manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Security Sensor
  8. •
  9. Honeywell Ex-Or MLS2021DF Installation and operation manual

Honeywell Ex-Or MLS2021DF Installation and operation manual

Installation and Commissioning
Instructions
Note: QuickSet Pro required for commissioning
1
MLS2021DSM
MLS2021DALISM
MLS2021DF & MLS2021DSM for DSI ballasts
MLS2021DALIF & MLS2021DALISM for DALI ballasts
Digital Gold PIR Detector
with regulating photocell
MLS2021DF
MLS2021DALIF
Digital Gold PIR Detector with Regulating Photocell
Please note that UltraLite versions of these detectors (suffix CWL7) do not offer
MLS functionality and cannot be connected using MLS cable.
Only suitably qualified personnel should install this equipment.
This is a high-performance, communicating presence detector which can be used as
part of a full Ex-Or MLS Digital Managed Lighting System or as a stand-alone unit. It is
equipped with a regulating photocell to control digital DSI or DALI ballasts (when using
the detector’s Digital Output) and a volt-free output for control of non-dimmable lighting
loads. The product incorporates Ex-Or’s OneSwitch Dimming, local manual operation of
any controlled lighting load.
Electrical Connections
This detector should be connected in accordance with the diagrams overleaf. Both the
Digital Output and MLS connections are polarity-free however other MLS products
require that polarity be maintained. The MLS cable should be mains-rated, unscreened,
twisted pair of at least 1.5mm CSA. For further information please refer to Wiring
Application Guide AN4001. Please note that UltraLite versions of these detectors
(suffix CWL7) do not offer MLS functionality and cannot be connected using MLS
cable.
The detector is designed to control up to 25 DSI or DALI luminaires, a switched load of
up to 6 Amps or a combination of the two. When controlling DSI or DALI ballasts the
ballast type must not be mixed. The DSI or DALI input terminals on the ballasts should
be connected in parallel with each other and to the Polarity-Free Digital Output terminals
on the rear of the detector. Each DSI or DALI luminaire is controlled completely by its
digital input and therefore would normally have a permanent power supply. Turning the
power off to some lights within a control circuit will not affect the operation of those lights
that remain powered up and under the control of the detector.
When switching via the volt-free output, multiple MLS2021D detectors may be
connected in parallel provided the controlled load does not exceed 6 Amps.
Note: The digital dimming signals of two detectors should NEVER be connected
together. Their only connections should be to the digital inputs of high frequency
ballasts of the correct type.
Fixing
MLS2021DSM/DALISM - The housing may be secured to a hard surface or to a BESA
box. The unit fits into the housing with a simple bayonet action.
MLS2021DF/DALIF - Supplied with a sinking (dry-lining) box for flush fitting. The
sinking box fits into an 89mm diameter hole in a ceiling tile or plasterboard ceiling. To
avoid damage to ceiling tile do not overtighten. Depth required behind ceiling 62mm from
front flange plus an allowance for the minimum bend radius of the cable. No access
above the ceiling is necessary.
2
3
Digital
Output
MLS
BUS
These Connections are
Polarity-Free
1 2 1 2
MLS2021D
Using OneSwitch, MLS*, Switched and
Digital Outputs
N
E
L
Permanent
or switched
supply
VOLT-
FREE
OUTPUT
LIVE
NEUTRAL
EARTH
LOAD
(MAX 6 AMPS)
ONESWITCH
DIMMING
Digital output
MLS Bus Connection
(Some MLS devices require
that polarity be maintained)
Momentary
push-to-make
switch
Digital
Output
MLS
BUS
These Connections are
Polarity-Free
1 2 1 2
MLS2021D
Using Switched Output and MLS*
N
E
L
Permanent
or switched
supply
VOLT-
FREE
OUTPUT
LIVE
NEUTRAL
EARTH
LOAD
(MAX 6 AMPS)
ONESWITCH
DIMMING
Optional MLS Bus Connection
(Some MLS devices require
that polarity be maintained)
NC
NC
2 x MLS2021D
In Parallel, using Switched Output only
LOAD
(Max 6 Amps)
N
E
LPermanent
or switched
supply
VOLT-
FREE
OUTPUT
VOLT-
FREE
OUTPUT
LIVE IN LIVE IN
NEUTRAL NEUTRAL
EARTH EARTH
Any connection not shown is NO CONNECTION
ONE
SWITCH
NC NC
ONE
SWITCH
Relay outputs may be connected together in parallel to cover larger areas, however the
total load on all combined relay outputs must not exceed 6 Amps.
Please note that the Earth terminal has no internal
connection and is used for termination only.
Please note that the Earth terminal has no internal
connection and is used for termination only.
* UltraLite-version detectors (suffix CWL7)
do not offer MLS functionality and cannot
be connected using MLS cable.
* UltraLite-version detectors (suffix CWL7)
do not offer MLS functionality and cannot
be connected using MLS cable.
Parameter
Power up
Response
Off delay
On Sensitivity
Bus Connect
1st Zone
2nd Zone
3rd Zone
4th Zone
Corridor 1
Corridor 2
Global 1 Rx
Global 2 Rx
Manual I/P
Start Lamps
Entry Scene
Lamp Max
Dimming
Fade to Off
Vacant
Bright-Out
Photocell
Set Point Low
Set Point High
Default
Setting
ON
AUTO
20 min
100
YES
-
-
-
-
-
-
NO
NO
LOCAL
MAX
Scene 1
100%
100%
NO
OFF
NO
Disabled
1023
1023
Options
ON/OFF
Auto, Manual/Bus, Manual Only
1min - 96hrs, Disabled
0-100
YES/NO
1-100 addresses
1-100 addresses
1-100 addresses
1-100 addresses
1-100, Building Zone Span
1-100, Building Zone Span
YES/NO
YES/NO
LOCAL/SHARE
MAX/MIN
Scene 1-6
10% - 100%
Regulate 100% to 50%
YES/NO
(10 Alternative Exit Scenes)
YES/NO
Active, Passive, Disabled
1-1023
1-1023
Notes
Each of these settings
can be re-programmed,
if desired, by use of the
infrared programming
tool QuickSet Pro.
All settings are retained
in the event of a power
failure.
Commissioning
The units are supplied with the factory default settings shown below which make further
commissioning unnecessary in many applications. To make use of the programmable
settings, an infrared commissioning tool is required (QuickSet Pro). A ten-second time
delay is selectable from programmer to aid commissioning.
Sensitivity to Movement
While the factory settings will be correct for many applications, the sensitivity can be
adjusted if required. The ON RANGE setting controls the sensitivity, with higher
numbers giving greater sensitivity. Like all programmable parameters, the sensitivity
setting will be retained in the event of a power failure and can be re-programmed any
number of times.
Factory Default Settings
These are the settings to which the units have been programmed before they leave
the factory.
4
5
Photocell Control
i) Regulating Photocell
Regulating photocell control tries to maintain a constant level of total illumination in the
space controlled by dimming and brightening the controlled luminaires to compensate
for changes in illumination from other sources.
With the photocell configured as DISABLED the Regulating Control module is
influenced only by the BRIGHT-OUT setting. BRIGHT-OUT = YES allows it to hold-off
the lights at the start of occupancy if natural light already exceeds SET-POINT LOW
and to extinguish the lights during occupancy if total light, after the controlled luminaires
have been dimmed to minimum, exceeds SET-POINT HIGH continuously for a period
equal to the OFF DELAY . The lighting is restored immediately if the illumination level
subsequently drops below SET-POINT LOW.
If the photocell is configured for ACTIVE or PASSIVE control of the relay switched load
then the Regulating Control module adopts the decision made by the Switching Control
module in the case of turn-on inhibit on entry, but still obeys the BRIGHT-OUT YES/NO
setting with regard to turn-off during occupancy.
ii) Switching Photocell (PHOTOCELL: ACTIVE or PASSIVE)
Both ACTIVE or PASSIVE modes hold off the controlled lighting on entry when natural
light is sufficient, i.e. SET-POINT LOW is exceeded, but only ACTIVE mode will
extinguish the lighting if natural light increases sufficiently during occupancy, i.e. SET-
POINT HIGH is exceeded continuously for a period equal to OFF DELAY. The lighting
is restored immediately if the illumination level subsequently drops below SET-POINT
LOW.
iii) Photocell DISABLED
If the photocell is configured as DISABLED for relay Switching Control it will have no
effect on the control of that load, which will be ON continuously during periods of
occupancy unless commanded OFF via manual switch or infrared control. The photocell
readings are still available for use by the Regulating Control module while in this mode.
Programming the Photocell Set-points.
The parameters SET-POINT LOW and SET-POINT HIGH programme the detector’s
photocell response The SET-POINTS can be manually programmed as numbers
between 1 (darkest) and 1023 (brightest). This number is not scaled to correlate with
‘lux’ measurements made using a light meter, but nevertheless is a true representation
of the light level perceived by the detector. To assist with finding the appropriate SET-
POINT settings, the light level currently perceived by the photocell can be viewed on the
QuickSet Pro screen briefly, following a download operation. The number represents the
light level read immediately before the download took place.
Programming the Photocell Set-points (Continued)
Tip: Turn the lights off with the QuickSet Pro (UTILITIES / LIGHTSPOT/MLS/LCM /
IR REMOTE / HC5) to measure the perceived light level with no contribution from the
controlled lighting.
Alternatively the SET-POINTS can be configured semi-automatically;
i) The Primary Interest is the Regulating Control Output.
With the photocell configured as DISABLED:-
Using the QuickSet Pro (UTILITIES / LIGHTSPOT/MLS/LCM / SET LIGHT LEVEL)
or HC5A (+,- Scene 1) set the required light output from the controlled luminaires and
then press and hold OK (QuickSet Pro) or Scene 1 (HC5A) until the controlled lights
"blink" to indicate that a new SET-POINT LOW has been stored and a calculated SET-
POINT HIGH has also been inserted. Using the QuickSet Pro the photocell can now be
re-configured as ACTIVE or PASSIVE if required.
With the photocell configured as ACTIVE or PASSIVE:-
1) If the lights are not already on, switch them on manually by pressing ‘UTILITIES /
LIGHTSPOT/MLS/LCM / IR REMOTE / Luminaire+ / OK’ (QuickSet Pro) or "+"
(HC5A). Fluorescent lights do not reach full output until up to 15 minutes after being
switched on, so ensure that the lights are fully warmed up before continuing.
2) Wait until the time of day when the natural light level is at the point below which you
would want the lights to be on, and above which you would not want the lights to be on.
3) Start the internal self-programming mechanism by pressing ‘UTILITIES /
LIGHTSPOT/MLS/LCM / SET LIGHT LEVEL / OK’ (QuickSet Pro) or Scene 1 (HC5A).
The detector takes a photocell reading, adds a small amount and stores the value in
SET-POINT HIGH. Then it turns the lights off, makes another measurement and stores
the value in SET-POINT LOW. The lights now switch on again to acknowledge a
successful programming operation.
The two switching thresholds have now been set, and the difference between them is
equal to slightly more than the contribution made by the electric lighting. This is the
perfect amount of hysteresis to ensure that the lights will not oscillate.
6
OneSwitch
OneSwitch Dimming affords local control to the end-user whereby a simple,
momentary, push-to-make wall switch can be used to raise or lower the lighting level or
toggle the output of the unit ON or OFF. A short press (less than 1 second) toggles all
outputs from both OFF to both ON or from either ON to both OFF. A long press will ramp
the digital output either up or down with no effect on the volt-free output. If the output
prior to pressing the switch is above 90% the output will ramp down; if below 90% it will
ramp up. If the latest press and the current press are within 5 seconds of each other it will
ramp in the opposite direction. A latching switch can be used to override the outputs
OFF or ON at maximum output.
User Overrides
The end-user can configure a number of lighting scenes that can be recalled using a
hand-held override. With an HC5A hand-held controller lighting can be overridden OFF
or ON, or a set level can be chosen, affecting either the controlled group or, with an MLS
system, the whole zone. Regulating and switched loads can be adjusted independently
through a combination of OneSwitch Dimming and the HC5A.
Important Additional Notes
1. All terminals on this product are provided for final connections. It is not intended that the
product be used as a junction box for looping cables.
2. A means for disconnection must be incorporated in the fixed wiring in accordance with the
current wiring regulations.
3. Although nominally 12V, the dimming output is not SELV and therefore should be treated
with the same respect as mains with regard to wiring practice.
4. The dimming control output should be connected only to the control input of the ballasts -
never to other detectors.
5. Due to the fact that the photocell is on the ceiling looking down, it is not possible for
measurements made with a lux meter on the working plane to remain constant when daylight
illuminates the ceiling and the working plane to a differing extent. Therefore, products of this
type should be regarded as capable of maintaining an APPROXIMATE light level only.
6. This equipment switches lights no more frequently than would a responsible human
occupant. However, manufacturers of some lighting types (e.g. ‘2D’ luminaires) may specify
a maximum number of switching cycles in order to achieve a predicted lamp life. Please
check with the manufacturer of the luminaires to ensure that they are compatible with
automatic controls in this respect.
7
Technical Data
2
MLS CABLE : 1.5mm unscreened twisted-pair (applicable when
detector is used as part of a full MLS Digital Managed Lighting
System): see Application Note AN4001
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3.0m
RANGE: Cone-shaped detection
pattern, diameter (at floor level)
= 2.4 x mounting height
OFF DELAY: 1 minute - 96 hours (adjustable)
PHOTOCELL: Adjustable 50-5000 lux via HP2000
OPERATING VOLTAGE: 230V ~ 50Hz (UK & Europe)
PRODUCT RATING AND RECOMMENDED CIRCUIT
PROTECTION: 10 Amps
MAXIMUM RECOMMENDED LOAD (VOLT-FREE): 6 Amps
MAXIMUM RECOMMENDED LOAD (DSI/DALI): 25 Ballasts
COLOUR: White (RAL9010)
MATERIAL: Flame retardant PC/ABS
WEIGHT: 210g (flush version), 187g (surface version)
IP RATING: 3X
o o
OPERATING TEMPERATURE: 0 C to 40 C
W4426G
6.0m
2.5m
Fascia
10mm
deep
8
100mm
Honeywell Ex-Or
St. Marks Court, North Street,
Horsham, West Sussex, RH12 1BW, UK
Tel:+44 (0)1942 719229
Fax: +44 (0)1942 508753
Email: technicalsales.ex-or@honeywell.com
www.ex-or.com
At the end of their useful life
the packaging and product
should be disposed of via a
suitable recycling centre.
Do not dispose of with normal
household waste.
Do not burn.
Dimensions
Outer Enclosure
62mm deep
(behind ceiling for
MLS2021DF and
MLS2021DALIF)

This manual suits for next models

3

Other Honeywell Security Sensor manuals

Honeywell BW Solo User manual

Honeywell

Honeywell BW Solo User manual

Honeywell Lyric W1 User manual

Honeywell

Honeywell Lyric W1 User manual

Honeywell 748LC User manual

Honeywell

Honeywell 748LC User manual

Honeywell 997 User manual

Honeywell

Honeywell 997 User manual

Honeywell Ex-Or LS3043DR User manual

Honeywell

Honeywell Ex-Or LS3043DR User manual

Honeywell Lyric YCHW4000W4004 Installation guide

Honeywell

Honeywell Lyric YCHW4000W4004 Installation guide

Honeywell FS24X User manual

Honeywell

Honeywell FS24X User manual

Honeywell Searchline Excel Cross-Duct Release Note

Honeywell

Honeywell Searchline Excel Cross-Duct Release Note

Honeywell R4343E User manual

Honeywell

Honeywell R4343E User manual

Honeywell 5800FLOOD User manual

Honeywell

Honeywell 5800FLOOD User manual

Honeywell XT Series User manual

Honeywell

Honeywell XT Series User manual

Honeywell FG8M User manual

Honeywell

Honeywell FG8M User manual

Honeywell GENT S4-720 Instruction manual

Honeywell

Honeywell GENT S4-720 Instruction manual

Honeywell Fire-Lite Alarms SD365T User manual

Honeywell

Honeywell Fire-Lite Alarms SD365T User manual

Honeywell Miller DuraHoist Operator's manual

Honeywell

Honeywell Miller DuraHoist Operator's manual

Honeywell PEHA D MLS2500CDRR4 Installation and operation manual

Honeywell

Honeywell PEHA D MLS2500CDRR4 Installation and operation manual

Honeywell MaxLED Centralized Series User manual

Honeywell

Honeywell MaxLED Centralized Series User manual

Honeywell Ex-Or MLS2401CDR Installation and operation manual

Honeywell

Honeywell Ex-Or MLS2401CDR Installation and operation manual

Honeywell DT8035 DUAL TEC User manual

Honeywell

Honeywell DT8035 DUAL TEC User manual

Honeywell Ex-Or MR1500P Installation and operation manual

Honeywell

Honeywell Ex-Or MR1500P Installation and operation manual

Honeywell BW Ultra User manual

Honeywell

Honeywell BW Ultra User manual

Honeywell C08MS User manual

Honeywell

Honeywell C08MS User manual

Honeywell 5800COMBO User manual

Honeywell

Honeywell 5800COMBO User manual

Honeywell krom schroder DG Smart Manual

Honeywell

Honeywell krom schroder DG Smart Manual

Popular Security Sensor manuals by other brands

ANATEL LN-104C EMF Instructions and warnings for installation and use

ANATEL

ANATEL LN-104C EMF Instructions and warnings for installation and use

Eaton HaloHome MST20C18W instruction manual

Eaton

Eaton HaloHome MST20C18W instruction manual

Camp Safety GOBLIN manual

Camp Safety

Camp Safety GOBLIN manual

SORHEA G-WALL installation manual

SORHEA

SORHEA G-WALL installation manual

Camp Safety SWIFTY VEST manual

Camp Safety

Camp Safety SWIFTY VEST manual

Eaton 2450 Series manual

Eaton

Eaton 2450 Series manual

Carrier DET-TRONICS Dual Spectrum PM-5MPX instructions

Carrier

Carrier DET-TRONICS Dual Spectrum PM-5MPX instructions

MAXIMUM Security CURTAIN-FLT manual

MAXIMUM Security

MAXIMUM Security CURTAIN-FLT manual

Petzl Croll manual

Petzl

Petzl Croll manual

Velleman VTTEST18 user manual

Velleman

Velleman VTTEST18 user manual

Maxouttech RF-RDWS-345-NN installation instructions

Maxouttech

Maxouttech RF-RDWS-345-NN installation instructions

Tinker & Rasor M/1 Product instructions

Tinker & Rasor

Tinker & Rasor M/1 Product instructions

Abus AirSecure CO2WM110 user manual

Abus

Abus AirSecure CO2WM110 user manual

Abus FUMK50020 installation instructions

Abus

Abus FUMK50020 installation instructions

Ono Sokki FP-4135 instruction manual

Ono Sokki

Ono Sokki FP-4135 instruction manual

DF ROBOT SEN0545 user manual

DF ROBOT

DF ROBOT SEN0545 user manual

Fantini Cosmi Sicurgas P63 manual

Fantini Cosmi

Fantini Cosmi Sicurgas P63 manual

TECHNO-AC Success CBI-116N operating instructions

TECHNO-AC

TECHNO-AC Success CBI-116N operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.