 5 minute
hush period, the alarm will sound. The hush feature will not operate at
levels above 350 ppm (parts per million) carbon monoxide.
CO SENSOR END-of-LIFE FEATURE
When the CO sensor has passed end-of-
life, a trouble signal will be sent to
the control panel (if programmed). This indicates that the CO sensor inside
the detector must be replaced. If unresolved for 30 days, the detector will
chirp every 45 seconds. The typical life of the CO sensor is ten years from
the date of manufacture. It is recommended to periodically check the
“Replace by” date located on the label on the back of the detector head.
TESTING SIGNAL STRENGTH
Perform this test in accordance with NFPA 72 inspection, testing and
maintenance requirements to determine a strong communication path with
the control panel.
1. Activate the wireless system’s GO/NO GO TEST mode.
2. Press the detector’s Smoke TEST button (•) for 1-2 seconds. The
detector should immediately transmit an alarm signal to the control
panel. The built-in horn will start to sound about 2.5 seconds after
pressing the button.
3. The wireless system’s keypad should emit at least three beeps when
the alarm transmission is received and display the transmitting
detector’s zone number.
4. When the console has received the test signal, the horn will stop and a
few seconds later the detector’s zone number will clear from the co
nsole
display.
5. If the console does not respond as noted, and if this is an initial
installation, try moving the detector to another location that provides
proper reception. Also be sure that the detector has been “enrolled” by
the control panel (see Enrollment section). Then, repeat the test.
6. Turn off the system’s TEST mode (typically security code + OFF).
REPLACING THE BATTERIES
CAUTION: The batteries used in this device may present a fire or
chemical burn hazard if mistreated. Do not recharge, disassemble, heat
above 100°C (212°F) or dispose of in fire. Use only Panasonic CR123A
Lithium batteries. Use of other batteries may present a risk of fire or
explosion. Keep used batteries away from children. Dispose of used
batteries properly.
Remove old batteries. Wait 10 seconds and then replace with four new
batteries. To avoid a low battery indication when installing new batteries,
all 4 batteries must be installed within 15 seconds of installing the first one
.
Any low battery condition that may have occurred should clear when the
base plate is installed.
CLEANING
NOTE:Notify the proper authorities when the system
will be temporarily out of service.
IMPORTANT: This detector must be tested and
maintained regularly following NFPA-72 requirements.
The detector should be cleaned at least once a year.
1.
Remove the detector from the base plate by turning
counterclockwise.
2.
Clean the outside casing with a cloth. Ensure that
the holes on the front of the alarm are not blocked
with dirt and dust. Canned air can be used to
remove any dust or debris.
3.
Reattach the detector to the base plate by rotating
clockwise.
4.
Test the detector to insure it is fully functional. (See
Testing section).
5.
Notify the proper authorities and Central Station
when the system is back in service.
MAINTENANCE
Do not paint, and do not use cleaning agents, bleach
or polish the detector.
NOTE: Before performing any maintenance on the detector,
notify the proper authorities and Central Station that
maintenance is being performed and the system will be
temporarily out of service. Disable the zone or system
undergoing maintenance to prevent any unwanted alarms.
Power must be removed from the detector before performing
maintenance of any kind.
The 5800COMBO detector reports maintenance issues
to the control panel and communicates them visually
and audibly per Table 2.
Trouble feature: When the sensor (supervision) is in a
trouble condition (such as a detector that is dirty or CO
sensor non-functioning), the detector will send a trouble
signal to the control panel. Depending on the issue, the
detector must then be serviced or replaced.
NOTE: Smoke detectors are not to be used with detector
guards unless the combination is evaluated and found
suitable for that purpose.
LED INDICATORS
The 5800COMBO has a multi-color top LED:
Green = Supervisory indication; blinks during power on,
reset, and during normal operation
Amber = Signal maintenance and trouble events
Red = Alarm condition (either Smoke or CO)
Side LED windows indicate alarms:
red = smoke
blue = CO
Table 3: Carbon Monoxide Detector: Events and Their ID Codes
Event Alpha Keypad
CS Report
CO alarms
CO Alarm
CO alarm (CID 162)
CO test
CO Alarm
CO alarm (CID 162)
Low battery
Lo Bat
RF low-battery (CID 384)
detector
CO Trouble
RF sensor supervision
(CID 381)
detector end-of-
life/trouble CO Trouble sensor trouble - end-of life
(CID 380)
tamper
disarmed = CO Trouble
armed = CO Alarm
RF sensor tamper
(CID 383)
LIMITED LIFE OF CO SENSOR
This detector is manufactured with a long-life electrochemical carbon
monoxide sensor. Over time the sensor will lose sensitivity and will
need to be replaced. The life span of the CO sensor is approximately
ten years from the date of manufacture.
Periodically check the detector’s replacement date. Remove the
detector head and refer to the ‘replace by’ sticker placed on the
underneath side of the detector. The sticker will indicate the date the
detector should be replaced.
Reminder: This detector is also equipped with a feature that will
signal the panel once the CO sensor has passed the end of its’ useful
life. If this occurs, it is time to replace the detector.
What to do if the detector goes into CO alarm:
If the detector goes into CO alarm (4 beeps), immediately move to a
spot where fresh air is available, preferably outdoors, where the air is
safe and call your security service provider. Tell your provider the
detector alarm status, and that you require professional assistance in
ridding your home of the carbon monoxide.
This detector is NOT:
•
A substitute for the proper servicing of fuel-burning appliances or
the sweeping of chimneys.
•
To be used on an intermittent basis or as a portable alarm for the
spillage of combustion products from fuel-burning appliances or
chimneys.
Carbon monoxide gas is a highly poisonous gas which is released
when fuels are burnt. It is invisible, has no smell and is therefore is
impossible to detect with the human senses. Under normal conditions
in a room where fuel burning appliances are well maintained and
correctly ventilated, the amount of carbon monoxide released into the
room by appliances should not be dangerous.
FEDERAL COMMUNICATIONS COMMISSION STATEMENTS
The user shall not make any changes or modifications to the equipment unless
authorized by the Installation Instructions or User's Manual. Unauthorized changes or
modifications could void the user's authority to operate the equipment.
FCC STATEMENT
This device complies with Part 15 of the FCC Rules,. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference, and (2)
This device must accept any interference received, including interference that may
cause undesired operation.
SUPPORT & WARRANTY
For the latest documentation and online support information, please go to:
https://mywebtech.honeywell.com/
For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa.
For patent information, see www.honeywell.com/patents
MyWebTech
Warranty
Patents
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL WITH WHICH THIS DEVICE IS USED FOR
DETAILS REGARDING THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
Agile ref. #800
-22142 1/17 Rev E
I
56-6250-005 1/17
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
© 2016 Honeywell International Inc.
www.honeywell.com/security
SYMPTOMS OF CARBON MONOXIDE POISONING
Carbon monoxide bonds to the hemoglobin in the blood and
reduces the amount of oxygen being circulated in the body.
The following symptoms are examples taken from NFPA 720;
they represent approximate values for healthy adults.
Concentration
(ppm CO) Symptoms
200 Mild Headache after 2-3 hours of exposure
400 Headache and nausea after 1-2 hours of exposure
800 Headache, nausea, and dizziness after 45 minutes of expo-
sure; collapse and unconsciousness after 2 hours of exposure
Many cases of reported carbon monoxide poisoning indicate that
while victims are aware that they do not feel well, they become
so disoriented that they are unable to save themselves by either
exiting the building or calling for assistance. Also young children,
elderly and pets may be the first to be affected.
CO ALARM ACTIVATION
Per UL standard 2075, the 5800COMBO detector has been
tested to the sensitivity limits defined in UL standard 2034.
CO Alarm Thresholds
Parts per Million
Detector Response Time (Min.)
30+-3ppm
No alarm within 30 days
70+-5ppm
60-240
150+-5ppm
10-50
400+-10ppm
4-15
SPECIFICATIONS
Electrical Specifications
Voltage: 3 volts DC
Battery Type: CR123A lithium
Battery Manufacturer: Panasonic CR123A only
Number of Batteries: 4
Sensitivity: UL limits .9 to 3.50%/ft / ULC limits .9 to 3.08 %/ft
Thermal alarm: 135° F (57° C)
Freeze trouble: 41° F typical (5° C)
Audible Signal: 85dBA
Physical Specifications
Diameter: 16.002 cm x 4.19 cm Thick / 6.3 in. Diameter x
1.65 in. Thick
Weight: : 14.3 oz; 406 g
Operating Temperature Range: 32° –100° F / 0° –38° C
Storage Temperature Range: -10 - 70° C (14 - 158° F)
Operating Humidity Range: 20-95% RH
Approval Listings:
FCC
Listed to UL 268 & UL 2075.
Listed to CSA 6.19.
Other Standards: RoHS

Other Honeywell Security Sensor manuals

Honeywell Minipeeper C7027A Operation manual

Honeywell

Honeywell Minipeeper C7027A Operation manual

Honeywell CLLRF2OCR2BP User manual

Honeywell

Honeywell CLLRF2OCR2BP User manual

Honeywell Viewguard DUAL AM BUS-2/BUS-1 Instruction manual

Honeywell

Honeywell Viewguard DUAL AM BUS-2/BUS-1 Instruction manual

Honeywell Viewguard PIR AM FAI Instruction manual

Honeywell

Honeywell Viewguard PIR AM FAI Instruction manual

Honeywell Vitoject 890 User manual

Honeywell

Honeywell Vitoject 890 User manual

Honeywell Miller Techline HLLR Series Operator's manual

Honeywell

Honeywell Miller Techline HLLR Series Operator's manual

Honeywell Miller 8172 Operator's manual

Honeywell

Honeywell Miller 8172 Operator's manual

Honeywell Activ8 PIR User manual

Honeywell

Honeywell Activ8 PIR User manual

Honeywell C7007A User manual

Honeywell

Honeywell C7007A User manual

Honeywell OMV-VX Series User manual

Honeywell

Honeywell OMV-VX Series User manual

Honeywell Small SATCOM Instruction Manual

Honeywell

Honeywell Small SATCOM Instruction Manual

Honeywell C7061A Operation manual

Honeywell

Honeywell C7061A Operation manual

Honeywell IRD 1020.1 User manual

Honeywell

Honeywell IRD 1020.1 User manual

Honeywell PANORAMA Series User manual

Honeywell

Honeywell PANORAMA Series User manual

Honeywell Peha D MLS2001AF Installation and operation manual

Honeywell

Honeywell Peha D MLS2001AF Installation and operation manual

Honeywell C7061 A User manual

Honeywell

Honeywell C7061 A User manual

Honeywell FG-730 User manual

Honeywell

Honeywell FG-730 User manual

Honeywell FlexGuard FG-1625SN V-Plex User manual

Honeywell

Honeywell FlexGuard FG-1625SN V-Plex User manual

Honeywell MultiPro User manual

Honeywell

Honeywell MultiPro User manual

Honeywell PEHA MLS Digital Hi-Bay D MLS2001AHBF Installation and operation manual

Honeywell

Honeywell PEHA MLS Digital Hi-Bay D MLS2001AHBF Installation and operation manual

Honeywell FIRE-LITE ALARMS H365 User manual

Honeywell

Honeywell FIRE-LITE ALARMS H365 User manual

Honeywell Miller Falcon MP50G-LE Installation instructions

Honeywell

Honeywell Miller Falcon MP50G-LE Installation instructions

Honeywell Ex-Or MLS2021DF Installation and operation manual

Honeywell

Honeywell Ex-Or MLS2021DF Installation and operation manual

Honeywell SS2 Series User manual

Honeywell

Honeywell SS2 Series User manual

Popular Security Sensor manuals by other brands

EDELRID Shark Soft manual

EDELRID

EDELRID Shark Soft manual

TESTO 316-4 instruction manual

TESTO

TESTO 316-4 instruction manual

SPX Radiodetection RD8200 user guide

SPX

SPX Radiodetection RD8200 user guide

Max-Air Systems 2000-210 Instructions for use

Max-Air Systems

Max-Air Systems 2000-210 Instructions for use

Avsl primalux 522.010UK user manual

Avsl

Avsl primalux 522.010UK user manual

GE DD205RF/60-947-8A Series installation instructions

GE

GE DD205RF/60-947-8A Series installation instructions

GE KL700 Series Installation and service manual

GE

GE KL700 Series Installation and service manual

DANLERS WM-HBSP IP66 Series quick start guide

DANLERS

DANLERS WM-HBSP IP66 Series quick start guide

HSS Hire Life Line instructions

HSS Hire

HSS Hire Life Line instructions

TIF TIF8900 owner's manual

TIF

TIF TIF8900 owner's manual

Qiagen FLUO SENS manual

Qiagen

Qiagen FLUO SENS manual

PCB LOAD & TORQUE 2508-01A Installation and operating manual

PCB

PCB LOAD & TORQUE 2508-01A Installation and operating manual

Art ROPEGUIDE 2010 instruction manual

Art

Art ROPEGUIDE 2010 instruction manual

PSW Protech PSW-7175NR Instructions for use

PSW Protech

PSW Protech PSW-7175NR Instructions for use

Exit Light EXST installation instructions

Exit Light

Exit Light EXST installation instructions

Evikon PluraSens E2658-VOC user manual

Evikon

Evikon PluraSens E2658-VOC user manual

Apollo XP95A Series installation guide

Apollo

Apollo XP95A Series installation guide

PCB Piezotronics W138A05 Installation and operating manual

PCB Piezotronics

PCB Piezotronics W138A05 Installation and operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.