IBAIONDO CRB AUTOMAT Touch Screen User manual

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB
AUTOMAT
Touch Screen
COMPRESSOR CONTROLLED
PRESSURIZATION SYSTEM

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Description
Compressor controlled pressurization units, classified as a dynamic pressurization system for heating and
cooling water systems. It requires an auxiliary power source for its operation.
They are controlled by a compressor and allow to maintain steady pressure in the system, by compensating
volumetric changes suffered by the fluid, as a consequence of temperature variations in the system.
CRB AUTOMAT is formed mainly by a control unit (Compressor & controller) and an expansion vessel.
Expansion tank is fitted with a bladder to divide the vessel between air and water side.
CRB AUTOMAT provides the following safety features:
• Optimization of pressure maintenance.
• Reduced corrosion damage due to oxygen removal.
• No direct intake of air thanks to a regulation of the pressure maintenance.
• No circulation issues caused by free bubbles in the water system.

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Application
Increases and decreases in water volume are continuous in heating and cooling systems due to temperature
variation. When temperature raises, the pressure in the system increases. As a consequence water level in water
side of the expansion vessel changes. That increase is absorbed by the expansion vessel. Pressure differences in
air side is showed in display.
On one hand, pressure sensor measures air pressure and transmit to the control unit. Control unit compares the
measured value with the programmed nominal value and if the pressure increases, the solenoid valve will be
activated to reduce the pressure until reaching set values.
On the other hand, when temperature in system drops, pressure in the air side change. Control unit compares the
measured value with the operative or set point pressure value and if pressure decreases the compressor will be
activated until reaching set values.
A. Temperature increase
Unit contains a small amount of water. Unit is
in res
t
B. Temperature increase
Water volume and pressure system rises. Controller
responds to this by discharging air from the vessel and
as a result, the ex
p
ansion water flows into the bladder.
C. Full power
By storing increasing amounts of water in the
vessel, controller keeps pressure system at a
constant level. When system has warmed up
completely, vessel will be operating at almost
its maximum ca
p
acit
y
.
D. Cooling down
When water volume and thus pressure system
decreases, controller will respond by increasing the air
pressure in the vessel with displacement of water back
into the subsystem as a result. This restores
e
q
uilibrium in
p
ressure s
y
stem.

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Overview CRB AUTOMAT
Nº
Accessories
1
Compressor
2
Control unit
3
Water side purgue
4
Air connection
5
Valves support
5.1
5.2
5.3
5.4
Safety valve
Solenoid valve
Anti-return valve
Pressure sensor
6
Air pipe between vessel and
anti-return valve
7
Steel expansion vessel
8
Sticker
9
Bladder
10
Cable duct
11
Flexible hose to the system
12
Level sensor - load cell
5
1
3
4
2
7
11
12
10 9
8
6

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Compressor Air supply
When water in the system is heated,
pressure in the system rises. If the
nominal pressure at the controller is
exceeded, the solenoid valve opens
and discharges air from the vessel.
It allows water to flow into the
expansion vessel and the water
pressure within the system drops up
to nominal pressure.
As water cools, water pressure in
the system drops. If pressure in the
system drops below the nominal
pressure, compressor delivers air
into the expansion vessel up to
reach the nominal
p
ressure
Overview CRB AUTOMAT
Replaceable bladder
Bladder stores water. It
allows to divide air side
from the water side
Flexible connection R1”
for the expansion line
Load cell
It measures the water level
inside the expansion vessel.
If water level rises over a
limit occurs ”high water
level alarm”
If water level drops below a
limit, occurs “Low water
level alarm”
Expansion vessel Compressor
controlled expansion vessel.
It allows to maintain steady
pressure in the system,
compensating volumetric
changes suffered by the fluid,
as a consequence of
temperature variations in the
system.
The air side of the expansion
vessel and the load cell are
connected to vessel control
uni
t
.
Control unit-Touch screen
Pressure system integrated
control
It includes compressor, 7” touch
screen control unit with solenoid
valve, antireturn valve, safety
valve and pressure sensor.
Solenoid valve opens and
discharges air from the vessel.
Antireturn valve avoids air going
in an opposite direction.
Pressure sensor displays
continuous pressure in the
system.
Safety valves protects expansion
vessel.

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Main features
- Automatic expansion vessels for pressure maintenance in heating and cooling systems
- Replaceable bladder according to EN13831 (non-potable)
- Upper membrane purge
- Control unit for regulating water pressure and volume. Includes:
7 "color touch screen for control of the system
Standard compressor with max. operative pressure of 8 Bar. Oil free.
Power supply 220V / 50Hz single phase
Weight cell with cable and connector for connection to the control unit
Pressure sensor 4-20 mA
Solenoid valve with silencer
Backflow valve
Pneumatic safety valve
Top screwed flange for inspection
- External finish in blue RAL-5012
- Manufactured in accordance with Directive 2014/68 / EU
- Optional: Automatic water replenishment (Auto filling kit)
- Optional: RS-485, Ethernet
- Bottom condensate drain valve
- Water connection by flexible hose R1 "G.H.
(*) 10 Bar Compressor, consult factory
TYPE 200 CRB
AUTOMAT
300 CRB
AUTOMAT
500 CRB
AUTOMAT
700 CRB
AUTOMAT
Product code 04022427 04035427 04050427 04070427
Weight 70 Kg 85 Kg 150 Kg 192 Kg
Max. Work. Pressure 6 Bar 6 Bar 6 Bar 6 Bar
Volume 200 Liter 300 Liter 500 Liter 700 Liter
Diameter 600 mm 600 mm 700 mm 800 mm
Height 1.225 mm 1.475 mm 1.795 mm 1.955 mm
Connection R1” R1” R1” R1”
Bladder Replaceable Replaceable Replaceable Replaceable
Permissible Oper. Temp. 70ºC 70ºC 70ºC 70ºC
Noise level 52 dB 52 dB 52 dB 52 dB
Voltage 220 V 220 V 220 V 220 V
Electrical output 0.75Kw 0.75Kw 0.75Kw 0.75Kw
Frequency 50 Hz 50 Hz 50 Hz 50 Hz
Power supply Plug Plug Plug Plug
Compressor F114-8Bar F114-8Bar F114-8Bar F114-8Bar

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Spare parts
Compressor
Control unit Load cell
Valves
l/min CFM m
3
/h Bar psi HP KW Min
-1
LxPxH
mm Kg
105
3.7
6,3
8
116
1
0,75
1.450 340x185x315
10
Control unit-Touch screen (2)
- 7” Touch screen - colour display
- Electronic board
- ABS Box for electronic hosting
- Permanent display of the operating
parameters in the system
- Pressure & Volume
- Graphic user interface
- Integrated control of system pressure
- Evaluation and storage of the most
important data
- Interfaces:
RS-485
Ethernet
Load cell-Level sensor
Allows determining the filling level
Technical data
Supply: 5…15V
Signal Out: 0-10 mV
Sensitivity: 2 mV/V±1%
Wire length: 4 meters
Anti-return valve
To avoid air returning from the vessel
Safety valve
Protects from the excessive pressure
Solenoid valve
Opens if the pressure has increased from
operative pressure
Pressure Sensor
Detect the pressure in the vessel
Air pipe
Air pipe between compressor and vessel
distributor

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Control unit
The control unit includes the following parts:
ABS Box for electronic hosting
7” Touch screen
Electronic board
Touch screen
7 "color touch screen. The operating data of the system are entered through the touch screen. There are 6
different screens through which you can navigate by entering an access code.
MAIN SETTINGS TEST COMM EVENT INFO

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Control unit
Electronic board
The electronic board include de following elements:
Terminals for 230Vac power input
Magnetothermic protection 10A serie C
Microcontroller for the management and control of the equipment
Relay for the activation of the 230Vac 10A compressor with function check
Relay for the activation of the air solenoid valve 230Vac 10A with function check
Relay for the activation of the 230Vac 10A automatic filling solenoid valve with function check
Voltage alarm relay of 230Vac 10A potential-free
Pressure alarm relay 230Vac 10A potential-free
Analog input 4 - 20 mA of pressure measurement
Analog input 4 - 20 mV of volume / weight measurement (load cell)
Pressure output 4 - 20 mA mirror of the pressure input
Volume output 4 - 20 mA mirror volume / weight input
Connection with the touch screen
RS485 connection
Ethernet connection
Lithium battery for the maintenance of the hour
Connectors
Connector for the power supply (phase, neutral and ground)
DB9 connector for RS45 communication is connected (A, B, GND)
RJ45 female connector for Ethernet port
Connector of double row of 30 contacts whose connections are:
01: Analogue In Pressure -> +24VDC
02: Analogue In Pressure -> A
03: Analogue In Pressure -> B
04: Analogue In Volume/Weigth ->
+24VDC
05: Analogue In Volume/Weigth -> A
06: Analogue In Volume/Weigth -> B
07: Analogue Out Pressure -> Vref
08: Analogue Out Pressure -> A
09: Analogue Out Pressure -> B
10: Analogue Out Volume/Weight -> Vref
11: Analogue Out Volume/Weight -> A
12: Analogue Out Volume/Weight -> B
13: Digital In Water -> Signal
14: Digital In Water -> Ref (GND)
15: Auxiliar In -> Signal
16: Auxiliar In -> Ref (GND)
17: Pressure alarm Out -> A
18: Pressure alarm Out -> B
19: Volume/Weight alarm Out -> A
20: Volume/Weight alarm Out -> B
21: Alarm Out CPU -> A
22: Alarm Out CPU -> B
23: Auxiliar Out-> A
24: Auxiliar Out-> B
25: Compressor out -> Phase
26: Compressor out -> Zero
27: Solenoid valve air Out -> Phase
28: Solenoid valve air Out -> Zero
29: Solenoid valve autofilling -> Phase
30: Solenoid valve autofilling -> Zero

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Connectors (control unit):
Connector 1
1. Ground
2. Phase
3. Neutral
4. COMPRESSOR Phase
5. COMPRESSOR Neutral
6. SOLENOID VALVE Air OUT phase
7. SOLENOID VALVE Air OUT neutral
8. Water IN Phase
9. Water IN AGUA neutral
Connector 2
1. Auxiliar relay AUX 1 A
2. Auxiliar relay AUX 1 B
3. Auxiliar relay AUX 2 A
4. Auxiliar relay AUX 2 B
5. Auxiliar relay AUX 3 A
6. Auxiliar relay AUX 3 B
7. DIGITAL IN 2 +
8. DIGITAL IN 2 –
9. DIGITAL IN 1 +
10. DIGITAL IN 1 –
Connector 3
1. LOAD CELL (-)
2. LOAD CELL (A)
3. LOAD CELL (B)
4. LOAD CELL (+)
5. Pressure IN 4/20 mA (+)
6. Pressure IN 4/20 mA (S)
7. Pressure. IN 4/20 mA (-)
8. Volume IN 4/20 mA (+)
9. Volume IN 4/20 mA (S)
10. Volume IN 4/20 mA (-)
Connector 4
1. Volume OUT 4 /20 mA (+)
2. Volume OUT 4 / 20 mA (S)
3. Volume OUT 4 / 20 mA (-)
4. Pressure OUT 4 / 20 mA (+)
5. Pressure OUT 4 / 20 mA (S)
6. Pressure OUT 4 / 20 mA (-)
7. GND
8. RS 485 GND
9. RS 485 B
10. RS 485 A
Connector 5
Ethernet
Box view from the back side

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Pre-Comissioning
Determine the position of the expansion vessel. It must be placed on a level ground or surface, or failing that,
proceed to level it correctly, in order to ensure the proper functioning of the vessel. It is important to do this
correctly so that the volume sensor can detect a third of the weight of the vessel and therefore, indicate the correct
volume. If the delivery includes more than one vessel, the "secondary" vessel does not have a volume sensor.
Check that the data collected on the sticker attached to the expansion vessel are in accordance with the purchase
specification and they are suitable for installation. Before proceeding with installation, make sure that the volume
of the expansion vessel has been calculated by authorized personnel, technical staff has an appropriate profile and
training in the facilities of this type of equipments. The local regulations for the operation of the expansion vessels
must be considered. The installation and operation must be carried out in accordance with good practices by
professional installers and authorized technical personnel.
The expansion vessel must be installed in an enclosure protected from the weather with necessary dimensions to
facilitate the inspection of the vessel from all parts, being the control unit, air filling valve, the connection sleeve
to the installation and label accessible. It should be located in the boiler room, well ventilated and with an ambient
temperature of 5 to 40 ° C. Check that there is enough space around the vessels and the pressure maintenance unit
to facilitate future maintenance and service work. It is not allowed to isolate any part of the equipment.
Make sure that the equipment has no marks, dents or signs of tampering.
Do not place any valve whose closing may unintentionally cancel the operation of the expansion vessel. It is
recommended to install traps and / or air separators to avoid air accumulation.
Avoid direct radiation on the expansion vessel to protect the membrane from possible excesses of temperature.
In closed heating systems, a warning should be visible next to the expansion vessel to indicate people who are in
danger because they are near surfaces with high temperatures.
Mounting air hose: If the equipment includes an extra or secondary vessel, mount the T-tube supplied with the
hose set, in the main vessel and the elbow coupling in the sleeve located in the upper part of the secondary vessel
(air side). If it is necessary to cut the connecting air hose of the two vessels, main and secondary use a sharp knife.
If is used other ripping tool, plastic chips can be appear and can enter in solenoid valve or other sensitive places
and cause unnecessary operating anomalies.
Attention: The pipes must be dimensioned and installed in accordance with the specific requirements
according to local and national regulations. Remember that the connection of pipes or equipment with the
system may cause additional stress to the device. Ensure a stress-free installation of the pipe connections
between the ex
p
ansion vessel and the s
y
stem.

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Being the valve that connects the expansion vessel with the closed heating system closed, install the expansion
vessel to the heating / cooling system using the flexible hose with elbow supplied. The angled end of the flexible
hose is screwed into water connection of the expansion vessel located in the lower part of the vessel and the
straight part of the flexible hose to the heating system.
Being closed the water passage valve between vessel al heating system, check that the manual air bleed valve on
the top of the vessel is closed through the hose fitted on the top cover. Also check that the valve in the lower part
of the tank (condensation water) is closed. It is preferable to fill the system with the valve closed.
Commissioning is easier when the vessel is empty.
Attention: If using a secondary expansion vessel in addition to the primary vessel, make sure that all
vessels have the same type and dimensions.
Before proceeding to parameterize the control unit, confirm that:
- The tank is empty of water.
- The heating system is completely filled with water.
- The control unit is connected to the expansion vessel.
- The water connections of the tanks to the system of facilities are established.
- The valves for emptying the tanks are open.
- The electrical connection has been created in accordance with applicable national and local regulations.

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Comissioning
Plug the connector to provide power (230 V) to the controller.
If this is the first time the control unit is used, you will be asked to calibrate the touch screen through 3 points.
Once calibrated, the following symbol appears in the screen
Once calibrated, the following symbol appears in the screen
Press the power icon (stand-by) for 2 seconds to start the unit.
The unit systematically goes through two initial screens.
The first time the unit is turned on, the LANGUAGE, DATE and HOUR SELECTION screen is accessed. By
default the starting language is English.
To select the language, click on the grid to the right of LANGUAGE SELECTION and select the desired
language from SPANISH (ESP), ENGLISH (ENG), SWEDISH (SE) and FRENCH (FRA).

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
In addition, if desired, data such as,
- DATE: Click on the grid to the right of DATE. A keyboard emerges that allows you to enter the date in
DDMMYY format (DayMayYear). It is validated by pressing the ENTER button.
- TIME: Press on the grid to the right of TIME, A keyboard emerges that allows you to enter the date in
HHMMSS format (HourMinuteSeconds). It is validated by pressing the ENTER button.
Once the previous values have been adjusted press the CONTINUE key.
If you are in the LANGUAGE SELECTION screen and do not press the touch screen in 5 minutes, the unit will
go directly to the MAIN screen. If you need to select the language again, you must turn off the control unit. To
do this, on the MAIN screen, press the stand-by icon, the power off button will appear in the center of the MAIN
screen. Press for 2 seconds to turn off the unit. To turn the control unit back on, press the Stand-by icon for 2
seconds.
After setting the language of the unit and pressing the CONTINUE key, the following CHECK LIST screen is
accessed, where a list of checks to be confirmed is displayed, before proceeding to adjust the parameters of the
control unit. Once the list is checked, press the ACCEPT key and continue with the configuration of the unit.
If you are on the CHECK LIST screen and do not press the touch screen in 5 minutes, the unit will go directly to
the MAIN screen. If you need to go through this CHECK LIST list again, you must turn off the control unit. To
do this, on the MAIN screen, press the stand-by icon, the power off button will appear in the center of the MAIN
screen. Press for 2 seconds to turn off the unit. To turn on the control unit again, press the Stand-by icon for 2
seconds. Once the ACCEPT key has been pressed, the screen called MAIN of the unit is accessed.

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
The control unit has 6 menus (Password 1861 configurable at client's choice).
M
ain Settin
g
sTes
t
Comm Even
t
I
n
f
o
To move or to modify the unit's parameters, a password is required. The default password is 1861 press ENTER.
Main: Shows in general the data of the selected model, setpoint values of the device as well as the status of the
alarms.
Settings (see units of measure): Divided into 3 sections. DEVICE, referring to the selection of the model to be
installed. PRESSURE, referring to the configuration of the air part of the equipment (compressor). VOLUME,
referring to the water part of the equipment (Load cell).
Test. Calibration of the Load cell, as well as manual check of the operation of the components associated with
the unit (compressor, air solenoid valve, automatic filling, as well as alarms).

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Comm. RS-485 and Ethernet communications configuration. Language selection and password change.
Event. It shows with date and time the events generated throughout the operation of the equipment. (Maximum
250 events)
Info. Shows the different processor parameters for information

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Language selection: For it, access to COMM Menu. Once COMM menu is selected, is need to enter the
PASSWORD. Press ENTER to validate access.
In the MISC section of the COMM menu
- LANGUAGE: Click on the box below the language and select the desired language between SPANISH (ESP),
ENGLISH (ENG), SWEDISH (SE) and FRENCH (FRA).
If you also want to establish,
- DATE: Click on the box below DATE and enter the desired date in DDMMYY format (DayMonthYear). It is
validated by pressing ENTER button.
- TIME: Press on the box below TIME, enter desired time in HHMMSS format (HourMinuteSecond). It is
validated by pressing ENTER button.
- SCREENSAVER: If you wish to set a time for activation of the SCREENSAVER, press on the box below the
SCREENSAVER, the keyboard appears and the desired time for activation is entered. Time between 1 minute
and 60 minutes. 0 (Zero) means SCREENSAVER disabled. It is validated by pressing ENTER button.
Expansion vessel: For it, access to SETTINGS Menu. Once SETTINGS menu is selected, is need to enter the
PASSWORD. Press ENTER to validate access.
SETTINGS menu is divided into 3 sections, DEVICE, PRESSURE and VOLUME

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Device: Configuration of the values corresponding to the selected expansion vessel model.
- MODEL: Click on the box MODEL, enter the desired model between, 200, 300, 500, 700, 1000, 1400, 2000,
3000, 5000, 200x2, 300x2, 500x2, 700x2, 1000x2, 1400x2, 2000x2, 3000x2 and 5000x2. By default the chosen
model is “NoDef” (Not Defined).
- V.SENS: Click on the box V.SENS, enter the desired type of VOLUME SENSOR between RES (Resistive)
and 4-20mA. By default the chosen V.SENS is RES.
- L.CELL: Click on the box T.CELL, enter the the admissible weight of the load cell. The values to select 500
Kg / 1000 Kg. By default the chosen load cell is 500 Kg.
- COMP: Click on the box COMP, enter the desired type of compressor. The possible values: 6/8 bar. By default
the chosen compressor is 6 Bar.
- RELAY 1: Press on the box RELAY 1, enter the desired type of alarm from the following options: NoDef,
HIGH AIR PRESSURE (ALrPH), LOW AIR PRESSURE ALARM (AlrPL), HIGH WATER VOLUME
ALARM (AlrVH), LOW WATER VOLUME ALARM (AlrVL), VOLUME ALARM (AlVol), PRESSURE
ALARM (AlPrs), COMPRESSOR ALARM (ALCmp), AUTOMATIC FILLING ALARM (AlAut), MANUAL
ALARM (AlMan). By default the chose alarm is "NoDef".
- RELAY 2: Press on the box RELAY 2, enter the desired type of alarm from the following options: NoDef,
HIGH AIR PRESSURE (ALrPH), LOW AIR PRESSURE ALARM (AlrPL), HIGH WATER VOLUME
ALARM (AlrVH), LOW WATER VOLUME ALARM (AlrVL), VOLUME ALARM (AlVol), PRESSURE
ALARM (AlPrs), COMPRESSOR ALARM (ALCmp), AUTOMATIC FILLING ALARM (AlAut), MANUAL
ALARM (AlMan). By default the chose alarm is "NoDef".
- RELAY 3: Press on the box RELAY 3, enter the desired type of alarm from the following options: NoDef,
HIGH AIR PRESSURE (ALrPH), LOW AIR PRESSURE ALARM (AlrPL), HIGH WATER VOLUME
ALARM (AlrVH), LOW WATER VOLUME ALARM (AlrVL), VOLUME ALARM (AlVol), PRESSURE
ALARM (AlPrs), COMPRESSOR ALARM (ALCmp), AUTOMATIC FILLING ALARM (AlAut), MANUAL
ALARM (AlMan). By default the chose alarm is "NoDef".

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
Pressure: Configuration of the values corresponding to the air side of the chosen expansion vessel.
- NOMINAL: Value of the nominal pressure or compressor stop pressure. Press on the box and enter the value of
the desired NOMINAL PRESSURE, between values from MIN 0.5 bar to MAX 5.0 bar. It is validated by
pressing ENTER button. By default the selected NOMINAL value is 1.5 bar.
Adjustment of pressurization values,
- HYSTER.: Pressure difference in BAR below which the compressor starts up until reaches the NOMINAL
pressure value or pressure difference above which the air solenoid valve is activated to expel air from the
expansion vessel until reaching the NOMINAL pressure. Click on the box and enter desired HYSTERESIS
value, between values from MIN 0.1 bar to MAX 1.0 bar. It is validated by pressing ENTER button. By default,
the selected HYSTER value is 0.0 bar.
- ALARM HIGH: Value of the pressure from which the LED on the MAIN screen is activated in red color, not
at all by high pressure. Optionally, RELAY1, RELAY2, RELAY3 can be used as a configuration of this type of
array to enable monitoring. The Screensaver in case of activation, will do in RED FLASHING. Click on the box
and enter the value of the desired ALARM HIGH value, between values 0.5 bar to 5.0 bar. It is validated by
pressing the ENTER button. By default the selected ALARM HIGH value is 5.9 bar.
- ALARM LOW: Value of the pressure from which the LED on the MAIN screen is activated in red color,
giving rise to an alarm due to low pressure. Optionally, RELAY1, RELAY2, RELAY3 can be used as a
configuration of this type of array to enable monitoring. The Screensaver in case of activation, will do in RED
FLASHING. Click on the box and enter the value of the desired ALARM LOW, between value from 0.5 bar to
5.0 bar. It is validated by pressing the ENTER button. By default the selected NOMINAL value is 1.0 bar.
Adjustment of pressurization values,
NOMINAL PRESSURE ≥PST / 10 + 0.6 Bar
being, PST the static height of the system in wmc.
It must be ensured that the maximum operating pressure of the
expansion vessel indicated on the sticker attached to the tank is
never exceeded.

PLENTZIA BIDEA, 3 BILLELA AUZOTEGIA
48100 MUNGIA- SPAIN
CRB AUTOMAT
- BLK.TIM: Value in seconds of the compressor BLOCKING TIME. By compressing the selected time the
compressor will stop giving rise to a monitoring alarm in case of selection in any of the RELAY1, RELAY2,
RELAY3. The Screensaver in case of activation, will do in RED FLASHING. Press on the box and enter the
value of COMPRESSOR BLOCKING, between values from 0 seconds to 999 seconds. It is validated by
pressing the ENTER button. By default, the selected value is 0 sec.
Volume: Configuration of the values corresponding to the water side of the chosen expansion vessel.
- NOMINAL: Value of the NORMAL volume of water of in %. Click on the box and enter the value of the
desired NOMINAL VOLUME. Values from MIN 20% to MAX 80%. It is validated by pressing the ENTER
button. By default, the selected NOMINAL value is 30%.
- ALARM HIGH: Value of the volume of water, from which the LED on the MAIN screen is activated in red
color, due to HIGH WATER VOLUME. The RELAY1, RELAY2, RELAY3 can be used as a configuration of
this type of array to enable monitoring. The SCREENSAVER in case of activation, will do in RED FLASHING.
Click on the BOX and enter the value of ALARM HIGH WATER VOLUME, between the values from MIN 1%
to MAX 99%. It is validated by pressing the ENTER button. By default, the ALARM HIGH value selected is
99%.
- ALARM LOW: Value of the volume of water, from which the LED on the MAIN screen is activated in red
color, due to LOW WATER VOLUME. The RELAY1, RELAY2, RELAY3 can be used as a configuration of
this type of array to enable monitoring. The SCREENSAVER in case of activation, will do in RED FLASHING.
Click on the BOX and enter the value of ALARM LOW WATER VOLUME, between the values from MIN 1%
to MAX 99%. It is validated by pressing the ENTER button. By default, the ALARM LOW value selected is
1%.
- AUTOFILLING: Click on the box and select YES or NO.
- TIME ACTIVATION: If AUTOFILL is selected YES, the TIME ACTIVATION will be the activation time in
seconds for the AUTOFILLING activation once it is activated with ALARM LOW. Click on the box and enter
the value of the desired TIME ACTIVATION, between value from 1 sec up to 60 secs. It is validated by
pressing the ENTER button.
In order for the AUTOFILL to be blocked, one of these two conditions must be met
- BLK.TIM: Value in minutes of the LOCKOUT TIME for the AUTOFILL of water. If value zero (0) means
OFF. (BLK. TIM: If the AUTOFILL once is activated above the BLK.TIM the AUTOFILL will be blocked, and
the control unit will go to MANUAL MODE).
- BLK.N: Number of activations of the AUTOFILLING of water for its blocking. If value zero (0) means OFF.
(BLK. N: If AUTOFILL is activated in one hour (1 hour), a number of times above BLK. N, AUTOFILL will be
b
locked, and the control unit will
g
o to MANUAL MODE).
Table of contents
Popular Industrial Equipment manuals by other brands

Danfoss
Danfoss Termix VVX-IV 7 Series operating guide

Honeywell
Honeywell Modutrol IV 41 Series instruction manual

STEPCRAFT
STEPCRAFT M Series Construction manual

Scotsman
Scotsman BL1048S Installation and user manual

Dustcontrol
Dustcontrol TPR 50 Original instructions

goodnature
goodnature AA-375R owner's manual