4. OPERATION – PUSH BUTTON UNIT QZC-C
To operate the unit, manually press the central red button and release.
Provided the ambient temperature is BELOW the unit’s threshold temperature
the unit will perform a soft start, increasing the gradually power over a timescale
of 2-3 seconds.
The unit will then stay on for a number of minutes before switching off.
To protect against excessive operation that could damage the unit, only two on/off
cycles are permitted per minute.
5. OPERATION – PIR UNIT QZC-D
If motion is detected and the ambient temperature is BELOW the unit’s
threshold set point the unit will perform a soft start, increasing the power
gradually over a timescale of 2-3 seconds.
It will then stay on for a number of minutes before switching off.
If motion is detected whilst the unit is already operating the timer will be reset.
An externally visible red LED indicates when motion is detected.
6. PARAMETER ADJUSTMENT
Both models include two parameter adjustments
- Run Time
- Threshold temperature
MAINS POWER MUST BE DISCONNECTED FROM THE UNIT
BEFORE ATTEMPTING ADJUSTMENT.
To adjust, rst open cover.
On the right hand side of the PCB are two small potentiometers that can be
adjusted with a small at bladed screwdriver (see Figure 2).
The top potentiometer controls the run time in minutes.
The lower potentiometer controls the threshold temperature in degrees C.
The unit will not operate if the ambient temperature is above the threshold
temperature. To effectively disable the temperature control set it to the highest
setting.