
5
CAUTION Additionally, DO NOT install the valve(s) in any manner such,
that if the valve were to close:
1. A water softener were to close would not operate correctly.
2. A sprinkler/ or irrigation system would not operate correctly.
(Unless using two valves and Valve #2 is designated for irrigation).
3. A well pump/ pressure tank would not operate correctly.
4. A recirculation pump could fail.
The ball valve(s) are bi-directional. It does not matter which end of the valve is input or output.
The valve is 1” and it is recommended to use plumbers tape when connecting the male
adapters to the valve.
OUR SYSTEM IS ALSO CAPABLE OF OPERATING LARGER VALVES AND FLOW
METERS. SEE OUR WEBSITE WWW.HYDRO-COM.COM/ FAQ INSTALLATION FOR
THE CORRECT OPERATION AND WIRING.
IF YOU ARE USING WELL WATER, OR A WATER SOURCE THAT HAS HIGH SUSPENDED
SOLIDS, WE RECOMMEND THE USE OF A 50 MICRON PRE-FILTER BEFORE THE
FLOW METER AND VALVE.
FLOW METER(S) INSTALLATION -- AUTOTROL TURBINE
Observe the flow direction arrow on the turbine. Provide
a minimum of 12 inches (306 mm) of straight pipe before
and after the 2 inch (51 mm) turbine, and 6 inches (153
mm) before and after the 1 inch (25 mm) turbine.
Be especially careful of turbine orientation (Figure
3). Both horizontal and vertical orientations are
acceptable,however, be certain that you will have a full
pipe condition at all times. DO NOT mount the turbine
in a vertical orientation in a down-flow condition. Under
normal conditions the turbine will require no maintenance.
In areas where the make-up water has suspended solids,
prefiltration is required. A Wye-type stainer with a 50 mesh
specification is recommended.
NOTE: DIMENSIONS ARE FOR REFERENCE ONLY. Care should be taken to
adequately support and align the pipes running into and out of the turbine.
CAUTION: DO NOT over tighten the turbine housing adapter nuts or you may
damage the threads. Hand tight plus 1/4-turn on nuts is recommended.
Insert sensor probe into turbine housing. The probe will “click” into place when inserted the
proper depth into the housing receptacle. Run the cable to the controller along the pipe using
cable ties or in conduit.
Figure 2 2-inch (51 mm) Turbine