Hyco QZC Series Supplement

QZC Series
Infrared Electric Soft Start
Quartz Heating Controllers
Models QZC-C and QZC-D
Installation and Operating Instructions Manual
Version 1.0 October 2011

HYCO QZC SERIES INFRARED ELECTRIC SOFT START
QUARTZ HEATING CONTROLLERS
QZC-C Push Button operation
QZC-D PIR remote operation
1. INTRODUCTION
Thank you for purchasing a Hyco QZC Series controller. These products are
designed to provide:
- Energy efcient control of quartz heaters by providing time (and in some cases
temperature) control
- A reduction in the high inrush current that occurs when the lamps are rst
switched on from cold.
To install and use this equipment safely please read this manual carefully. When
the unit has been installed these instructions should be left with the user of the
equipment.
Do not proceed with installation if there is any sign of damage to the product.
CAUTION
READ THESE INSTRUCTIONS BEFORE ATTEMPTING
INSTALLATION.
INSTALLATION MUST BE UNDERTAKEN BY A COMPETENT
INSTALLER IN ACCORDANCE WITH THE LATEST EDITION OF
THE IEE WIRING REGULATIONS.
THIS UNIT CONTAINS LIVE PARTS.
ONLY QUALIFIED PERSONNEL SHOULD BE ALLOWED TO
ADJUST AND MAINTAIN THE UNIT. UNIT MUST BE
DISCONNECTED BEFORE ADJUSTMENT OR MAINTENANCE.
1

2
A MEANS FOR DISCONNECTING THE UNIT MUST BE
INCORPORATED INTO THE FIXED WIRING.
THE UNIT MUST NOT BE USED BY CHILDREN OR BY
PERSONS WITH A REDUCED PHYSICAL, SENSORY OR MENTAL
CAPABILITY OR LACK OF EXPERIENCE AND KNOWLEDGE.
THERE ARE NO USER SERVICEABLE PARTS INSIDE THE UNIT.
2. SPECIFICATIONS
PARAMETER VALUE
Supply Voltage 230VAC, 50Hz
Switching Capacity 6kW Max, 26A
Lamp On-Time 1 to 99 minutes
Current Consumption (control circuit) 2W (10mA max )
Terminals 6.00mm2
Operating Temperature -20 to +60°C
Protection Rating IP65
Gland Diameter 20mm
Enclosure Dimensions (W x L x H) 100mm x 100mm x 60mm
Weight 500 grams

3
3. INSTALLATION AND ELECTRICAL CONNECTION
The following section is relevant to the push button model (QZC-C) and
PIR model (QZC-D).
The unit should be positioned with the cable glands facing down and securely
xed via the four mounting holes (see Figure 1).
THE UNIT MUST BE SITED AWAY FROM DIRECT RADIATION
FROM THE HEATER AND IDEALLY OUT OF DIRECT SUNLIGHT.
Remove cover using four screws.
Connect supply as to terminals, noting the supply is the incoming supply is to the
left and the load (heater) is connected to the right.
Screw down gable glands and verify cables are securely clamped.
A MEANS FOR DISCONNECTING THE UNIT MUST BE
INCORPORATED INTO THE FIXED WIRING.
THE UNIT IS CAPABLE OF SWITCHING UP TO 6KW. SUITABLE
CABLE MUST BE USED DEPENDENT ON THE INSTALLATION.
THE CABLE GLANDS SUPPLIED (M20) MAY NOT BE SUITABLE
FOR VERY SMALL DIAMETER CABLES. IF NECESSARY THEY
MUST BE REPLACED BY SUITABLE GLANDS WITH
APPROPRIATE IP RATING.
DO NOT EXCEED POWER RATING (MAX 6kW).

4
IMPORTANT!
Drilling of any holes through the
enclosure will immediately
invalidate the warranty of the unit.
The unit MUST be orientated with
the cable glands facing down.
Figure 1
THIS ILLUSTRATION IS NOT FULL SCALE AND SHOULD NOT
BE USED AS A GUIDE FOR MOUNTING OR INSTALLATION.
USE THE MEASUREMENTS PROVIDED ABOVE FOR ACCURATE
INSTALLATION.
113.5 mm
113.5 mm
4.5 mm

5
4. OPERATION – PUSH BUTTON UNIT QZC-C
To operate the unit, manually press the central red button and release.
Provided the ambient temperature is BELOW the unit’s threshold temperature
the unit will perform a soft start, increasing the gradually power over a timescale
of 2-3 seconds.
The unit will then stay on for a number of minutes before switching off.
To protect against excessive operation that could damage the unit, only two on/off
cycles are permitted per minute.
5. OPERATION – PIR UNIT QZC-D
If motion is detected and the ambient temperature is BELOW the unit’s
threshold set point the unit will perform a soft start, increasing the power
gradually over a timescale of 2-3 seconds.
It will then stay on for a number of minutes before switching off.
If motion is detected whilst the unit is already operating the timer will be reset.
An externally visible red LED indicates when motion is detected.
6. PARAMETER ADJUSTMENT
Both models include two parameter adjustments
- Run Time
- Threshold temperature
MAINS POWER MUST BE DISCONNECTED FROM THE UNIT
BEFORE ATTEMPTING ADJUSTMENT.
To adjust, rst open cover.
On the right hand side of the PCB are two small potentiometers that can be
adjusted with a small at bladed screwdriver (see Figure 2).
The top potentiometer controls the run time in minutes.
The lower potentiometer controls the threshold temperature in degrees C.
The unit will not operate if the ambient temperature is above the threshold
temperature. To effectively disable the temperature control set it to the highest
setting.

6
ON DVP
31 2 4
E N LL N E
0
4
8
12 16
20
24
Max
1
2
5
10 20
30
40
50
Temp
Time
Figure 2
Temperature
Adjustment
LOADMAINS
Timer
Adjustment

Hyco Manufacturing Ltd
Unit 2
Normandy Court
Express Way
Castleford
WF10 5NR
Tel: 01924 225215 Fax: 01924 225 210
Web: www.hyco.co.uk
E-mail: sales@hyco.co.uk
7
7. GUARANTEE AND SERVICE POLICY
This product is guaranteed against faulty materials and manufacture for a period
of one year from the date of purchase. Hyco will in its sole discretion repair,
replace or refund any faulty unit. The results of incorrect installation are excluded.
Consequential losses such as damage to ttings or labour charges are excluded
from this guarantee.