mount applications. NOTE: SD365R and SD365R-IV are also listed for use in-
side DNR(W) duct smoke detectors.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes, and any special requirements of the Authority Having
Jurisdiction. Proper wire gauges should be used. The installation wires should
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the
event of a fire.
Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) per the wiring diagram, Figure 2.
2. Set the desired address on the sensor address switches, see Figure 1.
3. Install the sensor into the sensor base. Push the sensor into the base while
turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control panel and
activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
CAUTION
Dust covers provide limited protection against airborne dust particles during
shipping. Dust covers must be removed before the sensors can sense smoke.
Remove sensors prior to heavy remodeling or construction.
FIGURE 2. WIRING DIAGRAM:
2
31
2
33
1
2
1
(–)
(+)
+ -
UL Listed Compatible
Control Panel
CAUTION: Do not loop wire under
terminal 1 or 2. Break wire run to
supervise connections.
CLASS A OPTIONAL WIRING
Remote
Annunciator
(–)
(+)
RA
+–
+
RA
+–
+
RA
+–
+
C0129-10
TAMPER-RESISTANCE
Models SD365R and SD365R-IV include a tamper-resistant capability that pre-
vents their removal from the base without the use of a tool. Refer to the base
manual for details on making use of this capability.
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Test-
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors
SPECIFICATIONS
Operating Voltage Range: 15 to 32 VDC
Operating Current @ 24 VDC: 200 uA (one communication every 5 seconds with green LED blink on communication)
Maximum Alarm Current: 2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)
Maximum Current: 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)
Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range: 32°F to 122°F (0°C to 50°C), -4°F to 158°F (-20°C to 70°C) in duct applications
Air Velocity: 0 to 4000 ft./min. (0 to 1219.2 m/min.)
Height: 2.0˝ (51 mm) installed in B300-6 Base
Diameter: 6.2˝ (156 mm) installed in B300-6 Base; 4.1˝ (104 mm) installed in B501 Base
Weight: 3.4 oz. (95 g)
Isolator Load Rating: 0.0063*
*Please refer to your isolator base/module manual for isolator calculation instructions.
UL268A listed for Duct Applications
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when
installed in compliance with the National Fire Protection Association (NFPA);
see NFPA 72.
GENERAL DESCRIPTION
Models SD365R and SD365R-IV are plug-in type smoke sensors that combines
a photoelectronic sensing chamber with addressable-analog communications.
When used in duct applications with a DNR(W), testing can be done remotely
using approved System Sensor test accessories, eliminating the need for a test
coil. The sensors transmit an analog representation of smoke density over a
communication line to a control panel. Rotary dial switches are provided for
setting the sensor’s address.
FIGURE 1. ROTARY ADDRESS SWITCHES:
TENS ONES
910
11
12
13
14
15
8
7
6
5
4
3
210
9
8
7
6
5
4
3
210
C0162-00
Two LEDs on the sensor are controlled by the panel to indicate sensor status.
An output is provided for connection to an optional remote LED annunciator
(P/N RA100Z).
Note: Only System Sensor approved accessories may be used with the SD365R
and SD365R-IV.
Fire-Lite panels offer different features sets across different models. As a re-
sult, certain features of the photoelectric sensors may be available on some
control panels, but not on others. SD365R will support only LiteSpeed® pro-
tocol mode. SD365R-IV will support either LiteSpeed or CLIP (Classic Loop
Interface Protocol) mode. The possible features available in the SD365R and
SD365R-IV, if supported by the control panel are:
1. The sensor’s LEDs can operate in three ways—on, off, and blinking–and
they can be set to red, green, or amber. This is controlled by the panel.
2. The remote output may be synchronized to the LED operation or con-
trolled independent of the LEDs.
3. Devices are point addressable up to 159 addresses.
Please refer to the operation manual for the UL listed control panel for specific
operation. The SD365R and SD365R-IV require compatible addressable com-
munications to function properly. Connect these sensors to listed-compatible
control panels only.
SPACING
Fire-Lite recommends spacing sensors in compliance with NFPA 72. In low air
flow applications with smooth ceilings, space sensors 30 feet apart (9.1 m).
For specific information regarding sensor spacing, placement, and special ap-
plications, refer to NFPA 72 or the System Smoke Detector Application Guide,
available from Fire-Lite.
Duct Applications: SD365R and SD365R-IV are listed for use in ducts. See
Duct Smoke Detectors Applications Guide HVAG53 for details on pendant
I56-6524-001
INSTALLATION AND MAINTENANCE INSTRUCTIONS
SD365R and SD365R-IV
Intelligent Photoelectric Smoke Sensor
with Remote Test Capability in Duct Applications
One FireLite Place
Northford, CT 06472
Phone: 203.484.7161
Preliminary 1 I56-6524-001
09/23/2019
Fire-Lite®and LiteSpeed®are registered trademarks of Honeywell International, Inc. Testifire®is a registrered trademark of SDi, LLC.
offer maximum performance when tested and maintained in compliance with
NFPA 72.
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
This sensor can be functionally tested with a test magnet. The test magnet
electronically simulates smoke in the sensing chamber, testing the sensor
electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown in Figure 3.
2. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor
status. Coded signals, transmitted from the panel, can cause the LEDs to
blink, latch on, or latch off. Refer to the control panel technical documen-
tation for sensor LED status operation and expected delay to alarm.
B. Smoke Entry
Sensitivity readings are available through the FACP. Refer to the manufac-
turer’s published instructions for proper use.
Additionally, canned aerosol simulated smoke (canned smoke agent) may
be used for smoke entry testing of the smoke detector. Tested and ap-
proved aerosol smoke products are:
Manufacturer Model
HSI Fire & Safety 25S, 30S (PURCHECK)
SDi SMOKE CENTURIAN, SOLOA4,
SMOKESABRE, TRUTEST
No Climb TESTIFIRE 2000
When used properly, the canned smoke agent will cause the smoke detec-
tor to go into alarm. Refer to the manufacturer’s published instructions for
proper use of the canned smoke agent.
CAUTION
Canned aerosol simulated smoke (canned smoke agent) formulas will vary by
manufacturer. Misuse or overuse of these products may have long term ad-
verse effects on the smoke detector. Consult the canned smoke agent manufac-
turer’s published instructions for any further warnings or caution statements.
C. Remote Test.
SD365R and SD365R-IV can be remotely tested using the RTS151 or
RTS151KEY test accessories. Refer to the DNR(W) manual for wiring dia-
grams. Maximum test response time may be up to two communications
from the panel.
A sensor that fails any of these tests may need to be cleaned as described
under CLEANING, and retested. When testing is complete, restore the system
to normal operation and notify the proper authorities that the system is back
in operation.
CLEANING
Before removing the detector, notify the proper authorities that the smoke
detector system is undergoing maintenance and will be temporarily out of
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.
1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place.
3. Vacuum the screen carefully without removing it. If further cleaning is
required continue with Step 4, otherwise skip to Step 7.
4. Remove the chamber cover/screen assembly by pulling it straight out.
5. Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber.
6. Reinstall the chamber cover/screen assembly by sliding the edge over the
sensing chamber. Turn until it is firmly in place.
7. Replace the cover using the LEDs to align the cover and then gently push-
ing it until it locks into place.
8. Reinstall the detector.
9. Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.
SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.
FIGURE 3: FEATURES OF THE PHOTO DETECTOR
Magnet
Test
Marker
LED
Base
Alignment
Notch
Magnet Test Marker
Base Alignment Notch
LED
Remote
Test
Capable
C2021-01
FIGURE 4: CLEANING THE PHOTO DETECTOR
Cover
Removal
Tabs
Sensor Cover
Sensing Chamber
Cover and Screen
Sensing Chamber
C2022-00
SPECIAL APPLICATION
When configured at the fire alarm control panel, this detector is capable of op-
erating in a special application mode such that it has a higher sensitivity than
is normally allowed by UL 268 for areas where early warning is important. In
this mode, the detector does not comply with the Cooking Nuisance Smoke
Test. Detectors (Sampling ports) set to the special application mode are not
suitable for use in areas where cooking appliances may be used. If cooking
appliances are used within the protected space, a normal application detector
or normal application mode must be used for that area.
Special application mode is not for general use and the detector may be more
prone to false alarms if used in unsuitable environments. While no list is
all-inclusive, some examples of unsuitable environments for special applica-
tion mode are areas with airborne particulate or aerosols including sawing,
drilling, and grinding operations, textile or agricultural processing, or areas
with engines that are not vented to the outside. A complete list of aerosol and
particulate sources is available in the Annex of NFPA 72.
Suitable environments for special application mode could include early warn-
ing for hospitals, museums, assisted living and other areas that do not have
airborne particulate or aerosols.
Refer to the fire alarm control panel documentation for information on how to
configure the detector for special application mode.
FCC STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference,
and (2) this device must accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there
is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following
measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
This Class B digital apparatus complies with Canadian ICES-003.
Please refer to insert for the Limitations of Fire Alarm Systems
DEVICE AND SYSTEM SECURITY
Before installing this product ensure that the
tamper seal on the packaging is present and
unbroken and the product has not been tampered
with since leaving the factory. Do not install this
product if there are any indications of tampering.
If there are any signs of tampering the product
should be returned to the point of purchase.
It is the responsibility of the system owner to
ensure that all system components, i.e. devices,
panels, wiring etc., are adequately protected to
avoid tampering of the system that could result
in information disclosure, spoofing, and integrity
violation.
Preliminary 2 I56-6524-001
©2019 Fire-Lite. 09/23/2019

This manual suits for next models

1

Other Honeywell Smoke Alarm manuals

Honeywell GENT Venturi-Air Duct Kit User manual

Honeywell

Honeywell GENT Venturi-Air Duct Kit User manual

Honeywell D355PL User manual

Honeywell

Honeywell D355PL User manual

Honeywell 5193SD User manual

Honeywell

Honeywell 5193SD User manual

Honeywell Lyric User manual

Honeywell

Honeywell Lyric User manual

Honeywell FCI 1151 User manual

Honeywell

Honeywell FCI 1151 User manual

Honeywell SiXCOMBO User manual

Honeywell

Honeywell SiXCOMBO User manual

Honeywell NOTIFIER FSP-951T-SELFT User manual

Honeywell

Honeywell NOTIFIER FSP-951T-SELFT User manual

Honeywell NOTIFIER NFXI-ASD11 Quick start guide

Honeywell

Honeywell NOTIFIER NFXI-ASD11 Quick start guide

Honeywell FMST FXV(E) Series User manual

Honeywell

Honeywell FMST FXV(E) Series User manual

Honeywell SS4-A2 User manual

Honeywell

Honeywell SS4-A2 User manual

Honeywell C8600A User manual

Honeywell

Honeywell C8600A User manual

Honeywell FAAST LT User manual

Honeywell

Honeywell FAAST LT User manual

Honeywell FireLite BEAM355 User manual

Honeywell

Honeywell FireLite BEAM355 User manual

Honeywell SiX Series User manual

Honeywell

Honeywell SiX Series User manual

Honeywell TC846A1005 User manual

Honeywell

Honeywell TC846A1005 User manual

Honeywell DFS8MS User manual

Honeywell

Honeywell DFS8MS User manual

Honeywell 5800COMBO User manual

Honeywell

Honeywell 5800COMBO User manual

Honeywell LT-200 MI-FL20 Series User manual

Honeywell

Honeywell LT-200 MI-FL20 Series User manual

Honeywell SiXSMOKE User manual

Honeywell

Honeywell SiXSMOKE User manual

Honeywell Ademco 5806 W3 Operating instructions

Honeywell

Honeywell Ademco 5806 W3 Operating instructions

Honeywell Photoelectronic Smoke/Temperature Detector... Assembly instructions

Honeywell

Honeywell Photoelectronic Smoke/Temperature Detector... Assembly instructions

Honeywell Fire Sentry SS4-AUV User manual

Honeywell

Honeywell Fire Sentry SS4-AUV User manual

Honeywell Gamewell 7100 Series Installation instructions

Honeywell

Honeywell Gamewell 7100 Series Installation instructions

Honeywell Smoke Alarm User manual

Honeywell

Honeywell Smoke Alarm User manual

Popular Smoke Alarm manuals by other brands

Cavius 2203-002 user guide

Cavius

Cavius 2203-002 user guide

Ei Electronics Ei 105R Optical product manual

Ei Electronics

Ei Electronics Ei 105R Optical product manual

FireAngel ST-625-INT manual

FireAngel

FireAngel ST-625-INT manual

DSC MN-240 series Installation and operation instructions

DSC

DSC MN-240 series Installation and operation instructions

Kidde TRUSENSE SMOKE 3050-VAS10 user guide

Kidde

Kidde TRUSENSE SMOKE 3050-VAS10 user guide

Brigit Systems BRS-SC installation instructions

Brigit Systems

Brigit Systems BRS-SC installation instructions

LST AOEX-55000-640 Specification sheet

LST

LST AOEX-55000-640 Specification sheet

Aico Ei600 Series User instructions

Aico

Aico Ei600 Series User instructions

Bellman & Symfon BE1284 manual

Bellman & Symfon

Bellman & Symfon BE1284 manual

Z-Wave SF813 manual

Z-Wave

Z-Wave SF813 manual

BRK electronic SC9120LBL quick start guide

BRK electronic

BRK electronic SC9120LBL quick start guide

Winext AN-102D user manual

Winext

Winext AN-102D user manual

Hama GS 508 operating instructions

Hama

Hama GS 508 operating instructions

GE Z630-3 Installation sheet

GE

GE Z630-3 Installation sheet

Bosch D296 Series Application guide

Bosch

Bosch D296 Series Application guide

Kidde TRUSENSE SMOKE 3050-VDS10 user guide

Kidde

Kidde TRUSENSE SMOKE 3050-VDS10 user guide

SILENT KNIGHT 5700 Installation and operation manual

SILENT KNIGHT

SILENT KNIGHT 5700 Installation and operation manual

Meridian WLS906-433 Instructions for installation and use

Meridian

Meridian WLS906-433 Instructions for installation and use

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.