VICTRIX PRO 80 1 I -100 1 I - 120 1 I
6
2 VICTRIX PRO 80 1 I100 1 I120 1 I SPECIFICATIONS
Wall-hung, open-chamber and fan-assisted pre-mixed con-
densing boilers, high eciency with forced circulation, with a
maximum heat output for 50/30°C of:
VICTRIX PRO 80 1 I = 80.3 kW (68.994 kcal/h),
VICTRIX PRO 100 1 I = 98.8 kW (84.942 kcal/h),
VICTRIX PRO 120 1 I = 121.7 kW (104.682 kcal/h);
Type-approved for installation in heating control unit and
outside the building without any additional protection (in the
open), it can be used in two congurations:
Open chamber and fan assisted (appliance type B23p/B33/
B53p)- No additional kit is required for this factory-supplied
conguration.
Sealed chamber and fan assisted (appliance type C13/C33/C63)
- Only using the vertical or horizontal concentric kits.
e boiler is made up from:
• total pre-mixing combustion system with metal-bre steel
multigas cylindrical burner, complete with ignition electrodes
and ionisation control;
• pneumatic gas valve with double shutter;
• primary gas/water heat exchanger with stainless steel double
overlapping coil with safety thermofuse and automatic air vent
valve, composed of:
VICTRIX PRO 80 1 I = 12 elements (8+4 ue side),
VICTRIX PRO 100 1 I = 16 elements (10+6 ue side),
VICTRIX PRO 120 1 I = 18 elements (12+6 ue side);
• combustion chamber in stainless steel internally isolated using
ceramic panels;
• fan for ue evacuation with electronically variable speed;
• circuit for disposal of condensate including trap and exible
drain hose;
• hydraulic unit comprised of ow manifold, circulation pump
and automatic air vent valve;
• 4 bar safety valve and standard draining funnel;
• water overheating safety thermostat;
• ue control probe;
• control panel supplied with P.C.B. with microprocessor with
continuous ame modulation on heating with P.I.D. control,
modulation eld referring to 50/30 °C between:
8.1 to 80.3 kW (between 6.983 and 68.994 kcal/h)
VICTRIX PRO 80 1 I;
10.5 to 98.8 kW (between 9.023 and 84.942 kcal/h)
VICTRIX PRO 100 1 I;
12.2 to 121.7 kW (between 10.520 and 104.682 kcal/h)
VICTRIX PRO 120 1 I;
• system ow regulation probe;
• system return regulation probe;
• heating ow temperature with factory setting between 25 and
85°C;
• ignition delay device in central heating phase, antifreeze
protection, pump anti-blocking function, chimney sweep
function;
• control panel composed of main switch, C.H. system pressure
gauge, multifunction back-lit display and 7-key push button
panel with protective sliding door;
• setting and adjusting boiler operation parameters through
the following keys: C.H. temperature adjustment buttons,
D.W.H. temperature adjustment buttons, summer / winter
mode button, reset button, info, parameter conrmation and
multi-function button (anomaly records, D.W.H. exclusion);
• self-diagnosis system with digital display of the temperature,
functioning status and error codes;
• IPX5D electrical insulation level, with possibility of installation
outside without any additional protection (in the open);
• antifreeze protection to -5 °C as per standard (-15 °C with
relevant kit optional);
• set-up for the connection of the cascade and zone regulator
and of the external probe;
• set-up for connection to an external 3-way valve with 230 Vac
power supply, for coupling to a separate storage tank unit for
the production of D.W.H.;
• set-up for functioning in cascade conguration (up to 5 boilers
with a unique safety devices kit);
• set-up for the installation of the safety stub pipes, both in single
and cascade conguration (up to 5 boilers);
• possibility of installation with the supporting frame kit in "free
standing" mode, which can be used to install one or more
VICTRIX PRO 1 I without having to mount the boilers directly
on the wall. e frame is also suitable for outdoor installation,
in the open;
• possibility of connecting (in combination with a cascade and
zone regulator) to a remote management system for remote
management of the system (optional);
• it can be combined with the system by Ø 80 mm exible duct-
ing (single installation).
Supplied with sample points for combustion analysis, bottom
protective metal-sheet plate grid and gas interception cock.
Category II appliance2H3P
, operates with natural gas and L.P.G.
CE Marking.
It is available in the model:
• VICTRIX PRO 80 1 I code 3.024490
• VICTRIX PRO 100 1 I code 3.024491
• VICTRIX PRO 120 1 I code 3.024492
NOTA BENE: for correct installation of the boiler the Immergas
"Green Range" air intake/fumes exhaust kit must be used and
however, dedicated for the VICTRIX PRO 1 I boiler, whether in
single or cascade conguration (battery).