
T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
9 62-0258
Get Factory Schedule (Info/Clear)
Performing this operation reverts the schedules to the 
factory defaults:
1. Press both Info and Clear Start Time.
2. The display gives the option to revert to FAC SCH.
a. To restore the factory schedule, press up !or 
down "until the display indicates YES.
b. To cancel this option, ensure display indicates 
NO.
3. Press Run Schedule.
Test Mode (Occupied/Not Occupied/Schedule 
Day)
CAUTION
Possible Equipment Damage.
Equipment damage can result if compressor is 
cycled too quickly.
The minimum off time for compressors is 
bypassed during Test Mode. Equipment damage 
can occur if the compressor is cycled too quickly.
Use the Test Mode to check the thermostat configurations 
and operation. To start the system test:
1. Press Schedule Day, Occupied and Not Occupied 
simultaneously.
2. The display gives the option to TEST.
a. To enter test mode, press up !or down "until 
the display indicates IN TEST.
b. To cancel this option, ensure display indicates 
NO TEST.
3. Press Run Schedule.
NOTES:
— To verify whether or not the system test is still 
active, repeat the above process.
— The system test times out after ten minutes 
with no key pressed.
Save User Schedule (Info/Copy)
Performing this operation saves the current schedule 
(including holidays) to memory, overwriting the old saved 
schedule:
1. Press both Info and Copy.
2. The display gives the option to revert to SAV SHD.
a. To save the current schedule, press up !or 
down "until the display indicates YES.
b. To cancel this option, ensure display indicates 
NO.
3. Press Run Schedule.
Get User Schedule (Info/Run)
Getting the user schedule restores the schedule 
(including holidays) from saved memory, overwriting the 
schedule currently in use:
1. Press both Run Schedule and Info.
2. The display gives the option to GET SHD.
a. To retrieve the saved schedule, press up !or 
down "until the display indicates YES.
b. To cancel this option, ensure display indicates 
NO.
3. Press Run Schedule
DEHUMIDIFICATION
There are five methods through which the T7351 can 
control for dehumidification. Three of them modify the 
control algorithm, thus providing limited dehumidification 
through cooling. The other two use the auxiliary output to 
control another device.
NOTE: The dehumidification high limit can be set within 
the range of 10 to 90 percent relative humidity.
Control Through Cooling
Configure using some combination of the following:
— Minimum On.
— Reheat.
— Reset.
NOTES:
— These methods operate only during cooling.
— Selecting both Reheat and Reset options can 
cause frequent setpoint adjustments. This 
selection is not recommended.
Min. ON Time
Dehumidifies by increasing the compressor minimum on 
time (normally 3 minutes) by a programmable amount. 
This is useful with oversized systems in that it forces the 
coils to cool to a point where dehumidification can occur.
NOTES:
— Can force wider temperature swings by cool-
ing when setpoint control does not require it.
— The minimum on time can be set within the 
range of 5 to 15 minutes.
— Hysteresis and a minimum timer are used to 
ensure this behavior does not change with 
every equipment cycle.
Reheat
Dehumidifies by operating cooling during typical off time. 
The T7351 maintains the proper setpoint by running the 
heat at the same time.
IMPORTANT
At times during Reheat dehumidification, the 
T7351 operates heating and the cooling simulta-
neously. This is normal.
NOTES:
— The heat stage never energizes during 
Reheat if more than one cool stage is on.
— Reheat mode cannot occur during heating.
Reset Temp SetPt
The room temperature set point resets to a specified 
number of degrees below the actual set point when room 
relative humidity (RH) rises above humidity high limit set 
point.
Though this may not technically reduce relative humidity 
in the room, it reduces the dew point to provide the 
customer with a sense of comfort due to a lower 
temperature setting in the room.
As long as RH stays above humidity high limit set point, 
this set point is maintained.
NOTE: Hysteresis and a minimum timer prevent the set 
point from short interval alternation (between 
standard and reset set points).