Hydromatic Novus 1000 Series Manual

STANDARD ELECTRICAL
CONTROLS
04/10
Item # H-03-481
Part # 5625-481-1
NOTE! To the installer: Please make sure
you provide this manual to the owner of
the equipment or to the responsible party
who maintains the system.
Installation and Service Manual

2
Thank you for purchasing your
Hydromatic®Novus Control
Panel. To help ensure years of
trouble-free operation, please read
the following manual carefully.
Before Operation:
Read the following instructions
carefully. Reasonable care and
safe methods should be practiced.
Check local codes and
requirements before installation.
Attention:
This manual contains important
information for the safe use of
this product. Read this manual
completely before using this
product and refer to it often for
continued safe product use. DO
NOT THROW AWAY OR LOSE
THIS MANUAL. Keep it in a
safe place so that you may refer
to it often.
Unpacking Panel:
Remove panel from carton. When
unpacking unit, check for
concealed damage. Claims for
damage must be made at the
receiving end through the delivery
carrier. Damage cannot be
processed from the factory.
WARNING: Do not attempt to
wire this control box unless you
have a good working knowledge
of electricity and are familiar
with the state and local codes. If
you are in doubt about anything,
contact a qualified electrician.
Do not attempt to operate this unit
on any other voltage or power
distribution other than for which it
was originally designed (check
nameplate). Failure to comply
with this will result in the
immediate cancellation of all
warranties and claims.
It is advisable to put the panel on
its own circuit using a circuit
breaker adequately sized to
protect the pump(s). Check state
and local codes for the correct
wire size and circuit protection to
use. The wire should be sized
large enough to handle the full
load current of the pump(s) you
are operating, and any voltage
drop that might occur due to long
service runs.
Run power supply lines to the
control box and secure (knockouts
are not supplied in this box).
Select a convenient location on
the bottom to enter the box with
the power supply. Cut a hole with
a chassis punch. Caution should
be taken not to get metal chips in
the components while cutting
hole. After the hole is cut, any
metal particles must be removed
from the box. Failure to do so may
result in premature component
failure.
Connect incoming power to the
terminal blocks labeled L1, L2, L3,
and all necessary ground wires to
the ground lug at the bottom of the
box. The ground lug should be
fastened to a good driven earth
ground by one of the methods
described in the National Electric
Code. NEC does not permit using
ground as a current carrying
conductor, therefore a neutral
must be provided for 115 volt 1
phase, 208 volt 1 phase, 230 volt
1 phase, or 208 volt 3 phase
systems.
WARNING: Before handling
these pumps and controls,
General
Information
always disconnect the power
first. Do not smoke or use
sparkable electrical devices or
flames in a septic (gaseous) or
possible septic sump.
Electrical Connections:
The contractor must conform to
the latest requirements of the
National Electrical Code. All
conduit and cables shall be in
accordance with NEC Code
NFPA #70. To maintain UL and
CSA ENCL rating, use the same
type UL and CSA weatherproof
conduit hubs when connecting to
this enclosure. Prior to conducting
any installation, repair or service
with regard to the control panel,
refer to the schematic appropriate
for that panel. The schematic will
provide guidance with regard to
the terminal block connections.
CAUTION: A nonmetallic
enclosure does not provide
grounding conduit connections.
Use grounding bushing and
jumper wires.
Make the Following Electrical
Connections:
a. Connect the pump leads to
the control panel. If pump is
single phase and the panel
has start capacitor, start relay
and run capacitor, it is critical
that the pump leads be
connected properly. The
White, Black, and Red pump
leads must be connected to
the appropriate terminals
as directed by the panel
schematic and the label on
the back panel below the
terminals.
b. Connect the pump heat sensor
and seal failure leads (if
available on the pump) to the
appropriate terminal blocks in
the control panel.
Power
Supply

3
c. Connect all the float control
leads or 4-20mA leads to the
appropriate panel terminals.
Contractor must be very
careful in locating the floats at
the proper elevations. The
maximum distance from the
control panel to the floats
is the lesser of l00 feet,
or the maximum distance
recommended for the pump.
d. Before connecting power to the
control panel, make sure all
control switches (e.g. H-O-A
switch) and protective devices
(e.g. breakers) are in the Off
position. Now connect power
to the terminal block or the
circuit breaker as directed by
the schematic.
e. Control panel must be
grounded properly per NEC
and/or local codes. To
facilitate this, a ground lug is
provided on the control panel.
1. Check junction box for
moisture. Moisture may cause
chattering of relays/contactors.
2. If pump is single phase with
start capacitor, start relay
and run capacitor in panel.
Check that pump White,
Black, and Red power wires
are connected to panel
correctly.
3. WARNING! Live voltage can
kill! Check incoming power
voltage to make sure that
it is correct for panel and
pump model.
4. Energize control panel. (Turn
on power to panel.)
5. Check overload relay and
verify reset mode (if overload
is supplied).
WARNING: Before handling
these pumps and controls,
always disconnect the power
first. Do not smoke or use
sparkable electrical devices or
flames in a septic (gaseous) or
possible septic sump.
The maintenance schedule
will vary with operating and
environmental conditions. It will
also vary with the specific type of
control supplied. The list herein is
a guide only.
1. Exercise breaker through one
cycle. Be careful not to
overexercise as the breaker is
not a switching device.
Excessive operations tend
to affect the trip curve of
the breaker.
2. Check contactors and relays
for excessive humming. This
can be accomplished by
turning pumps on and off in
the Hand mode with the
H-O-A switch.
3. Check pump run light(s) by
running pump(s) in Hand
mode. Check bulb(s) in any
other light(s).
4. With the power off, check
continuity of all control fuses.
5. Check voltage at primary
and secondary of control
transformer.
6. Check the pump full
load amps.
7. For 1 phase panels with start
circuit, about 5 seconds after
the pump starts check the
voltage from terminal 1 to
terminal 2 on the start relay to
be sure that the relay has
operated. The voltage from
terminal 1 to terminal 2 on the
start relay must exceed 10
VAC. For some pumps the
voltage may exceed 400 VAC.
If after 5 seconds the voltage
from terminal 1 to terminal 2
on the start relay does not
exceed 10 VAC stop the pump
as damage to the start capacitor
may be damaged in about 15
seconds.
Start-up
Operation
6. WARNING! Live voltage can
kill! Check voltage to the
panel and at secondary of
control transformer using a
voltmeter. If no transformer is
supplied, check voltage at the
circuit breakers.
7. With H-O-A switch in hand,
check discharge to verify the
pump is running. Check for
flow. On three phase power,
check to see if each pump
has proper rotation. Wrong
rotation will give low flow.
8. Check full load current
with amp probe and compare it
with the nameplate rating. On
three phase pumps, check
all three phases. On single
phase pumps, check black
pump lead.
9. Check operation of start relay,
if supplied on single phase
panels, per procedure in Item
#7 of Maintenance Instructions.
10.With H-O-A switch in Auto,
check float operation and
response to control panel to
the float operation. For
sequence of operation, refer to
design specification.
11.Make sure H-O-A switch is left
in the Auto position after
start-up is completed.
Pump Start-Up:
Refer to pump Installation and
Service Manual.
Pump
Maintenance

4
WARNING: Before handling
these pumps and controls,
always disconnect the power
first. Do not smoke or use
sparkable electrical devices or
flames in a septic (gaseous) or
possible septic sump.
1. Pump does not run in
Hand position.
a. Check pump circuit
breaker and control fuse
for tripping or blown
condition.
b. Check incoming power
voltage and control
circuit voltage.
c. Check overload relay to see
if it is tripped. Reset relay
if tripped and check pump
current with ammmeter.
d. With the power off, check
motor heat sensor
continuity.
e. Check wiring of pump to
control panel. It should
agree with the schematic.
f. Check contactor coil
resistance.
2. Pump does not run in
Auto position.
a. Check items (a.) through
(f.) per Item #1 above.
Pump
Troubleshooting
If the start relay is not
operating check the pump and
the system voltage to be sure
that they match. Check the
power wiring to ensure that the
pump is connected properly.
Start the pump once more and
check that the voltage from the
terminal for the black wire to
the white wire is within system
tolerance. Call for help if you
cannot resolve the problem.
8. Check junction boxes for
moisture. Moisture may
cause chattering of relays
and contactors.
9. Check for moisture inside
control panel enclosure.
Moisture can cause damage to
electrical components. Check
door gasket for proper seal.
10.Check labels to verify they
have not been damaged.
11.Lubricate enclosure hinges.
12.Pull floats and check for
proper operation and ensure
there is no foreign buildup
on them.
Spare Parts List:
The following is a list of
recommended spare parts.
However, conditions of service
vary significantly and a general
list may not in its entirety be
applicable to a given installation.
The user should exercise
judgment in defining specific
requirements based on this guide.
1. Fuses for control transformer
primary and secondary. (If
required)
2. Contactor.
3. Bulbs for any light requiring
a bulb.
4. Control transformer. (If
required)
5. Alternator relay. (If required)
Optional: The LOW WATER /
REDUNDANT OFF float should
be installed just above where the
pump begins to ingest air
normally; this is about the top of
the volute.
The OFF float should be installed
about halfway down the pump. If
a LOW WATER / REDUNDANT
OFF float is used, then the off
float should be installed a
minimum of 4 inches above the
LOW WATER / REDUNDANT
OFF float.
Install the ON / LEAD floats a
minimum of 4 inches above the
OFF float. If additional volume is
to be pumped on each cycle or if
the pump running time for each
cycle needs to be increased, then
increase the distance from the
ON / LEAD float to the OFF float
as needed.
Install the HIGH WATER float
4 inches above the ON / LEAD
float.
For duplex systems install the
LAG / OVERRIDE float 4 inches
above the HIGH WATER float.
On duplex systems where both
pumps have to run on a daily basis
to keep up with the incoming
flow, then the HIGH WATER and
the LAG / OVERRIDE float
position should be reversed.
Float
Controls

b. Floats may be miswired to
control panel. Check float
type (N.O. or N.C.) and
hook up by referring to the
schematic. If the start and
stop floats are hooked in
reverse, pump will short
cycle and will not pump the
level down.
1. Is water level in the
system high enough to
activate the floats?
2. If there is enough water
in the system (with the
power turned off), mark
and disconnect the off
and on floats. Next,
install jumper wires in
the terminal blocks for
off and on floats. Turn
power back on, put H-O-
A switch in Auto and see
if pump runs.
3. If pump runs with
jumper, problem is with
floats. Remove jumpers
and troubleshoot floats
with ohmmeter.
4. If pump does not run
in Auto mode with
jumpers, check Auto
circuit wiring in panel.
3. Pump runs, but run light
does not energize.
a. Remove light and check
with an ohmmeter.
b. Check run light wiring.
4. Pump runs but does not
pump down the wet well.
a. On three phase only,
pump rotation may be
wrong. Wiring of pump to
control panel may be
reverse sequenced.
b. Impeller may be dragging in
volute due to solids. High
amperage draw would
identify this.
c. Refer to the pump manual
for other possibilities such
as closed discharge gate
valve, etc.
5. Severe humming/chattering
of contactors and control
relays.
a. There may be low voltage.
Check voltage at primary
and secondary of control
transformer using a
voltmeter. This low voltage
condition may cause severe
chattering and burnout of
contacters and relays.
b. Contactor may have dust
around magnet of coil
structure. Dry or clean
as required.
c. Check voltage to the
control panel. Contactors
require a minimum of 85%
of full voltage to pull
in without chatter. If the
problem is a recurring
one, measure voltage with
recorder on a 24 hour basis.
d. Make sure the floats are
located away from any
turbulence.
e. Dry out the junction box
(if furnished); moisture
in the junction box may
cause relays to energize
intermittently.
6. Short cycling pump.
a. Check float controls.
7. Run light stays on.
a. Selector switch may be in
the Hand position.
8. Nuisance tripping of
overload on motor starters
or circuit breakers.
a. Check pump amp draw with
amp probe and compare to
nameplate amps on pump.
b. The impeller may be locked
up due to excessive debris
or solids.
c. Possible motor failure (fault
in windings).
d. Pump may be miswired to
terminal block.
e. Voltage and current
unbalance. Three phase
only.
Voltage unbalance on three
phase power sources can
cause motor current to
become unbalanced and
excessive heating will
result. Tripping of the
overload protectors and
premature motor failures
can be expected if the
current unbalance exceeds
five percent.
Percent Maximum Current
Current = Difference from x 100
Unbalance Average Current
_______________
Average Current
To determine if motor current
unbalance is a function of the
motor or the power supply:
1. Label the leads and
the terminals 1, 2, and 3
respectively.
2. Record the amperage for
each lead.
3. Move each lead to the
next terminal (1 to 2, 2 to
3, 3 to 1).
4. Again read the amperage
of each lead.
5. Move each lead to the
next terminal (1 to 3, 2
to 1, 3 to 2).
6. Again read the amperage
of each lead.
5

4. Start relay check.
a. Check the coil resistance.
It should be 3,000 to
15,000 ohms.
b. Install a clamp on amp
meter around the start
winding lead.
c. Set the amp meter
scale to at least 2 times
the pump motor full
load current.
d. Place the H-O-A switch
in the Hand position to
start the pump.
e. The meter should read
approximately 2 times
full load current during
starting.
f. After the motor has
started (within one
second) the current
should drop to a value
much less than full load
current.
5. Motor voltage check:
6
Pump
Troubleshooting
7. If the unbalance moves
with the motor leads, the
unbalance is caused by
the motor. If the
unbalance remains with
the terminals, the
unbalance is in the
power supply.
8. If the current unbalance
exceeds five percent,
nuisance tripping or
excessive heating will
result.
9. Connect leads for the
lowest percent of current
unbalance.
f. Connections and start
components. Single phase
only.
1. Disconnect all power
from the panel before
making these checks.
2. Motor winding resistance
readings.
a. Disconnect all three
motor leads from panel
terminal blocks.
b. Using a volt-ohmmeter,
with the scale set
on RX1, measure the
resistance between the
leads with the chart.
Typical
Motor Resistance
Winding Leads Reading
Main Black to Lowest
White
Start Black to Next
Red Lowest
(Middle)
Both White to Highest
Red (Main & Start)
3. Capacitor check.
a. Make sure the capacitor
is discharged. Use
extreme caution as a
spark might occur.
b.Disconnect the capacitor
leads and connect
an analog-type volt-
ohmmeter to the capacitor
terminals.
c. Set the meter on the
RX1,000 scale to check
the start capacitor. Set the
meter on the RX10,000
scale to check the
run capacitor.
d. The meter should indicate
low ohms when it is first
connected, but as
the capacitor becomes
charged (by the meter), it
will return to a reading of
infinity (open circuit).
Typical
Motor Voltage
Component Lead Mode Reading
Main Winding Black to Start Line Voltage
White
Main Winding Black to Run Line Voltage
White
Start Winding Black to Start Line Voltage
Red
Start Winding Black to Run 120%
Red Line Voltage

7
Pump
Notes
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________

Pump
Notes
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
8

Pump
Notes
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
9

– Your Authorized Local Distributor –
www.hydromatic.com
STANDARD LIMITED WARRANTY
HYDROMATIC®warrants its products against defects in material and workmanship for a period of 12 months
from the date of shipment from Hydromatic or 18 months from the manufacturing date, whichever occurs first -
provided that such products are used compliance with the requirements of the Hydromatic catalog and
technical manuals for use in pumping raw sewage, municipal wastewater or similar, abrasive free
non-corrosive liquids.
During the warranty period and subject to the conditions set forth, Hydromatic, at its discretion, will repair or
replace to the original user, the parts which prove defective in materials and workmanship. Hydromatic
reserves the right to change or improve its products or any portions thereof without being obligated to provide
such a change or improvement for prior sold and/or shipped units.
Start-up reports and electrical schematics may be required to support warranty claims. Warranty is
effective only if Hydromatic authorized control panels are used. All seal fail and heat sensing devices must be
hooked up, functional and monitored or this warranty will be void. Hydromatic will only cover the lower seal
and labor thereof for all dual seal pumps. Under no circumstance will Hydromatic be responsible for the cost
of field labor, travel expenses, rented equipment, removal/reinstallation costs or freight expenses to and from
the factory or an authorized Hydromatic service facility.
This limited warranty will not apply: (a) to defects or malfunctions resulting from failure to properly
install, operate or maintain the unit in accordance with the printed instructions provided; (b) to failures resulting
from abuse, accident or negligence; (c) to normal maintenance services and parts used in connection with such
service; (d) to units which are not installed in accordance with applicable local codes, ordinances and good
trade practices; (e) if the unit is moved from its original installation location; (f) if unit is used for purposes other
than for what it is designed and manufactured; (g) to any unit which has been repaired or altered by anyone
other than Hydromaticor an authorized Hydromatic service provider; (h) to any unit which has been repaired
using non factory specified/OEM parts.
Warranty Exclusions: HYDROMATIC MAKES NO EXPRESS OR IMPLIED WARRANTIES WHICH EXTEND
BEYOND THE DESCRIPTION ON THE FACE HEREOF. HYDROMATIC SPECIFICALLY DISCLAIMS THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR ANY PARTICULAR PURPOSE.
Liability Limitation: IN NO EVENT SHALL HYDROMATIC BE LIABLE OR RESPONSIBLE FOR
CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES RESULTING FROM OR RELATED IN ANY MANNER
TO ANY HYDROMATIC PRODUCT OR PARTS THEREOF. PERSONAL INJURY AND/OR PROPERTY DAMAGE
MAY RESULT FROM IMPROPER INSTALLATION. HYDROMATIC DISCLAIMS ALL LIABILITY, INCLUDING
LIABILITY UNDER THIS WARRANTY, FOR IMPROPER INSTALLATION. HYDROMATIC RECOMMENDS
INSTALLATION BY PROFESSIONALS.
Some states do not permit some or all of the above warranty limitations or the exclusion or limitation of
incidental or consequential damages and therefore such limitations may not apply to you. No warranties
or representations at any time made by any representatives of Hydromatic shall vary or expand the
provision hereof.
USA
740 East 9th Street, Ashland, Ohio 44805
Tel: 419-289-3042 Fax: 419-281-4087
CANADA
269 Trillium Drive, Kitchener, Ontario, Canada N2G 4W5
Tel: 519-896-2163 Fax: 519-896-6337
Warranty Rev 02/09


START-UP REPORT
cut along dotted line
Distributor:__________________________________________________ Order No.: _________________________
Installing Contractor: _________________________________________ Phone: ____________________________
Sales Contact: ______________________________________________ Phone: ____________________________
Customer: ______________________________________________________________________________________
Location: _______________________________________________________________________________________
1. SYSTEM INFORMATION
Size of Wet Well:_______________________________________Manufacturer: _____________________________
Discharge from Bottom of Basin: ________________________Discharge Location:________________________
Inlet from Bottom of Basin: _____________________________Inlet Location: _____________________________
Type of Check Valves: __________________________________Type of Piping: ____________________________
Does System Have Suction Gauges? ❑Yes ❑No Suction Pressure Reading: __________________
Does System Have Discharge Gauges? ❑Yes ❑No Discharge Pressure Reading:________________
Liquid Being Pumped:_______________________Temperature (F°): __________ Pct. of Solid (%):___________
Is a Sketch or Photograph of System Available? ❑Yes ❑No If So, Please Attach.
Any Additional Comments on System:______________________________________________________________
_______________________________________________________________________________________________
2. ELECTRICAL INFORMATION
Control Panel Part Number: _____________________________Panel Rated Amps: ________________________
Manufacturer: _________________________________________Voltage: _______________ Phase: ____________
Heater Size:___________________________________________Location of Panel to Wet Well: _______________
Incoming Line Voltage: _________________________________Actual?___________________________________
Voltage to Pumps: _____________________________________Actual? ___________________________________
Type of Junction Box: __________________________________Manufacturer of Junction Box: ______________
Are Floats Installed in Wet Well? ❑Yes ❑No Are Floats Set to Engineer’s Specs? ❑Yes ❑No
Are Floats Wired for Proper Sequencing? ❑Yes ❑No Are Heat Sensors Hooked Up? ❑Yes ❑No
Is the Seal Leak Detection Hooked Up? ❑Yes ❑No
Any Additional Comments on Electrical: ____________________________________________________________
_______________________________________________________________________________________________
3. PUMP INFORMATION
Type of Pump:_________________________________________Serial Number of Pump: ____________________
Voltage of Pump: ________________ Phase: _______________RPM: _________________ Amps: ____________
Impeller Size:____________________ C.O.S. TDH: __________GPM: _________________
Voltage Supplied from Panel:____________________________Actual? ___________________________________
Actual Amperage (All Phases): Phase 1 Amps: ________ Phase 2 Amps: ________ Phase 3 Amps: ________
Define the Rotation of the Pump: ❑Clockwise ❑Counterclockwise
Method Used to Check Rotation: ❑Viewed from the Top ❑Viewed from the Bottom
Any Additional Comments on Pumps: ______________________________________________________________
_______________________________________________________________________________________________
4. ACKNOWLEDGE
Acknowledge that all information is accurate and proper procedures have been followed.
Customer: ___________________________________________________________________ Date: _____________
Start-up Technician:___________________________________________________________ Date: _____________
Send to Warranty Manager, 1101 Myers Parkway, Ashland, OH 44805
or Fax to 419-207-3344
or submit online at http://forms.pentairliterature.com/startupform/startupform.asp?type=h
Table of contents