Hunter Field Server 3000 User manual

Field Server
Automation Gateway
OWNER’S MANUAL
FS3000 and FS1000
hunterindustries.com |Built on Innovation®

2
eldserver operating manual
CONTENTS
About the Field Servers............................... 3
Certication ................................................... 3
Supplied Equipment ...................................... 3
Equipment Setup ......................................... 3
Mounting....................................................... 3
Physical Dimensions ...................................... 4
Installation ................................................... 5
DIP Switch Settings ....................................... 5
Bias Resistors ................................................ 5
Termination Resistor...................................... 6
Connecting the R1 and R2 Ports..................... 6
Wiring ............................................................ 6
Supported RS-485 Baud Rates
by Protocol..................................................... 7
10/100 Ethernet Connection Port .................. 7
Powering up the Gateway ........................... 7
Connecting the PC to the Gateway ............. 8
Connecting to the Gateway via Ethernet ....... 8
Changing the Subnet of the Connected PC.... 8
Setting Up Web Server Security ................. 9
Logging In to the Field Server........................ 9
Selecting the Security Mode.........................10
HTTPS with Own Trusted TLS Certicate ......10
HTTPS with Default Untrusted
Self-Signed TLS Certicate or HTTP
with Built-in Payload Encryption...................10
Setting Up the Network...............................11
Using FS-GUI to Input Network Settings .......11
Routing Settings............................................11
Eth1 and Eth2
Network Settings – LAN Mode...................... 12
Ethernet 2 Network Settings – WAN Mode.....12
Conguring the Field Server ...................... 13
Retrieving the Sample Conguration File ..... 13
Changing the Conguration File to Meet
the Application ............................................. 13
Loading the Updated Conguration File ....... 13
Using FS-GUI to Input Load a
Conguration File ......................................... 13
Retrieving the Conguration File for
Modication or Backup.................................14
Testing and Commissioning the Field Server..14
Accessing the Field Server Manager............. 14
Troubleshooting.......................................... 15
Lost or Incorrect IP Address.......................... 15
Viewing Diagnostic Information.................... 15
Checking Wiring and Settings....................... 15
Taking a Field Server Diagnostic Capture......16
LED Functions............................................... 17
Factory Reset Instructions............................ 17
Internet Browser Soware Support.............. 17
Additional Information............................... 17
Changing the Web Server Security
Settings Aer Initial Setup............................ 17
Changing the Security Mode ........................18
Editing the Certicate Loaded onto
the Field Server.............................................18
Changing the User Management Settings ..... 18
Creating Users .............................................. 19
Editing Users .............................................19
Deleting Users ...........................................19
Changing the Field Server Password.........20
Specications............................................20
Warnings ..................................................20
Complying with EN IEC 62368-1................20
Limited 2-Year Warranty...........................21

3
eldserver operating manual
ABOUT THE FIELD SERVERS
The Field Server is a high performance,
cost eective building and industrial
automation multi-protocol gateway
providing protocol translation between
serial/Ethernet devices and networks.
NOTE: For troubleshooting assistance,
refer to the Troubleshooting section or
any of the troubleshooting appendices
in the related driver supplements. Check
the Hunter Industries website for tech-
nical
support resources and documentation
that may be of assistance.
The Field Server is cloud-ready and
connects with Hunter Industries’s Grid.
See the section on Accessing the Field
Server Manager for more information.
Certication
BTL Mark – BACnet™
Testing Laboratory
The BTL Mark on the Field Server is a
symbol indicating that a product has
passed a series of rigorous tests
conducted by an independent
laboratory. This veries that the
product correctly implements the
BACnet features claimed in the listing.
The mark is a symbol of a high-quality
BACnet product.
Go to www.BACnetInternational.net
for more information about the BACnet
Testing Laboratory. You can view the
BACnet Protocol Implementation
Conformance Statement (PICS) at
bacnet.org/conformance-pics/. BACnet
is a registered trademark of ASHRAE.
Supplied Equipment
Field Server Gateway
• Preloaded with two selected drivers
and a sample conguration le.
EQUIPMENT SETUP
Mounting
The gateway can be mounted using the
DIN rail mounting bracket on the back of
the unit.
DIN Rail
Bracket

4
eldserver operating manual
Physical Dimensions
3.94"
(100 cm)
1.10"
(28 cm)
2.76"
(70 cm)
3.07"
(78 cm)
eldserver3000
Input: 24VAC, 50/60Hz or 8-30VDC 0.3A
Default Password: Password
Shipped IP 1: xxx xxx xxx xxx
ETH 1 MAC: xx xx xx xx xx xx
Shipped IP 2: xxx xxx xxx xxx
ETH 2MAC: xx xx xx xx xx xx
SO#: Sale Order
Product of China
FS-N64-XXXX
eldserver
Power Port
R2 Serial Port R1 Serial Port
R1
TX+
RX-
+
-
GND
GND
R1
R2
RX2TX2
OFF ON
TERM
BIAS-
BIAS+
TERM
BIAS-
BIAS+
485/232
OFF ON
R2
Micro SD
9-30 VDC
24 VAC
FG N L
NEC Class 2 Wiring
RX2
ETH 2 ETH 1
WAN LAN
TX2
BTN
$$ ERR PWR
E467736
REF

5
eldserver operating manual
INSTALLATION
DIP Switch Settings
Bias Resistors
To enable Bias Resistors, move both the
BIAS- and BIAS+ dip switches to the
right in the orientation shown above.
The bias resistors are used to keep the
RS-485 bus to a known state, when
there is no transmission on the line (bus
is idling), to help prevent false bits of
data from being detected. The bias
resistors typically pull one line high and
the other low far away from the
decision point of the logic.
The bias resistor is 510 ohms, which is in
line with the BACnet spec. It should only
be enabled at one point on the bus (for
example, on the eld port were there
are very weak bias resistors of 100k).
Since there are no jumpers, many
Field Servers can be put on the network
without running into the bias resistor
limit, which is < 500 ohms.
NOTE: See ni.com/support/serial/
resinfo.htm for additional information.
NOTE: The R1 and R2 DIP switches apply
settings to the respective serial port.
NOTE: If the gateway is already powered
on, DIP switch settings will not take
eect unless the unit is power cycled.
R1 Bias Resistor DIP
switches (2 and 3)
R2 Bias Resistor DIP
switches (2 and 3)

6
eldserver operating manual
Connect to the 3-pin connector(s) as
shown below.
Wiring
NOTE: The RS-485/RS-232 is part of the
RS-485/RS-232 interface and must be
connected to the corresponding terminal
on the BMS. If the cable is shielded, the
shield must be connected only at one
end and to earth ground. This will help
suppress the electromagnetic eld
interference. (Connecting the shield at
both ends will likely produce current
loops, which could produce noise or
interference that the shield was
intended to block).
Termination Resistor
If the gateway is the last device on the
serial trunk, then the End-Of-Line
Termination Switch needs to be enabled.
To enable the Termination Resistor,
move the TERM dip switch to the right in
the orientation shown above.
Termination resistor is also used to
reduce noise. It pulls the two lines of an
idle bus together. However, the resistor
would override the eect of any bias
resistors if connected.
NOTE: The R1 and R2 DIP switches apply
settings to the respective serial port.
NOTE: If the gateway is already
powered on, DIP switch settings will
not take eect unless the unit is
power cycled.
Connecting the R1 & R2 Ports
For the R1 port only: Switch between
RS-485 and RS-232 by moving the
number 4 DIP switch le for RS-485
and right for RS-232 (see images in
DIP Switch Setting section).
The R2 port is RS-485.
R1 Bias Resistor DIP
switches (2 and 3)
R2 Bias Resistor DIP
switches (2 and 3)
+ GND
TX+ RX GND
RS-485 RS-232
BMS RS-485
Wiring
Gateway Pin
Assignment
BMS RS-232
Wiring
Gateway Pin
Assignment
RS-485+ TX+ RS-232- TX+
RS-485- RX- RS-232+ RX-
GND GND GND GND

7
eldserver operating manual
NOTE: The Default IP Address of the
gateway is 192.168.2.101, and the Subnet
Mask is 255.255.255.0.
NOTE: The ETH2 port can be set to WAN
mode to limit Ethernet trac. See the
WAN Mode Settings for ETH2 section
for details.
NOTE: ETH1 and ETH2 must be
congured with IP Addresses on
dierent IP subnets.
POWERING UP THE GATEWAY
Check power requirements in the
table below:
NOTE: These values are “nominal” and
a safety margin should be added to the
power supply of the host system. A
safety margin of 25% is recommended.
Apply power to the Field Server as
shown on next page. Ensure that the
power supply used complies with the
specications provided in the
Specications section.
• The gateway accepts 9 to 30 VDC or
24 VAC on pins L+ and N-.
- Supports both Full-Wave and
Half-Wave AC
• Frame GND should be connected to
ensure personnel safety and to limit
material damages due to electrical
faults. Ground planes are susceptible
to transient events that cause sudden
surges in current. The frame ground
connection provides a safe and
eective path to divert the excess
current from the equipment to
earth ground.
Supported RS-485 Baud Rates
by Protocol
The supported baud rates for either port
is based on the protocol of the connected
devices. The following baud rates are
supported for Modbus RTU:
2400, 4800, 9600, 19200, 38400,
57600, 76800, 115200
The following baud rates are supported
for BACnet MS/TP: 9600, 19200,
38400, 76800, 115200
10/100 Ethernet Connection Port
NOTE: Do not use shielded Ethernet
cables.
The Ethernet port is used both for
BACnet/IP communications and for
conguring the gateway via the Web
App. To connect the gateway, either
connect the PC to the router’s Ethernet
port or connect the router and PC to an
Ethernet switch. Use Cat-5 cables for
the connection.
Ethernet Port 1 ETH1
Ethernet Port 2 ETH2
Power Requirement for Field Server External Gateway
Current Draw Type
Field Server Family 12VDC 24vdc/ac
FS-QS-3X109-XXXX (typical) 250mA 125mA

8
eldserver operating manual
Changing the Subnet of the
Connected PC
The default IP address for the
Field Server is 192.168.2.101, and the
Subnet Mask is 255.255.255.0. If the
PC and Field Server are on dierent IP
networks, assign a static IP address to
the PC on the 192.168.2.xxx network.
For Windows 10:
• Find the search eld in the local
computer’s taskbar (usually to the
right of the Windows icon) and type
in Control Panel.
• Click Control Panel, Network and
Internet, then Network and Sharing
Center in that order.
• Click Change Adapter Settings on the
le side of the window.
• Right-click on Local Area Connection,
and select Properties from the
dropdown menu.
• Highlight and then click the
Properties button.
• Select and enter a static IP address on
the same subnet. For example:
swx
• Click the Okay button to close the
Internet Protocol window. Next, select
the Close button to close the Ethernet
Properties window.
NOTE: Floating AC power supplies
are supported.
CONNECTING THE PC TO
THE GATEWAY
Connecting to the Gateway via Ethernet
Connect a Cat-5 Ethernet cable (straight
through or cross-over) between the local
PC and Field Server ETH1 (LAN port).
Power to
Gateway
Gateway
Pin Label
Pin
Assignment
Power in (+) L + V +
Power In (-) N- V -
Frame GND FG Frame GND
Ethernet Port

9
eldserver operating manual
• Additional text will expand below the
warning. Click the underlined text
to go to the IP address. In the
example below, this text is “Proceed
to 10.40.50.94 (unsafe).”
• When the login screen appears, put in
the Username (default is “admin”) and
the Password (found on the label of
the Field Server).
NOTE: There is also a QR code in the
top right corner of the Field Server label
that shows the default unique password
when scanned.
NOTE: A user has ve attempts to log
in. Aerward, there will be a 10-minute
lockout. There is no timeout on the Field
Server to enter a password.
NOTE: To create individual user logins,
go to the Change User Management
Settings section.
SETTING UP WEB SERVER
SECURITY
Logging In to the Field Server
The rst time the Field Server GUI is
opened in a browser, the IP address for
the gateway will appear as “untrusted.”
This will cause the following pop-up
windows to appear.
• When the Web Server Security
Uncongured window appears, read
the text and choose whether to move
forward with HTTPS or HTTP.
• When the warning that “Your
connection is not private” appears,
click the advanced button on the
bottom le corner of the screen.

10
eldserver operating manual
• Copy and paste the Certicate and
Private Key text into their respective
elds. If the Private Key is encrypted,
type in the associated Passphrase.
• Click Save.
• A “Redirecting” message will appear.
Aer a short time, the Field Server
GUI will open.
HTTPS with Default Untrusted Self-
Signed TLS Certicate or HTTP with
Built-in Payload Encryption
• Select one of these options and click
the Save button.
• A “Redirecting” message will appear.
Aer a short time, the Field Server
GUI will open.
Selecting the Security Mode
On the rst login attempt to the Field
Server, the following screen will appear.
It allows the user to select the mode that
the Field Server should use.
NOTE: Cookies are used for
authentication.
NOTE: To change the web server
security mode aer initial setup, go to
the Change Web Server Security
Settings Aer Initial Setup section.
The sections that follow include
instructions for assigning the dierent
security modes.
HTTPS with Own Trusted
TLS Certicate
This is the recommended selection and
the most secure. Please contact your IT
Department to nd out if you can obtain
a TLS certicate from your company
before proceeding with the Own Trusted
TLS Certicate option.
• Once this option is selected, the
Certicate, Private Key and Private
Key Passphrase elds will appear
under the mode selection.

11
eldserver operating manual
•
•
•
• Click on the arrow next to Setup to
expand the tree.
• Click on Network Settings.
Routing Settings
The Routing settings make it possible
to set up the IP routing rules for the
Field Server’s internet and network
connections.
NOTE: The default connection is ETH1.
• Select the default connection in the
rst row as either ETH 1 or ETH 2.
• Click the Add Rule button to add a
new row and set a new Destination
Network, Netmask, and Gateway IP
Address as needed.
SETTING UP THE NETWORK
Once the web server setup is complete,
the Field Server GUI (FS-GUI) landing
page will appear.
NOTE: The Field Server Manager tab
allows users to connect
to the Grid, Hunter Industries’s device
cloud solution for IIoT. The Field Server
Manager enables secure remote
connection to eld devices through a
Field Server and its local applications
for conguration, management, and
maintenance. For more information
about the Field Server Manager, refer
to the MSA Grid - Field Server Manager
Start-up Guide.
Using FS-GUI to Input
Network Settings
To navigate from the FS-GUI page to
the Network Settings page, follow the
instructions below:
• Find the Navigation tree across the
le side of the screen.
• Click the arrow next to the Field
Server title/CN number to expand
the tree.

12
eldserver operating manual
Ethernet 2 Network Settings –
WAN Mode
• Click the blue WAN box to change the
ETH 2 port to WAN mode.
- This grants access only to allowed
incoming trac on the ETH 2 port.
It does allow a connection to the
internet via port 80 and 443.
Scroll below the network settings to get
to the rewall options with rules that
allow specic incoming trac (through
setting rules) and outgoing options.
• Set the Priority for each connection
(1 to 255 with 1 as the highest priority
and 255 as the lowest).
• Click the Save button to activate the
new settings.
Ethernet 1 and Ethernet 2 Network
Settings – LAN Mode
• Check that the Mode is set to LAN.
If not, click LAN to change the ETH 2
port to LAN mode.
• Enable DHCP to automatically assign
IP settings or modify the IP settings
manually as needed, via these
elds: IP Address, Netmask, Gateway,
and Domain Name Server1/2.
NOTE: If connected to a router, set the
gateway to the same IP address as
the router.
• Click Save to record and activate the
new IP address.
• Connect the Field Server to the local
network or router.
NOTE: If the webpage was open in a
browser, the browser will need to be
pointed to the new IP address of the
Field Server before the webpage will be
accessible again.

13
eldserver operating manual
Changing the Conguration File to
Meet the Application
Refer to the Field Server Conguration
Manual in conjunction with the driver
supplements for information on
conguring the Field Server.
Loading the Updated Conguration File
Using FS-GUI to Load a
Conguration File
• In the main menu of the FS-GUI
screen, click Setup, then File
Transfer, and nally Update.
• Browse and select the cong.csv le,
open, then click Submit.
NOTE: See the options below for setting
rewall rules.
• Add 1023 to the Port Range eld to
allow Field Server Toolbox access.
• Add 47808 to the Port Range eld for
BACnet access.
• Add 80 and 443 to the Port Range
eld for web browser access.
• Use an asterisk (*) as a wild card for
the IP address.
CONFIGURING THE
FIELD SERVER
Retrieving the Sample
Conguration File
The conguration of the Field Server is
provided to the Field Server’s operating
system via a comma-delimited le called
cong.csv.
If a custom conguration was ordered,
the Field Server will be programmed
with the relevant device registers in the
cong.csv le for the initial start-up. If
not, the product will ship with a
sample cong.csv that shows an
example of the drivers ordered.
• In the main menu of the FS-GUI
screen, go to Setup, then File
Transfer, and nally Retrieve.
• Click on cong.csv, and open or
save the le.

14
eldserver operating manual
Testing and Commission the Field Server
• Connect the eld server to the
third party device(s), and test the
application.
• From the landing page of the FS-GUI
click on View in the navigation tree,
then Connections to see the number
of messages on each protocol.
NOTE: For troubleshooting assistance,
refer to the Troubleshooting section or
any of the troubleshooting appendices
in the related driver supplements and
conguration manual. Hunter Industries
also oers a technical support section
on the Hunter Industries website, which
contains
a signicant number helpful resources
and documentation.
Accessing the Field Server Manager
NOTE: The Field Server Manager tab
allows users to connect
to the Grid, Hunter Industries’s device
cloud solution for IIoT. The Field Server
Manager enables secure remote
connection to eld devices through a
eld server and its local applications
for conguration, management, and
maintenance. For more information
about the Field Server Manager, refer
to the MSA Grid - Field Server Manager
Startup Guide.
• Once the download is complete, a
message bar will appear conrming
that the conguration was updated
successfully.
• Click the System Restart Button to put
the new le into operation.
NOTE: It’s possible to do multiple
downloads to the QuickServer before
resetting it.
Retrieving the Conguration File for
Modication or Backup
To get a copy of the conguration le for
modifying or backing up a conguration
on a local computer, do the following:
• In the main menu of the FS-GUI
screen, click Setup, then
File Transfer.
• Click the cong.csv link under the
Retrieve heading in the middle
section of the screen.
- The le will automatically
download to the web browser’s
default download location.
• Edit or store the le as desired.
NOTE: Before using any backup
conguration le to reset the
conguration settings, check that
the backup le is not an old version.

15
eldserver operating manual
Viewing Diagnostic Information
• Type the IP address of the Field Server
into the web browser, or use the
Field Server Toolbox to connect to the
eld server.
• Click on the Diagnostics and
Debugging button, then click on
View, and then on Connections.
• If there are any errors showing on the
Connection page, refer to Checking
Wiring and Settings section for the
relevant wiring and settings.
Checking Wiring and Settings
No COMS on the Serial side. If the
Tx/Rx LEDs are not ashing rapidly,
this signies a COM issue. To x this
problem, check the following:
TROUBLESHOOTING
Lost or Incorrect IP Address
• Ensure that the Field Server Toolbox is
loaded onto the local PC. Otherwise,
download the Field Server-Toolbox.zip
le via the Hunter Industries website.
• Extract the executable le and
complete the installation.
• Connect a standard Cat-5 Ethernet
cable between the user’s PC and
Field Server.
• Double click on the FS Toolbox utility
and click Discover Now on the
splash page.
• Check for the IP address of the
desired gateway.
Ethernet Port

16
eldserver operating manual
• Go to Full Diagnostic, and select the
capture period.
• Click the Start button under the
Full Diagnostic heading to start
the capture.
- When the capture is complete, a
Download button will appear next
to the Start button.
• Click Download for the capture to be
downloaded to the local PC.
• Email the diagnostic zip le to
Technical Support (smc-support.
emea@msasafety.com).
NOTE: Diagnostic captures of BACnet
MS/TP communication are output in a
.PCAP le extension, which is
compatible with Wireshark.
• Check the LEDs on the Field Server
(LED Functions section).
• Check the baud rate, parity, data bits,
and stop bits.
• Check the device address.
• Verify the wiring.
• Verify that the device is connected to
the same subnet as the Field Server.
Field COM Problems
• Visual observations of LEDs on the
Field Server (LED Functions section).
• Verify wiring.
• Verify IP Address setting.
NOTE: If the problem still exists, a
diagnostic capture needs to be taken
and sent to Technical Support. See
Taking a Field Server Diagnostic Capture
section.
Taking a Field Server
Diagnostic Capture
When there is a problem on-site that
cannot easily be resolved, perform a
Diagnostic Capture before contacting
support. Once the Diagnostic Capture is
complete, email it to technical support.
The Diagnostic Capture will accelerate
diagnosis of the problem.
• Access the Field Server Diagnostics
page via one of the following
methods:
- Open the Field Server GUI page,
and click on Diagnostics in the
Navigation panel.
- Open the Field Server Toolbox
soware, and click the diagnose
icon of the desired device.

17
eldserver operating manual
NOTE: Internet Explorer is no longer
supported as recommended by
Microso.
NOTE: Computer and network rewalls
must be opened for Port 80 to allow the
Field Server GUI to function.
ADDITIONAL INFORMATION
Changing Web Server Security Settings
Aer Initial Setup
NOTE: Any changes will require a
Field Server reboot to take eect.
• Navigate from the QuickServer
landing page to the Field Server GUI
by clicking the blue Diagnostics text
on the bottom of the screen.
• The QuickServer landing page is
the Field Server GUI.
• Click Setup in the Navigation panel.
LED Functions
Factory Reset Instructions
For instructions on how to reset a
Field Server back to its factory-released
state, see ENOTE Field Server Next
Gen Recovery.
Internet Browser Soware Support
The following web browsers are
supported:
• Chrome Rev. 57 and higher
• Firefox Rev. 35 and higher
• Microso Edge Rev. 41 and higher
• Safari Rev. 3 and higher
TAG DESCRIPTION
SS The SS LED will ash once a second to indicate that the
bridge is in operation.
ERR The SYS ERR LED will turn solid, indicating a system error.
If this occurs, immediately report the related “system
error” shown in the error screen of the Field Server GUI to
Technical Support for evaluation.
PWR The power light should always be a steady green when the
unit is powered on.
RX The RX LED will ash when a message is received on the
serial port on the 3-pin connector. If the serial port is not
used, this LED is non-operational. RX1 applies to the R1
connection while RX2 applies to the R2 connection.
TX The TX LED will ash when a message is sent on the serial
port on the 3-pin connector. If the serial port is not used,
this LED is non-operational. TX1 applies to the R1
connection while TX2 applies to the R2 connection.
Diagnostic LEDs

18
eldserver operating manual
Changing User Management Settings
• From the Field Server GUI page, click
Setup in the Navigation panel.
• Click User Management in the
navigation panel.
NOTE: If the passwords are lost, the
unit can be reset to factory settings to
reinstate the default unique password
on the label. For recovery instructions,
see the Field Server Next Gen
Recovery document. If the default
unique password is lost, then the unit
must be mailed back to the factory.
NOTE: Any changes will require a
Field Server reboot to take eect.
• Check that the Users tab is selected.
User Types:
Admin: Can modify and view any
settings on the Field Server.
Operator: Can modify and view any data
in the Field Server array(s).
Viewer: Can only view settings/
readings on the Field Server.
• SSL/TLS (Secure Sockets Layer/
Transport Layer Security) is a security
technology for establishing an
encrypted connection between a
server and a client. This allows the
secure transfer of data across
untrusted networks.
Changing Security Mode
• Click Security in the Navigation panel.
• Click the Mode desired.
- If HTTPS with Own Trusted TLS
Certicate is selected, follow
instructions in the HTTPS with Own
Trusted TLS Certicate section.
• Click the Save button.
Editing the Certicate Loaded onto the
Field Server
NOTE: A loaded certicate will only be
available if the security mode was
previously setup as HTTPS with Own
Trusted TLS Certicate.
• Click Security in the Navigation panel.
• Click the Edit Certicate button to
open the certicate and key elds.
• Edit the loaded certicate or key text
as needed.
• Click Save.

19
eldserver operating manual
• Once the User Edit window opens,
change the User Security Group and
Password as needed.
•
• Click Conrm.
• Once the Success message appears,
click OK.
Deleting Users
• Click the trash can icon next to the
desired user to delete the entry.
• When the warning message appears,
click Conrm.
Creating Users
• Click the Create User button.
• Enter the new User elds: Name,
Security Group, and Password.
- User details are hashed and salted.
NOTE: The password must meet the
minimum complexity requirements.
An algorithm automatically checks the
password entered and notes the level
of strength on the top right of the
Password text eld.
• Click the Create button.
• Once the Success message appears,
click OK.
Editing Users
• Click the pencil icon next to the
desired user to open the User
Edit window.

20
eldserver operating manual
NOTE: Specications subject to change
without notice.
Warnings
FCC Class B
NOTE: This equipment has been tested
and found to comply with the limits for
a Class B digital device, pursuant to part
15 of the FCC Rules. These limits are
designed to provide reasonable
protection against harmful interference
in a residential installation. This
equipment generates, uses and can
radiate radio frequency energy and, if
not installed and used in accordance
with the instructions, may cause
harmful interference to radio
communications. However, there is no
guarantee that interference will not
occur in a particular installation. If this
equipment does cause harmful
interference to radio or television
reception, which can be determined by
turning the equipment o and on, the
user is encouraged to try to correct the
interference by one or more of the
following measures:
• Reorient or relocate the receiving
antenna.
• Increase the separation between the
equipment and receiver.
• Connect the equipment into an
outlet on a circuit dierent from that
to which the receiver is connected.
• Consult the dealer or an experienced
radio/TV technician for help.
Compliance with EN IEC 62368-1
For EN IEC compliance, the following
instructions must be met when
operating the Field Server.
Changing Field Server Password
• Click the Password tab.
• Change the general login password for
the Field Server as needed.
NOTE: The password must meet the
minimum complexity requirements.
An algorithm automatically checks the
password entered and notes the level
of strength on the top right of the
Password text eld.
Specications
E467736
FS-QS-3X10-F
Electrical
Connections
One 3-pin Phoenix connector with:
RS-485/RS-232 (Tx+ / Rx- / gnd)
One 3-pin Phoenix connector with: RS-485
(+ / - / gnd)
One 3-pin Phoenix connector with: Power
port (+ / - / Frame-gnd)
Two Ethernet 10/100 BaseT port
Power
Requirements
Input Voltage: 9 to 30 VDC or 24 VAC
Current draw: 24 VAC 0.125 A 9 to 30 VDC
0.25 A @12 VDC
Max Power: 3 W
Approvals CE and FCC compliant, UL 62368-1,
WEEE compliant ISED CAN ICES-003(B)/
NBM-003(B), RoHS compliant, REACH
compliant, UKCA compliant
Dimensions 4" x 1.1" x 2.7" (10.2 cm x 2.8 cm x 6.8 cm)
Weight 0.4 lb (0.2 kg)
Operating
Temperature
-4°F to 158°F (-20°C to 70°C)
Humidity 10 to 95% RH non-condensing