
11
installation & operation manual | clv heating system
4 MAINTENANCE,
REPAIR AND
TROUBLESHOOTING
4.1 SYSTEM FAULTS
4.1.1 COOLANT FAULTS
The coolant fault light will display if:
• The coolant pump motor protection switch is
tripped (MPS1).
• The coolant high-limit temperature is
exceeded (TCR2).
A failure in the pump motor that causes the motor
protection switch (MPS1) to trip will shut down the
heating system. A fault signal will be transmitted and the
coolant fault light will illuminate. If this failure occurs, the
on/off/prime switch must be switched to off and the
operator must press the MPS reset/on button to reset the
fault. (See SECTION 3.1.1.)
If there is a failure that causes a high temperature to
occur, the high-limit temperature controller (TCR2)
will shut down the heating system, including the
pump motor. A fault signal will be transmitted and the
coolant fault light will illuminate. To restart the system,
the on/off/prime switch must be switched to off
and then back to on to resume operation once the
uid temperature drops below the high-limit preset.
Restarting the system remotely will also reset a high-limit
fault. (See SECTION 3.1.3.)
NOTE: A high-limit fault can only occur when the
heating element is energized.
For additional troubleshooting, see SECTION 4.5.
4.2 SYSTEM MAINTENANCE
WARNING
!
Hazardous voltage: Before wiring, servicing or cleaning
the heating system, turn off the power and follow your
organization’s lockout and tagout procedure. Failure to do
so could allow others to turn on the power unexpectedly,
resulting in harmful or fatal electrical shock.
Instructions for the following maintenance procedures
are provided to ensure trouble-free operation of your
heating system. Replacement parts must meet or exceed
original part requirements in order to maintain the
compliance level of the original heating system.
NOTE: After maintenance is performed, refer
to SECTION 3.3.1 for system start-up
procedures.
4.2.1 PLUMBING CONNECTIONS
Periodically check plumbing connections for leaks and,
if necessary, tighten connections. A loose connection on
the suction side will cause a loss of flow and cavitation in
the pump. It can also pull air into the heating tank and
cause an element failure.
4.2.2 ELECTRICAL CONNECTIONS
Vibration and thermal cycling may cause terminals
to loosen. After initial first run, disconnect power and
tighten electrical connections (see SECTION 4.3).
Check connections again in a week. Tighten all electrical
connections every three months.
4.2.3 SYSTEM MOUNTING
Vibration may cause mounting bolts to loosen.
Periodically check and tighten all mounting bolts.
4.2.4 MAGNETIC CONTACTORS
Magnetic contactors are used to control motors and
heating elements in Hotstart heating systems. The
contactor coils operate at the system’s nameplate control
voltage. To test for failure, check for continuity across
the coil connections (A1 and A2); an open or direct-short
reading indicates a failed contactor coil.
With power disconnected, verify that the mechanism of
the contactor moves freely and is not stuck in an open
or closed position. With the contacts held closed, check
for unusually high resistance across the main poles.
For contactors with screw terminals, verify that all wire
connections are properly tightened.
Magnetic contactors have finite life cycles, as they
contain moving parts and electrical contacts that will
wear out with use. Replace contactors that develop
functional problems or show obvious external signs
of heat damage. Hotstart recommends that element
contactors be replaced at least every five years as a
preventative maintenance measure.
NOTE: Higher-current systems or systems operating in
high ambient temperatures may require more
frequent contactor replacement.
4.2.5 COOLANT PUMP SEAL
Coolant pump mechanical seals are controlled leakage
devices and are not intended to create a zero leak seal.
Some leaking from the seal is expected during normal
operation. If seal becomes worn, replacement pump
seals are available. To ensure pump seal longevity,
ensure the supply lines do not restrict flow excessively
(see SECTION 2.1.1 and SECTION 2.1.2) and run the