16 - IE
INSTALLATORUSERTECHNICIAN
Ignition of the boiler (Fig. 2-1). Before ignition,
make sure the heating system is lled with water
and that the manometer (7) indicates a pressure
of 1 ÷ 1.2 bar.
- Open the gas cock upstream from the boiler.
- Press key (2) and select the summer position
or winter ( ) position of the boiler ( ).
When in summer position( ) the domestic
hot water temperature is regulated by keys (3-4).
When in winter position ( ) the system water
temperature is regulated by keys (5-6) whilst the
regulation of the domestic hot water temperature
is regulated using keys (3-4), pressing (+) to
increase and (-) to reduce.
From this moment the boiler functions auto-
matically. With no demand for heat (heating or
domestic hot water production) the boiler goes
to “standby” function, equivalent to the boiler
being powered without presence of ame. Each
time the boiler ignites, the relative ame present
symbol is displayed (15).
2.4 FAULT AND ANOMALY SIGNALS.
e boiler signals out anomalies by ashing on
the display and relative error codes, listed on the
table, are displayed.
Anomaly signalled
code
displayed
(ashing)
Ignition block 01
Safety thermostat block (over-
temperature), ame control
anomaly
02
Electro-mechanical contacts 04
Delivery probe anomaly 05
Domestic hot water probe
anomaly 06
Insucient system pressure 10
Fumes pressure switch failure 11
Parasite ame 20
Insucient circulation 27
Extruder presence 28
Communication loss with
CRD 31
Ignition block. e boiler ignites automatically
with each demand for room heating or hot
water production. If this does not occur within
10 seconds, the boiler goes into ignition block
(code 01). To eliminate “ignition block” the Reset
button (1) must be pressed. On commissioning
or aer extended inactivity it may be necessary
to eliminate the “ignition block”. If this pheno-
menon occurs frequently, contact a qualied
technician for assistance (e.g. Immergas Aer-
Sales Technical Assistance Service).
Over temperature thermostat block. During
normal functioning, if a fault causes excessive
overheating internally, the boiler goes into over
temperature block (code 02). Aer allowing to
cool, eliminate the “overtemperature block” by
pressing the Reset key (1). If this phenomenon
occurs frequently, contact a qualied technician
for assistance (e.g. Immergas Aer-Sales Tech-
nical Assistance Service).
Electro-mechanical contacts is occurs when
the safety thermostat, the fume pressure switch or
the system pressure switch do not work properly
(code 04). Try resetting the boiler. If the anomaly
continues contact a qualified technician for
assistance (e.g. Immergas Aer-Sales Technical
Assistance Service).
Delivery probe anomaly If the board detects an
anomaly on the delivery probe (code 05), the boi-
ler will not start; contact a qualied technician for
assistance (e.g. Immergas Aer-Sales Technical
Assistance Service).
Domestic hot water probe anomaly. If the board
detects an anomaly on the delivery probe (code
06), the boiler will not start; contact a qualied
technician for assistance (e.g. Immergas Aer-
Sales Technical Assistance Service).
Insucient system pressure. Water pressure
inside the heating system (code 10), sucient to
guarantee the correct functioning of the boiler,
is not detected. Check that the system pressure
is between 1÷1.2 bar.
Fumes pressure switch failure. is occurs if the
intake or exhaust pipes are blocked or in case of
a fan fault (code 11). If normal conditions are
restored the boiler restarts without having to be
reset. If this anomaly persists, contact a qualied
technician for assistance (e.g. Immergas Aer-
Sales Technical Assistance Service.)
Parasite ame. is occurs in case of a leak on
the detection circuit or anomaly in the ame
control unit. (code 20), try to reset the boiler.
If the anomaly continues contact a qualified
technician (e.g. Immergas Aer-Sales Technical
Assistance Service).
Insucient water circulation. is occurs if
there is overheating in the boiler due to insuf-
cient water circulating in the primary circuit
(code 27); the causes can be:
- low circulation; check that no shut o devices
are closed on the heating circuit and that the
system is free of air (deaerated);
- circulating pump blocked; free the circulating
pump.
If this phenomenon occurs frequently, contact a
qualied technician for assistance (e.g. Immergas
Aer-Sales Technical Service).
Domestic hot water extruder circuit. If during
the heating phase, a rise in domestic hot water
temperature occurs, an anomaly is signalled (code
28) and heating temperature is reduced to limit
the formation of lime scale in the heat exchanger.
Check that all domestic hot water system cocks
are closed and are not drawing and check also
that there are no leaks in the system. Once good
conditions are restored in the domestic hot water
system, the boiler returns to normal functioning.
If this anomaly persists, contact a qualied tech-
nician for assistance (e.g. Immergas Aer-Sales
Technical Assistance Service).
Loss of Digital Remote Control communica-
tion. is occurs 1 minute aer communication
loss between the boiler and the CRD (code 31).
To reset the error code, remove and re-apply
power to the boiler. If this phenomenon occurs
frequently, contact a qualied technician for
assistance (e.g. Immergas Aer-Sales Technical
Assistance Service).
Boiler shutdown Press key (2 Fig. 2-1) (
) until the following symbol appears
().
N.B.: in these conditions the boiler is considered
still powered.
Disconnect the external omnipolar boiler switch
and close the gas cock upstream of the appliance.
Never leave the boiler switched on if le unused
for prolonged periods.
2.5 RESTORE HEATING SYSTEM
PRESSURE.
Periodically check the system water pressure.
e boiler pressure gauge should read a pressure
between 1 and 1.2 bar.
If the pressure is below 1 bar (with the circuit cool)
restore normal pressure via the cock located in the
lower part of the boiler (Fig. 2-2).
N.B.: close the cock aer the operation.
If pressure values reach around 3 bar
the safety valve may be activated.
In this case contact a professional technician
for assistance.
In the event of frequent pressure drops, contact
qualified staff for assistance to eliminate the
possible system leakage.
2.6 DRAINING THE SYSTEM.
To drain the boiler, use the special drain cock
(Fig. 1-33).
Before draining, ensure that the lling cock is
closed.
2.7 ANTIFREEZE PROTECTION.
e boiler is supplied with an antifreeze function
as per standard that activates the function of the
pump and the burner when the internal system
water temperature in the boiler falls below 4 °C
(protection range to a minimum temperature
of -5°C) and stops when it exceeds 42°C. e
antifreeze function is guaranteed if the boiler
is fully operative, is not in “block” status and is
electrically powered. To avoid keeping the system
switched on in case of a prolonged absence, the
system must be drained completely or antifreeze
substances must be added to the heating system
water. In both cases the boiler domestic hot water
circuit must be drained. In systems that are drai-
ned frequently, lling must be carried out with
suitably treated water to eliminate hardness that
can cause lime-scale.
All information relative to the anti-freeze protec-
tion is stated in Par. 1.4. In order to guarantee the
integrity of the appliance and the domestic hot
water heating system in zones where the tempera-
ture falls below zero, we recommend the heating
system is protected using anti-freeze liquid and
installation of the Immergas Anti-freeze Kit in
the boiler (Par. 1.4). In the case of prolonged
inactivity (second case), we also recommend that:
- disconnect the electric power supply;
- drain completely the boiler domestic hot water
circuit using the exhaust valves provided (Fig.
1-33) and the internal domestic hot water
system.