TH-100-EN54
4 605901 180100
Mounting Instruction
1. Attach two brackets each (WH left and WH right) to the ceiling using suitable fixing material
(not included in the delivery).
2. Then fix the speaker to the brackets with the M8x20 screws and the M8 washers. Please use
a torque of 16 Nm for tightening the screws of the bracket.
3. Feed the loudspeaker cable through the PG gland and connect the cable to the ceramic
clamp, according to the required power (see imprint on the clamp).
4. place the cover on the horn driver and fix it with the screws M8x25 and the steel and rubber
washers M8.
5. Tighten the screws of the rear cover of the horn driver in 2 steps:
1. Tighten all 8 screws with a torque of 2.0 Nm.
2. Retighten the screws with 2.0 Nm.
Should you use the TH-100-PH premium mounting, please refer to the corresponding installation
drawings.
Safety note: Due to the weight of the product, we recommend that the installation is carried out by 2
persons.
CE-Symbol according to 93/68EWG
Measurements according to DIN IEC
268-5
RoHS compliant (2011/65/EU)
CPR compliance according
305/2011/EU
Loudspeaker for voice alarm systems
for fire detection and fire alarm
systems for buildings
ic audio GmbH, Boehringerstraße 14A
D-68307 Mannheim, Germany
EN54-24:2008
Ref. Nr.:01T-15
ID-Code:SAA-
TH01
1438-CPR-
0481