
11
installation & operation manual | oxm/ogm heating system
5.2 SYSTEM MAINTENANCE
WARNING
!
Hazardous voltage: Before wiring, servicing or
cleaning the heating system, turn off the power
and follow your organization’s lockout and tagout
procedure. Failure to do so could allow others to turn
on the power unexpectedly, resulting in harmful or
fatal electrical shock.
Instructions for the following maintenance procedures
are provided to ensure trouble-free operation of your
heating system. Replacement parts must meet or exceed
original part requirements in order to maintain the
compliance level of the original heating system.
NOTE: After maintenance is performed, refer to
SECTION 4 for system start-up procedures.
5.2.1 PLUMBING CONNECTIONS
Periodically check plumbing connections for leaks and,
if necessary, tighten connections. A loose connection on
the suction side will cause a loss of flow and cavitation in
the pump. It can also pull air into the heating tank and
cause an element failure.
5.2.2 ELECTRICAL CONNECTIONS
Vibration may cause terminals to loosen. At start-up,
tighten electrical connections. Check connections again
in a week. Tighten all electrical connections every three
months.
5.2.3 SYSTEM MOUNTING
Vibration may cause mounting bolts to loosen.
Periodically check and tighten all mounting bolts.
5.2.4 MAGNETIC CONTACTORS
Magnetic contactors are used as voltage switching
controls for motors and heating elements in HOTSTART
heating systems. The contactors use 120 volt or 240
volt coils. To test for failure, check for continuity across
the coil connections; an open or direct-short reading
indicates a failed contactor coil.
The contacts on the magnetic contactor should be
inspected periodically for welding, arc erosion and
mechanical wear. If any of these conditions exist, replace
the magnetic contactor. HOTSTART recommends
contactors be replaced every five years.
5.2.5 PUMP SEAL
Pump mechanical seals are controlled leakage devices
and are not intended to create a zero leak seal. Some
leaking from the seal is expected during normal
operation. If seal becomes worn, replacement pump
seals are available for oil pumps. To ensure pump seal
longevity, ensure the supply line does not restrict flow
excessively (see SECTION 2.1.1) and run the heating
system for 20 minutes monthly during offseason periods
(see SECTION 5.4).
NOTE: Instructions to replace the pump seals are
included with replacement seals.
5.2.6 MOTOR LUBRICATION
Motors are installed with initial lubrication. If your motor
has provisions for relubrication, refer to the motor
manufacturer for recommended relubrication schedule
intervals. For recommended lubrication type, refer to the
motor nameplate.
NOTE: New motors installed on heating systems
placed in extended storage for a year or longer
may require relubrication. See SECTION 5.4.
5.2.7 OIL PRESSURE RELIEF VALVE
The oil pump pressure relief valve is internal to the pump
and releases pressure from the discharge side of the
pump to the suction side of the pump. No maintenance
for this part is required.
5.2.8 OIL PRESSURE/TEMPERATURE
GAUGE
The oil pressure/temperature gauge will indicate a
pressure increase when the pump motor is engaged
by pressing the prime button or during normal heater
operation. The gauge will also indicate the current
temperature of the uid. No maintenance for this part is
required.
5.2.9 VOLATILE CORROSION
INHIBITOR (VCI)
A volatile corrosion inhibitor (VCI) is provided with each
control box and should be replaced once a year.
NOTE: Heating systems placed in extended storage
will require that the VCI is replaced at six month
intervals. See SECTION 5.4.