
14 installation & operation manual | dlv heating system
5 MAINTENANCE, REPAIR AND TROUBLESHOOTING
5.1 COOLANT/OIL FAULTS
The coolant fault light will display if:
• The coolant pump motor protection switch is tripped (MPS1).
• The coolant high-limit temperature is exceeded (TCR2).
The oil fault light will display if:
• The oil pump motor protection switch is tripped (MPS2).
• The oil high-limit temperature is exceeded (TCR4).
A failure in the pump motor that causes the motor protection switch (MPS1 or MPS2) to trip will shut
down the respective heating system. A fault signal will be transmitted and the coolant or oil fault light will
illuminate. If this failure occurs, the on/off/prime switch must be switched to off and the operator must
press the MPS reset/on button to reset the fault. (See SECTION 3.2.)
If there is a failure that causes a high temperature to occur, the high-limit temperature controller (TCR2 or
TCR4) will shut down the coolant or oil heating system, including the pump motor. A fault signal will be
transmitted and the coolant or oil fault light will illuminate. To restart the system, the on/off/prime switch
must be switched to off and then back to on to resume operation once the uid temperature drops below
the high-limit preset (See SECTION 3.5.)
NOTE: A high-limit fault can only occur when the respective heating element is energized. A fault in one uid system
will not cause the other uid system to shut down.
For additional troubleshooting, see SECTION 5.5.
5.2 SYSTEM MAINTENANCE
WARNING
!
Hazardous voltage: Before wiring, servicing or cleaning the heating system, turn off the power and follow
your organization’s lockout and tagout procedure. Failure to do so could allow others to turn on the power
unexpectedly, resulting in harmful or fatal electrical shock.
Instructions for the following maintenance procedures are provided to ensure trouble-free operation of your
heating system. Replacement parts must meet or exceed original part requirements in order to maintain
the compliance level of the original heating system.
NOTE: After maintenance is performed, refer to SECTION 4 for system start-up procedures.
5.2.1 PLUMBING CONNECTIONS
Periodically check plumbing connections for leaks and, if necessary, tighten connections. A loose
connection on the suction side will cause a loss of flow and cavitation in the pump. It can also pull air into
the heating tank and cause an element failure.
5.2.2 ELECTRICAL CONNECTIONS
Vibration may cause terminals to loosen. At start-up, tighten electrical connections. Check connections
again in a week. Tighten all electrical connections every three months.