2HBLSDSA36 Surge Protective Device (SPD) INSTALLATION
Hubbell Wiring Devices
1-800-729-3406
www.Hubbell-Wiring.com
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Hubbell for any consequences arising out of the use of this material.
Installation 1. Turn off all power supplying this equipment before working on or inside
equipment.
2. For mounting, see Figure 1.
3. Confirm HBLSDSA36 is rated for your system by comparing voltage
measurements to the Line Voltage (L-L, L-N) on the product label.
4. Install in accordance with Article 285of the National Electric Code.
5. Confirm that the electrical terminals used to attach this device are
identified for these conductors.
6. Twist conductors 1/2 turn or more for every 12 inches of length.
7. Keep conductor length as short as possible with no sharp bends.
8. Ensure a high quality ground is in place.
9. Install cover and/or close door on equipment.
Diagnostic Operation
•LED ON = Normal Operation
•LED OFF = Fault, check phase voltage, breakers (if used) and
connections. If OK, replace unit. (see Figure 2)
Figure 1: Mounting Unit
Figure 2: Diagnostic Operation
Nut
0.5 in. [13 mm] knockout (trade size)
Actual hole size .875 in. [22 mm]
NOTE: The secondary surge arrester must be
installed in an accessible location (not within walls).
ON = OK OFF= Fault
Figure 3: Wiring Diagrams
Black
White
Black
Black
Black
Black
Black
White White
Single-phase
Three-wire 120/240 Vac Two Surge Arresters on 120/208Y Vac
Three-phase Four-wire Service
Figure 4: Dimensions
2.250
[57]
2.250
[57]
2.685
[68]
1.935
[49]
Dimensions: in.
[mm]
Table 1: General Specifications 12
1Suitable for use on a circuit capable of delivering not more than 22 kA rms symmetrical
Amperes.
2Contains no serviceable parts.
Product Catalog No. HBLSDSA36
Voltage 120/240 V
VPR 700 V L-N, 1200 L-L
In10 kA
MCOV 150 V L-N, 300 V L-L
Max. Surge Current 36 kA/Phase
Housing Rating Type 4X
Short Circuit Current Rating 22 kA
Product Weight .525 lb
Connection Method Parallel, 14 AWG Wire
Thermal Fusing Yes
Operating Temperature -40 to +160 °F (-40 to +70 °C)
Operating Frequency 50/60 Hz
Diagnostics Green Status LED
Product Standards ANSI/IEEE C62.11, CSA 233.1-87
CULUS Listed Type 1 SPD