HYDAC FILTER SYSTEMS LVU-CD-10 Manual

LVU-CD-10
LowViscosity Unit
CoaleserDiesel
with control type: Standard or Premium
Operating and Maintenance Instructions
English (translation of original instructions)
(Valid ≥Series no. 0002S03302K0000010)
Document No.: 3993633a

Imprint
LVU-CD-10 en(us) Page 2 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Imprint
Publisher and responsible for the content:
HYDAC FILTER SYSTEMS GMBH
Postfach 1251
66273 Sulzbach / Saarland
Germany
Telephone: +49 (0) 6897 509 01
Fax: +49 (0) 6897 509 9046
Homepage: www.hydac.com
Court of Registration: Saarbrücken, HRB 17216
Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang
Haering
Documentation Representative
Mr. Günter Harge
c/o HYDAC International GmbH, Industriegebiet, 66280 Sulzbach / Saar
Telephone: +49 (0) 6897 509 1511
Fax: +49 (0) 6897 509 1394
© HYDAC FILTER SYSTEMS GMBH
All rights reserved. No part of this work may be reproduced in any form (print,
photocopy or by other means) or processed, duplicated or distributed using
electronic systems without the written consent of the publisher.
These documents have been created and inspected with the greatest care.
However, errors cannot be ruled out completely.

Contents
LVU-CD-10 en(us) Page 3 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Contents
Imprint............................................................................................................2
Documentation Representative ...................................................................2
Contents ........................................................................................................3
Preface...........................................................................................................6
Technical Support........................................................................................6
Modifications to the Product ........................................................................6
Warranty ......................................................................................................6
Using the documentation .............................................................................7
Safety Information ........................................................................................8
Hazard symbols...........................................................................................8
Signal words and their meaning in the safety information and
instructions ................................................................................................10
Structure of the safety information and instructions...................................10
Proper/Designated Use .............................................................................11
Improper Use or Use Deviating from Intended Use ...................................12
Qualifications of personnel / target group ..................................................13
Wear suitable clothing ...............................................................................14
Observe regulatory information .................................................................14
Stoppage in an emergency (EMERGENCY STOP)...................................14
Unpacking the unit......................................................................................14
Transporting the unit..................................................................................15
Carry by hand ............................................................................................15
Transporting with the crane .......................................................................16
Storing the unit ...........................................................................................17
Decoding the model code label .................................................................18
Checking the Scope of Delivery ................................................................20
Operating elements / identifying the version ...........................................21
"Standard" version .....................................................................................22
"Premium" version .....................................................................................24
Working principle of the unit .....................................................................26
Filter element working principle .................................................................27

Contents
LVU-CD-10 en(us) Page 4 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Hydraulic diagram.......................................................................................28
Unit dimensions ..........................................................................................29
Unit setup/connection ................................................................................31
Notes on pipes / hosing .............................................................................32
Connecting the suction port (IN) ................................................................33
Connecting the pressure port (OUT) .........................................................33
Checking the water connection / water reservoir .......................................34
Electrical connection..................................................................................34
Connecting the remote control line.........................................................35
Preparing a visual clogging indicator - only for initial commissioning.........36
Using / setting / operating the "Standard" control type ..........................37
Switching the main switch on / off..............................................................37
Reading status LEDs .................................................................................38
Checking the motor protection switch........................................................38
Using / setting / operating the "Premium" control type ..........................39
Switching the main switch on / off..............................................................39
Reading status LEDs .................................................................................40
Adjusting the interval control......................................................................41
Adjusting the time selector switch ..........................................................42
Checking the motor protection switch........................................................42
Starting up the unit .....................................................................................43
Observe the clogging indicator - only with the "Standard" version.............43
Performing Maintenance ............................................................................44
Maintenance intervals................................................................................44
Perform visual check .................................................................................45
Checking / emptying water supply tank .....................................................46
Checking the pump for leaks .....................................................................47
Changing the filter element........................................................................49
Errors and troubleshooting........................................................................54
Customer Service .......................................................................................57
Taking the unit out of operation ................................................................58
Shutting down the unit ...............................................................................58
Disposing of the unit ..................................................................................58
Spare parts ..................................................................................................59

Contents
LVU-CD-10 en(us) Page 5 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Overview of spare parts.............................................................................59
Spare parts list...........................................................................................60
Technical details .........................................................................................61
Model Code..................................................................................................63
EC declaration of conformity.....................................................................64
Index ............................................................................................................65

Preface
LVU-CD-10 en(us) Page 6 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Preface
These operating instructions were made to the best of our knowledge.
Nevertheless and despite the greatest care, it cannot be excluded that
mistakes could have crept in. Therefore please understand that in the
absence of any provisions to the contrary hereinafter our warranty and
liability – for any legal reasons whatsoever – are excluded in respect of the
information in these operating instructions. In particular, we shall not be liable
for lost profit or other financial loss. This exclusion of liability does not apply
in cases of intent and gross negligence. Moreover, it does not apply to
defects which have been deceitfully concealed or whose absence has been
guaranteed, nor in cases of culpable harm to life, physical injury and damage
to health. If we negligently breach any material contractual obligation, our
liability shall be limited to foreseeable damage. Claims due to Product
Liability shall remain unaffected.
Technical Support
If you have any questions, suggestions, or encounter any problems of a
technical nature, please don't hesitate to contact us. When contacting us,
please always include the model/type designation and article no. of the
product:
Fax: +49 (0) 6897 / 509 - 9046
Modifications to the Product
We would like to point out that changes to the product (e.g. purchasing
options, etc.) may result in the information in the operating instructions no
longer being completely accurate or sufficient.
When making modifications or performing repair work to components
affecting the safety of the product, the product may not be put back into
operation until it has been examined and released by a HYDAC
representative.
Please notify us immediately of any modifications made to the product
whether by you or a third party.
Warranty
For the warranty provided by us, please refer to the General Terms of Sale
and Delivery of HYDAC FILTER SYSTEMS GmbH.
You'll find this under www.hydac.com -> General terms and conditions.

Preface
LVU-CD-10 en(us) Page 7 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Using the documentation
Note that the method described for locating specific information
does not release you from your responsibility of carefully reading
these instructions prior to starting the unit up for the first time and
at regular intervals in the future.
WHAT do you want to know?
I determine which topic I am looking for.
WHERE can I find the information I’m looking for?
The document has a table of contents at the beginning. I select the chapter
I'm looking for and the corresponding page number.
de
HYDACFiltertechnikGmbH
BeWa123456ade
Se ite x
Produkt/Kapitel
200x-xx-xx
The documentation number with its index enables you to order another copy
of the operating and maintenance instructions. The index is incremented
every time the manual is revised or changed.
Chapter description
Page number
Edition date
Document language
Documentation no.
with Index /
File name

Safety Information
LVU-CD-10 en(us) Page 8 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Safety Information
The unit was built according to the statutory provisions valid at the time of
delivery and satisfies current safety requirements.
Any residual hazards are indicated by safety information and instructions and
are described in the operating instructions.
Observe all safety and warning instructions attached to the unit. They must
always be complete and legible.
Do not operate the unit unless all the safety devices are present.
Secure the hazardous areas which may arise between the unit and other
equipment.
Maintain the unit inspection intervals prescribed by law.
Document the results in an inspection certificate and keep it until the next
inspection.
Hazard symbols
These symbols are listed for all safety information and instructions in these
operating instructions which indicate particular hazards to persons, property
or the environment.
Observe these instructions and act with particular caution in such cases.
Pass all safety information and instructions on to other users.
General hazard
Danger due to electrical voltage / current
Exposed electrical components
Danger of electrical shock
Danger due to operating pressure

Safety Information
LVU-CD-10 en(us) Page 9 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Risk of burns due to hot surfaces
Flammable
Danger from explosive atmosphere
Harmful to the environment

Safety Information
LVU-CD-10 en(us) Page 10 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Signal words and their meaning in the safety information and
instructions
DANGER
DANGER indicates a danger with a high risk and which will lead to death or
serious injury if not avoided.
WARNING
WARNING indicates a danger with a medium risk and which can lead to
death or serious injury if not avoided.
CAUTION
CAUTION indicates a danger with a low risk and which can lead to minor
injury if not avoided.
NOTICE
NOTICE indicates a danger which will lead to damage to property if not
avoided.
Structure of the safety information and instructions
All warning instructions in this manual are highlighted with pictograms and
signal words. The pictogram and the signal word indicate the severity of the
danger.
Warning instructions listed before an activity are laid out as follows:
SIGNAL WORD
Type and source of danger
Consequence of the danger
HAZARD SYMBOL
►Measures to avert danger

Safety Information
LVU-CD-10 en(us) Page 11 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Proper/Designated Use
Use the unit only for the application described in the following.
The LowViscosity Unit LVU is used for two-stage offline filtration, with solid
particle contamination and free water being removed from diesel fuel. The
degree of water separation is > 95 % as per ISO CD 16332 and the
dewatering rate is 12 l/h at 5 % water in the diesel. The limit of application is
obtained at a maximum of 10 % free water.
DANGER
Unacceptable fluid temperature
Risk of bodily injury due to burns
►Observe the maximum fluid temperature of <
50°C and at least 10°C below the flash point
of the fluid used.
DANGER
Dry running of the pump
Risk of bodily injury due to burns
►Ensure that the pump does not run dry.
NOTICE
Impermissible operating media.
The unit will be destroyed.
►The unit may only be used in combination with diesel, .biodiesel
B0 … B100 or fuel oil.

Safety Information
LVU-CD-10 en(us) Page 12 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Proper or designated use of the product extends to the following:
observing all instructions contained in these operating instructions.
adhering to maintenance work.
The unit is only suitable for suction operation mode
Operation is only permitted at an earthed power supply.
Not to be operated in the open air
Keep the unit away from sources of ignition
Improper Use or Use Deviating from Intended Use
DANGER
Danger due to unanticipated use of the unit
Risk of bodily injury due to fire
►Never operate the unit in potentially
explosive atmospheres.
►The unit is only to be used with permissible
media.
Any use extending beyond or deviating therefrom shall not be considered
intended use. HYDAC Filter Systems GmbH will assume no liability for any
damage resulting from such use. The user alone, shall assume any and all
associated risk
Improper use may result in hazards and/or will damage the unit. Examples of
improper use:
Operation with a non-approved medium.
Operation in potentially explosive atmospheres.
Operation under non-approved operational conditions.
Operation when the safety devices are defective.
Modifications to the power unit made by the user or purchaser.
Inadequate monitoring of parts that are subject to wear and tear
Improperly performed repair work.

Safety Information
LVU-CD-10 en(us) Page 13 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Qualifications of personnel / target group
Persons who work on the power unit must be aware of the associated
hazards when using the power unit.
Operating and specialist personnel must have read and understood the
operating instructions, in particular the safety information and instructions,
and applicable regulations before beginning work.
The operating instructions and applicable regulations are to kept so they are
accessible for operating and specialist personnel.
These operating instructions are intended for:
Operating personnel: such persons have been instructed in power unit
operation and are aware of potential hazards due to improper use.
Specialist personnel: such persons with corresponding specialist training and
several years work experience. They are able to assess and perform the
work assigned to them, they are also able to recognize potential hazards.
Activity Person Knowledge
Transport / storage Auxiliary
personnel
No specialist knowledge
required
Startup operation
Operations control
Auxiliary
personnel
Product-specific knowledge
Knowledge about how to handle
operating media.
troubleshooting,
maintenance,
decommissioning,
Disassembly
Specialist
personnel
Safe handling/use of tools
Product-specific knowledge
Disposal Specialist
personnel
Proper and environmentally-
friendly disposal of materials
and substances
Decontamination of
contaminants
Knowledge with regard to
recycling

Unpacking the unit
LVU-CD-10 en(us) Page 14 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Wear suitable clothing
Loose-fitting clothing increases the risk of being caught or being drawn in on
rotating parts, and the risk of getting caught on protruding parts. You can be
severely injured or killed.
Wear close-fitting clothing.
Do not wear any rings, chains or any other jewelry.
Wear work safety shoes.
Wear gloves.
Observe the information relating to personal protection equipment in
the safety data sheet of the operating fluid.
Observe regulatory information
Observe the following regulatory information and guidelines:
Legal and local regulations for accident prevention
Legal and local regulations for environmental protection
Country-specific regulations, organization-specific regulations
Stoppage in an emergency (EMERGENCY STOP)
In an emergency, switch the unit off at the main on/off switch or unplug the
power connector.
Unpacking the unit
Prior to delivery, the unit is function and leak-tested in the factory.
When unpacking the unit, check it for damage in transit.

Transporting the unit
LVU-CD-10 en(us) Page 15 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Transporting the unit
Empty the unit completely before transport, including the filter and coalescing
casing. Pull out the power plug and securely fasten the power cord to the
unit.
Carry by hand
Only transport the unit by carrying the frame, or with it standing on its feet.
When transporting the unit, never pick it up by its attachment parts or
components.

Transporting the unit
LVU-CD-10 en(us) Page 16 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Transporting with the crane
For transport with a crane, fasten the correct band loops on the frame.

Storing the unit
LVU-CD-10 en(us) Page 17 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Storing the unit
Before storing, empty the unit completely, including the filter and coalescing
casing. Pull out the power plug and securely fasten the power cord to the
unit.
Permitted storage temperature
range
0 … 45 C
Air Clean, salt-free air, not near
oxidizing substances (rust film)
Storage duration Unrestricted, but in any case before
the unit is started up again: after a
storage period of greater than 2
years, all seals must be replaced.
Storage position Only standing.

Decoding the model code label
LVU-CD-10 en(us) Page 18 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Decoding the model code label
Details for identifying the filtration unit can be found on the name plates on
the unit and the components.
Item -> Description
(1) -> Name plate of filtration unit
(2) -> Name plate of electric motor
(3) -> Model code; for details, see page 63

Decoding the model code label
LVU-CD-10 en(us) Page 19 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
The following information can be found on the name plate of the unit:
Row -> Description
Part No. -> Part number
S/N -> Serial number / year of production
Power -> Power consumption
Voltage/Grid -> Voltage / power supply
Frequency -> Frequency
Current -> Current consumption
Pressure max. -> Operating pressure, maximum
Weight -> Empty weight
Flow rate -> Flow rate
Temp. Fluid -> Permitted fluid temperature range
Temp. Amb. -> Permitted ambient temperature range
Volume -> Fluid volume in unit

Checking the Scope of Delivery
LVU-CD-10 en(us) Page 20 / 68
BeWa LVU-CD-10 StdPrm 3993633a en-us 2015-08-26.doc 2015-08-26
Checking the Scope of Delivery
The filtration unit comes factory-assembled. Check that the filtration unit is
complete before starting up.
The following items are supplied:
Qty Designation
1 LowViscosity Unit LVU-CD-10, version in accordance with your
order, check the name plate on page 18.
1 Operation and Maintenance Instructions (this document)
Example: Figure: LVU-CD-10 "Standard"
Other manuals for LVU-CD-10
1
Table of contents
Other HYDAC FILTER SYSTEMS Industrial Equipment manuals

HYDAC FILTER SYSTEMS
HYDAC FILTER SYSTEMS OFU-ATEX Manual

HYDAC FILTER SYSTEMS
HYDAC FILTER SYSTEMS FluidAqua Mobil FAM 5 Manual

HYDAC FILTER SYSTEMS
HYDAC FILTER SYSTEMS Filtromat OF5 F Manual

HYDAC FILTER SYSTEMS
HYDAC FILTER SYSTEMS LowViscosity Unit CoalescerDiesel LVU-CD-40 User manual

HYDAC FILTER SYSTEMS
HYDAC FILTER SYSTEMS OXiStop OXS User manual

HYDAC FILTER SYSTEMS
HYDAC FILTER SYSTEMS CMP 43x0-5 Series User manual

HYDAC FILTER SYSTEMS
HYDAC FILTER SYSTEMS LVU-CD-10 Manual