1
INSTALLATION
INSTRUCTIONS
P/N PISVKITS-A
REV. B, 02/2015
DIRECT-VENT SYSTEM TO PREFABRICATED METAL CHIMNEY / MASONRY CHIMNEY
FOR DIRECT-VENT GAS BURNING STOVES AND FIREPLACE INSERTS
CAT. NUMBERS SV4MCK, SV4CCK1, SV4CCK2, SV4CCK3, SV4MCK, SV4FK, SV4FAK AND SV4FBK
SECURE VENT®CONVERSION KITS
VENTING INSTRUCTIONS
APPLICATION
Check the appliance manufacturer’s rating plate to confirm that
the SECURE VENT®system is approved for use on the appliance
you have selected.
IMPORTANT
Read all instructions carefully before starting the installation.
Failure to follow these instructions may create a fire or other
safety hazard, and will void the warranty. Be sure to check the
appliance manufacturer’s installation instructions for specific
venting and clearance to combustible requirements, which may
vary from one appliance to another.
RECOMMENDATIONS
• Foryoursafety,alwaysweargogglesandgloves.
• Makesuretolocatetheelectricwiresbeforedrillingthrough
the wall.
PLEASE KEEP THIS MANUAL FOR FUTURE REFERENCE
WARNING
• Itisofutmostimportancetomaintaintherequiredminimum
clearances to combustible materials for the unit and the
chimney system. These spaces must be unobstructed; do
not fill them with insulating material.
• Multipleventingintoacommonueisprohibited.
Innovative Hearth Products
1508 Elm Hill Pike, Suite 108
Nashville, TN 37210
www.IHP.us.com
US
Portland
fire-parts.com
2
TABLE OF CONTENTS GENERAL INFORMATION
........................................................... PAGE
Safety Precautions .....................................Cover Page
General Information ............................................... 2
Prefabricated Metal Chimney Kit Installation ................. 3
Masonry Chimney Kit Installation ............................... 4
General Maintenance ............................................. 5
Warranty ............................................................ 6
If you encounter any problems, need clarification of these
instructions or are not qualified to properly install this kit,
contact you local distributor or dealer.
Readthis manual in its entiretybefore beginning the installation.
ALL WARNINGS AND PRECAUTIONS IN THE INSTALLATION
AND OPERATIONMANUALSPROVIDEDWITHTHEAPPLIANCE
APPLY TO THESE INSTRUCTIONS.
The SECURE VENT®conversion kits are made to convert the
SECURE VENT standard 4-inch pipes to your existing prefab-
ricated metal chimney or masonry chimney.
The prefabricated metal chimney kits are available in three
sizes to fit most of the existing diameters. The minimum
inside diameter is 6”, while the maximum outer diameter is
12”. The venting system starts at the Direct-Vent gas ap-
pliance using SECURE VENT 4-inch black pipes. Then the
prefabricated metal chimney is used as the outer casing of
the venting system and the inner pipe is replaced by a 4-inch
flexible pipe through the metal chimney. The venting system
ends on the roof using SECURE VENT galvalume 4-inch pipe
and vertical termination cap. Two adaptors are included in the
kit to make the bond between the SECURE VENT pipe and the
prefabricated metal chimney.
The masonry chimney kit is available in one size that fits most
masonry chimneys. The procedure is basically the same as
for the prefabricated metal chimney kit. The venting system
starts at the Direct-Vent gas applia nce with SECURE VENT
4-inch black pipes. Then using the masonry chimney as the
outer casing and a 4-inch flexible pipe as the flue outlet, the
venting system ends on the top of the chimney with a flashing
and a vertical termination cap. Two adaptors are included in
this kit to make the bond between the SECURE VENT pipe and
the masonry chimney.
The two venting systems, prefabricated metal chimney and
masonry chimney, need to be sealed so the flow of air intake
depends only on the vertical termination cap. This will ensure
a performance very similar to a standard vertical installation
with 4-inch SECURE VENT pipes.
The gas appliance must be located according to the clearances
to the wall indicated in the manufacturer’s instruction manual.
Once the location of the appliance has been determined,
you will have to select the venting components required to
complete the installation. Refer to the appliance installation
manual for permissible vent configuration.
fire-parts.com
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3
PREFABRICATED METAL CHIMNEY KITS
INSTALLATION
NOTE:Theprefabricatedmetalchimneyueopeningneeds
to have an inside diameter of at least 6” to ensure proper
air intake.
1. Remove the prefabricated metal chimney termination cap
and sweep the chimney.
2. Measure the total length of your prefabricated chimney.
Add three inches to this length in order to obtain the overall
length of flexible pipe needed. The flexible pipe must be
fully stretched before cutting.
3. Using a tightening collar, join the flexible pipe to the cap
adaptor. Push the flexible pipe down to the stopper. Re-
align the tightening collar in the center of the stopper and
the end of the inner pipe of the cap adaptor. Seal the end
of the flexible pipe using the high temperature sealant
MILL-PAC.
4. Using a tightening collar, tie a 20 foot rope to the end of
the flexible pipe. First insert the rope into the prefabricated
metal chimney and then follow with the flexible pipe.
5. Apply a silicone sealant on top of the prefabricated metal
chimney. Then attach the cap adaptor to the prefabricated
metal chimney using metal screws.
6. Install the vertical termination cap on the cap adaptor. The
termination cap height must be in accordance with Table
1. If necessary, add a galvalume vent length to reach the
minimum height.
7. Using the rope, pull the flexible pipe inside the room. Then,
with a tightening collar join the flexible pipe to the flex black
adaptor. Seal the end of the flexible pipe using the high
temperature sealant MILL-PAC.
8. Using four black metal screws, attach the flex black adaptor
to the prefabricated chimney support. Align the adaptor
with the center of the prefabricated chimney. No air should
pass between the adaptor and the support. If necessary,
seal the joint with a silicone sealant.
9. Using a plumb line, align the flue of the appliance with
the flex adaptor. Insert the first black vent length on the
appliance outlet and secure it with two black screws. If
the appliance outlet does not fit the SECURE VENT twist
lock system, seal the inner and outer pipes with a high
temperature sealant such as MILL-PAC. Do not use a
silicone sealant. A minimum of 1-1/2” overlap is required.
10.Install black vent lengths until you reach the flex adaptor.
Slide the last vent length into the flex adaptor and attach it
on the preceding vent length. A minimum of 1-1/2” overlap
is required. Using 3 black metal screws, secure the last
vent length to the flex adaptor. The flex adaptor joint at the
inner pipe must be sealed with high temperature sealant
such as MILL-PAC, the joint at the outer pipe can be sealed
with a silicone sealant.
Figure 1
Figure 2
Cap Adaptor
(included)
Vertical Cap
SV4CGV (included)
4” Dia. Flexible Pipe
4F14/35
S.V. to Flex Black
Adaptor (included)
4” Diameter
S.V. Pipe
Tightening Collar
(included)
Roof Pitch Minimum Height (H)
Feet Meters
Flat to 7/12 1.0 0.3
Over 7/12 to 8/12 1.5 0.46
Over 8/12 to 9/12 2.0 0.61
Over 9/12 to 10/12 2.5 0.76
Over 10/12 to 11/12 3.25 0.99
Over 11/12 to 12/12 4.0 1.22
Over 12/12 to 14/12 5.0 1.52
Over 14/12 to 16/12 6.0 1.83
Over 16/12 to 18/12 7.0 2.13
Over 18/12 to 20/12 7.5 2.29
Over 20/12 to 21/12 8.0 2.44
Table 1
H
fire-parts.com
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
4
MASONRY CHIMNEY KITS INSTALLATION
NOTE:Themasonrychimneyueopeningneedstohavean
area of at least 35 square-inches to ensure proper air intake.
1. The chimney must be clean and in good working order and
constructed of non-combustible materials. Also, make sure
that the masonry chimney walls are air-tight.
2. Insert the first vent length on the appliance outlet and se-
cure with two screws. If the appliance outlet does not fit
the SECURE VENT®twist lock system, seal the inner and
outer pipes with a high temperature sealant such as MILL-
PAC. Do not use a silicone sealant. A minimum of 1-1/2”
overlap is required. Install the remaining vent lengths.
3. Drill a hole of 6-1/2” minimum (7” maximum) in the ma-
sonry chimney (and the concrete) aligned with the center
of the horizontal vent. If there is a finishing wall before
the concrete, cut and frame a hole of 10-3/8” x 10-3/8”
(see Figure 5). A horizontal vent run should be level; the
maximum rise allowed is 1/4” per linear foot.
4. Determine the length of flexible pipe needed by adding the
following distances: from the hole previously drilled to the
chimney top, from the inner face of the concrete to the
chimney center and finally add 5”. The flexible pipe must
be fully stretched before cutting.
5. Put the masonry cover on the chimney top. If the cover is
larger than the chimney, cut the four corners of the cover
then fold them on the chimney wall. Apply a silicone
sealant between the cover and the chimney top. Drill four
holes through the masonry cover and into the chimney top.
Insert screw anchor in the masonry chimney, then fasten
the cover with screws.
6. Using a tightening collar, join the flexible pipe to the cap
adaptor. Push the flexible pipe down to the stopper. Re-
align the tightening collar in the center of the stopper and
the end of the inner pipe of the cap adaptor. Seal the end
of the flexible pipe using the high temperature sealant
MILL-PAC.
7. Using a tightening collar, tie a 20 foot rope to the end of
the flexible pipe. First insert the rope into the masonry
chimney and then the flexible pipe.
8. Put the cap adaptor over the hole of the masonry cover.
Fasten the cap adaptor to the masonry cover using three
metal screws. Seal the joint with a silicone sealant. Install
the vertical termination cap on the cap adaptor.
9. Using the rope, pull the flexible pipe inside the room. Then,
with a tightening collar join the flexible pipe to the flex black
adaptor. Seal the end of the flexible pipe using the high
temperature sealant MILL-PAC.
Figure 3
Figure 4
Masonry Cover
Apply Sealant
4” Dia. Flexible Pipe
4F14/35
Masonry Cover
(included)
Cap Adaptor
(included)
Vertical Cap
SV4CGV (included)
Concrete
Tightening Collar
(included)
S.V. to Flex Black
Adaptor (included)
4” Diameter
S.V. Pipe
fire-parts.com
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
5
MASONRY CHIMNEY KITS INSTALLATION (con’t) GENERAL MAINTENANCE
10.Using four masonry screws, attach the flex black adaptor
to the masonry chimney. Align the adaptor with the hole.
Seal the joint with a silicone sealant. If there is a finishing
wall before the concrete, slide the decorative plate over the
flex black adaptor and fasten it to the wall using four black
screws.
11.Move the appliance to the intended location and slide the
last vent length into the flex adaptor. A minimum of 1-1/2”
overlap is required. Using 3 black metal screws, secure
the last vent length to the flex adaptor. The flex adaptor
joint at the inner pipe must be sealed with high temperature
sealant such as MILL-PAC. The joint at the outer pipe can
be sealed with a silicone sealant.
Decorative Plate
SV4PF (included)
S.V. to Flex Black
Adaptor (included)
Figure 5
The following inspection should be performed after the installa-
tion of your vent system and subsequently examined annually.
1. Ensure that every joint of the vent system is properly
locked; the threads must be aligned with the arrows.
2. Make sure the roof support and the wall bands are properly
fixed to the frame and vent.
3. Check the outer flue of the vent system to detect any sign
of serious corrosion.
4. Remove the termination cap. Make sure there is no
obstruction that could block the flow of combustion and
ventilation air.
5. Using a flashlight, verify that the flexible pipe is still at-
tached to the cap adaptor.
6. Make sure that the venting system is air sealed. Verify that
the black flex adaptor and the cap adaptor joints with the
prefabricated metal chimney or the masonry chimney are
still sealed.
fire-parts.com
6
NOTES
fire-parts.com
7
Printed in U.S.A. © 2014 IHP LLC
P/N 900250-00 Rev. NC 03/2014
Innovative Hearth Products
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
INNOVATIVE HEARTH PRODUCTS
SECURE VENT® CHIMNEY & VENTING PRODUCT
LIMITED LIFETIME WARRANTY
THE WARRANTY
This Innovative Hearth Products (IHP) Limited Lifetime Warranty warrants your residential vent and/or chimney system to be free from defects in material and workmanship
at the time of manufacture. This Limited Lifetime Warranty includes all components and fittings, except termination caps. After installation, if covered components manu-
factured by IHP are found to be defective in materials or workmanship during the Limited Lifetime Warranty period and while the Product remains at the site of the original
installation, IHP will, at its option, replace the covered components. IHP reserves the right to replace covered components with an equivalent product and the replacement
must be carried out in accordance with IHPs recommendations. If replacement is not commercially practical, IHP will, at its option, refund the purchase price or wholesale
price of the IHP product, whichever is applicable. Labor to replace IHP components is not included. THERE ARE EXCLUSIONS AND LIMITATIONS to this Limited Lifetime
Warranty as described herein.
COVERAGE COMMENCEMENT DATE
Warranty coverage begins on the date of installation. In the case of new home construction, warranty coverage begins on the date of first occupancy of the dwelling or six
months after the sale of the Product by an independent IHP dealer/distributor, whichever occurs earlier. The warranty shall commence no later than 24 months following
the date of product shipment from IHP, regardless of the installation or occupancy date.
EXCLUSIONS AND LIMITATIONS
This Limited Lifetime Warranty applies only if the Product is installed in the United States or Canada and only if used for the application for which it was designed and
intended. The Product must be maintained in accordance with the printed instructions accompanying the Product and in compliance with all applicable installation and
building codes and good trade practices.
This warranty is non-transferable and extends to the original owner only. The Product must be purchased through a listed supplier of IHP and proof of purchase must be
provided. IHP will be responsible for the replacement of the residential vent and/or chimney system considered to be defective for the following periods:
Termination Caps – Replacement at no charge for 5 years from the date of installation, excluding labor
Components and ttings (excludes termination caps and labor) –
Year 1-10 – Replacement of all components and fittings.
Year 11-15 – Replacement at 75% off of the prevailing list price in effect at the time of replacement (25% of the retail list price paid by the consumer).
Year 16 + – Replacement at 50% off of the prevailing list price in effect at the time of replacement (50% of the retail list price paid by the consumer).
IHP will not be responsible for: (a) damages caused by normal wear and tear, corrosion from salt air, accident, riot, fire, flood or acts of God; (b) damages caused by abuse,
negligence, misuse, or unauthorized alteration or repair of the Product affecting its stability or performance. (The Product must be subject to normal use with approved fuels
listed in the Operation Manual provided with the product. Where applicable, fuel products with abnormal burning characteristics, including but not limited to fuel such as
driftwood, plywood and wood products using a binder may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly;
(c) damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product; (d) damages, repairs or inefficiency
resulting from faulty installation or application of the Product.
This Limited Lifetime Warranty covers only parts as provided herein. IHPs entire liability is limited to the purchase price of this product. In no case shall IHP be responsible
for materials, components or construction which are not manufactured or supplied by IHP or for the labor necessary to install, repair or remove such materials, components
or construction. Additional utility bills incurred due to any malfunction or defect in equipment are not covered by this Limited Lifetime Warranty. All replacement or repair
components will be shipped F.O.B. from the nearest stocking IHP factory.
LIMITATION ON LIABILITY
It is expressly agreed and understood that IHP’s sole obligation and the purchaser’s exclusive remedy under this warranty, under any other warranty, expressed or implied,
or in contract, tort or otherwise, shall be limited to replacement, repair, or refund, as specified herein.
In no event shall IHP be liable for any incidental or consequential damages caused by defects in the Product, whether such damage occurs or is discovered before or after
replacement or repair, and whether such damage is caused by IHP’s negligence. IHP has not made and does not make any representation or warranty of fitness for a particular
use or purpose, and there is no implied condition of fitness for a particular use or purpose.
IHP makes no expressed warranties except as stated in this Limited Lifetime Warranty. The duration of any implied warranty is limited to the duration of this expressed warranty.
No one is authorized to change this Limited Lifetime Warranty or to create for IHP any other obligation or liability in connection with the Product. Some states and provinces
do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. The provisions of this Limited
Lifetime Warranty are in addition to and not a modification of or subtraction from any statutory warranties and other rights and remedies provided by law.
INVESTIGATION OF CLAIMS AGAINST WARRANTY
IHP reserves the right to investigate any and all claims against this Limited Lifetime Warranty and to decide, in its sole discretion, upon the method of settlement.
To receive the benefits and advantages described in this Limited Lifetime Warranty, the appliance must be installed and repaired by a licensed contractor approved by IHP.
Contact IHP at the address provided herein to obtain a listing of approved dealers/distributors. IHP shall in no event be responsible for any warranty work done by a
contractor that is not approved without rst obtaining IHP's prior written consent.
HOW TO REGISTER A CLAIM AGAINST WARRANTY
In order for any claim under this warranty to be valid, you must contact the IHP dealer/distributor from which you purchased the product. If you cannot locate the dealer/
distributor, then you must notify IHP in writing. IHP must be notified of the claimed defect in writing within 90 days of the date of failure. Notices should be directed to the
IHP Warranty Department at 1508 Elm Hill Pike, Suite 108; Nashville, TN 37210.
fire-parts.com
8
Printed in U.S.A. © 2000 Innovative Hearth Products
P/N PISVKITS-A Rev. B 02/2015
IHP reserves the right to make changes at any time, without notice, in design, materials,
specifications, prices and also to discontinue colors, styles and products. Consult your local
distributor for fireplace code information.
1508ElmHillPike,Suite108•Nashville,TN37210
fire-parts.com

This manual suits for next models

6

Other IHP Fan manuals

IHP VENT-KIT-6X12 User manual

IHP

IHP VENT-KIT-6X12 User manual

Popular Fan manuals by other brands

RITE-HITE Revolution HVLS Fan owner's manual

RITE-HITE

RITE-HITE Revolution HVLS Fan owner's manual

Vornado 4T user manual

Vornado

Vornado 4T user manual

Teral CTFII instruction manual

Teral

Teral CTFII instruction manual

Holmes HCF0611A owner's manual

Holmes

Holmes HCF0611A owner's manual

EDM 33936 instruction manual

EDM

EDM 33936 instruction manual

Turbonics Kickster KWM Series installation instructions

Turbonics

Turbonics Kickster KWM Series installation instructions

Greenheck Series L Installation, operation and maintenance manual

Greenheck

Greenheck Series L Installation, operation and maintenance manual

Ayce FD-40M Original instruction

Ayce

Ayce FD-40M Original instruction

Vents-us TwinFresh Comfo RA1-50 user manual

Vents-us

Vents-us TwinFresh Comfo RA1-50 user manual

Ebmpapst W3G800-KU21-03 operating instructions

Ebmpapst

Ebmpapst W3G800-KU21-03 operating instructions

Acqua AC-MGD2 instruction manual

Acqua

Acqua AC-MGD2 instruction manual

Vents TwinFresh Comfo RA1-50 user manual

Vents

Vents TwinFresh Comfo RA1-50 user manual

Lorell 44551 operating instructions

Lorell

Lorell 44551 operating instructions

Objecto FLOW F1 user manual

Objecto

Objecto FLOW F1 user manual

Skov DA 820 LPC Technical user guide

Skov

Skov DA 820 LPC Technical user guide

colt CYCLONE installation manual

colt

colt CYCLONE installation manual

Dantherm HCC 2 ALU Service manual

Dantherm

Dantherm HCC 2 ALU Service manual

Greenwood Unity CV2GIP Homeowner's guide

Greenwood

Greenwood Unity CV2GIP Homeowner's guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.