Imtex-Controls VSD-IOM-002 User manual

!
7b
7c
7d
11
10
17
16
12
5
7
1
2
2a
9
20
15
19
14
13
14a
15a
15b
18
Button A
Button B
3
4
Type VSD Valve Controllers are designed to provide high accuracy feedback of valve position with comprehensive diagnostics, including Partial
Stroke Testing (PST). This document, outlines the essential safety information for installing the device, connecting into the device (including
connecting the primary solenoid) and the connection to and setting of the independent feedback systems. Additional connections to and operation
of the Valve Diagnostic/PST system within the device are covered by document VSD-IOM-001.
Installation - Mounting
Attach mounting plate (1) to the actuator using fasteners (2) and lockwashers (2a) provided with mounting kit (if supplied by Imtex).
Loosen indicator cover set screw (3) and rotate indicator cover (4) to desired viewing angle. Retighten set screw (3).
Fit VSD assembly to actuator ensuring that the NAMUR coupler (7) engages the shaft of the actuator (9). If a torque coupler (7a) is
used instead of the NAMUR Coupler on Non-NAMUR actuators, ensure this is securely fitted to the underside of the controller using the screw,
flatwasher and lockwasher supplied (7b/7c/7d) before fitting over the flats on the actuator shaft (9).Secure the assembly using the screws (10) and
lockwashers (11) provided with the mounting kit. Eccentricity of the shaft must not exceed 0.25mm.
If it should be necessary, re-align controller by loosening mount screws (10). Retighten screws when satisfied with alignment.
Fine tune the indicator cover (4) by loosening set screw (3). Retighten set screw when completed.
Installation - Wiring and Setting Internally Wired Transmitter and Independent Switches
Once the controller is fitted to the actuator, remove cover (12) by loosening 2 x cover lock screws (13).
Bring field wiring into the enclosure via the conduit entries (14) fitted with a suitable cable gland. Use blanking plugs to block off any un-used cable
entries. If wiring in the actuator solenoid(s) or additional components, bring these into the enclosure using conduit entries 14a to facilitate wiring.
NOTE: Suitable IP6x rated cable glands, blanking plugs and thread adaptors must be used to maintain controller IP rating. On flameproof enclosures,
only ATEX/IECEx certified Exd cable gland, blanking plugs and thread adaptors can be used. Blanking plugs must not be used with a gland adaptor.
Connect wiring to the terminals (15, 15a, 15b) within the enclosure according to the wiring diagram and terminal labelling. Connect earth conductor
(which forms part of the supply cable and MUST be at least equal to the size of the phase conductors ) to the internal earth points (18). Connect
the external earth/equipotential bonding conductor to the controller using the external earth clamp assembly(19). Conductor should be 4mm2 (min)
The next stage of the installation requires the actuator to be stroked. This can be done in a number of ways depending on the configuration of the
controller installed. Document VSD-IOM-001 covers how the actuator might be stroked using the controller. Otherwise, the actuator canbe stroked
using the solenoid(s) backwired into the controller as operated from the control room, (may require a seperate 24VDC power supply to be connected
depending on unit supplied).
The internally wired transmitter is factory set to provide feedback for 90 degree rotation - clockwise to close. If required, the internally wired transmitter
can be re-programmed.
NOTE: THIS SHOULD ONLY BE DONE IF CONFIDENT THE TRANSMITTERREQUIRES RESETTING BECAUSE IT IS
PROVIDING AN INVERTED SIGNAL.
Clear the transmitter (20) programming by pressing and holding buttons 'A' and 'B' for 2 seconds until the LED
blinks. Drive the actuator to closed position. Press and hold button 'A' for 2 sec until it blinks. Drive the actuator to open position. Press and hold
button 'B' for 2 sec until it blinks.
For controllers fitted with standard cam/spline activated switches/sensors, drive the actuator to the first required indication position and
set the bottom switch by lifting and rotating the bottom cam (16). Secure the cam by allowing it to fully re-engage with the spline (17).
Repeat the process for each switch in-turn by lifting/pushing down the appropriate cam, rotating and re-engaging as desired position is reached.
For controllers with barrel or slotted sensors, or with a transmitter, consult page 2 of these instructions for 'Further Setting Instructions'.
Once completed, verify that indication is as required by fully stroking the actuator. Then refit cover (12) and secure using the 2 x cover lock screws (13).
SPECIAL CONDITIONS FOR SAFE USE OF CERTIFIED ENCLOSURES - ATEX / IECEx
Installation should be carried out by suitably trained personnel to an applicable Code of Practice (eg IEC/EN60079-14 & IEC/EN61241-14).
Only suitably IP and Exd certified and temperature rated cable glands, thread adaptors and blanking plugs are permitted for use
with ATEX/IECEx flameproof enclosures.
The equipment shall not be subjected to a build up of dust and is to be cleaned regularly to prevent dust build up forming on the enclosure.
Where intrinsically safe components are fitted and are to be used within an Intrinsically Safe Circuit, they MUST be supplied by an
ATEX/IECEx approved barrier that is suitable to work with Input Parameters of the respective components
WARNING - For units operating at +85
C, cable, cable glands or conductors in conduit shall be rated +100
C (minimum).
WARNING - Monitor includes external plastic parts and presents an Electrostatic Hazard: Clean Only with a Damp Cloth.
WARNING - Do not install on an external source of heating or cooling e.g. by hot/cold air blowing temperature units
WARNING - Locate monitor to prevent propagating brush discharges
WARNING - Monitor should not be opened when energised or an explosive atmosphere may be present. The cover
screws (13) must be loosened before opening and re-tightened before the controller re-enters service.
The maximum constructional gap (i
C
) is less than that required by
Table 1 of IEC 60079-1:2007 clause 5.2.2 as detailed below:
Flamepath - Through Shaft
Max Gap (mm) - 0.07
Comment - Cylindrical Spigot Joint
Item 7a
REV
DATE
TITLE:
DWG NO.
SHEET 1 OF 3
VSD-IOM-002
Installation, Operating & Maintenance
VSD - IECEx/ATEX
Imtex Controls Limited
CHK'D
ECO
Tel:+44(0)8700-340002
Website: www.imtex-controls.com
13-2019
Additional Instructions for Safe Use
The certification for this monitor relies upon the following materials used in its construction:
- Stainless Steel
- EDPM 70
If the equipment is likely to come into contact with aggressive substances, then it is the responsibility
of the user to take suitable precautions that prevent it from being adversely affected, thus ensuring
that the type of protection provided by the equipment is not compromised. Aggressive substances
might be: acidic liquids or gases that attack Stainless Steel, or direct and prolonged contact with some
Hydrocarbons that could affect the seals. Regular checks/inspections should be carried out if aggressive
substances are present.
Instructions
Reference Diagram
DRAWN
28.2.13
PT
B
17-2618
14.2.17
A
PT
REV
STATUS
R
18-2692
1.2.18
PT
B

!
!
Warning: Electrostatic Hazard - See Instructions
Model:
Serial:
IQ
INTRINSICALLY SAFE COMPONENTS (connect to safe area via Certified Barrier):
WARNING: DO NOT OPEN WHEN ENERGISED OR WHEN AN
EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
TYPE VSD
Valve Controller
IEC CERTIFICATE NO: IECEx TRC 13.0004X
ATEX CERTIFICATE NO: TRAC13ATEX0005X
Tonbridge - TN11 0AH - UK
www.imtex-controls.com
WARNING: FOR T
amb
+85
C, CABLE GLANDS OR CONDUCTORS IN
CONDUIT ENTRIES SHALL BE RATED +100
C (MIN)
II 2 GD
CONSULT INSTRUCTIONS PRIOR
TO INSTALLATION, OPERATION
or MAINTENANCE
0518
Exd [ib] IIC T4 Tamb = -
C to +85
C Gb & Ex tb IIIC T135
C Db IP6X
Exd [ib] IIC T6 Tamb = -
C to +60
C Gb & Ex tb IIIC T85
C Db IP6X
INTRINSICALLY SAFE INFORMATION:
U
i
I
i
P
i
C
i
L
i
V
mA
W
nF
µH
(1) 3/4"NPT / (5) 1/2" NPT
(3) 3/4"NPT / (3) 1/2" NPT
(1) M25 x 1.5 / (5) M20 x 1.5
(2) M25 x 1.5 / (4) M20 x 1.5
T
(2) 3/4"NPT / (4) 1/2" NPT
S
U
ENTRIES SUPPLIED
DIGIT
Y
(3) M25 x 1.5 / (3) M20 x 1.5
V
(6) 1/2" NPT
W
(6) M20 x 1.5
X
Z
ENTRIES SUPPLIED
DIGIT
CABLE ENTRY GUIDE
A
Barrel Sensor
16
Barrel/Slot Sensor Setting
Drive the actuator to the first required indication position and set the first switch
by pushing round the lower metal shim on the shaft (16) to cover the sensor.
Repeat the process for each sensor in-turn by driving the actuator to the indication
position and adjusting the appropriate shim to cover the corresponding sensor.
Independent Transmitter Setting
NOTE: The Type VSD Transmitter is factory set to provide position information over
a 90 Degree span. The Transmitter type and setting is done following the same
method as the internally wired transmitter. The independent transmitter will be
located above the internally wired transmitter.
Clear the transmitter programming by pressing and holding buttons 'A' and 'B' for 2
seconds until the LED blinks. Drive the actuator to closed position. Press and hold
button 'A' for 2 sec until it blinks. Drive the actuator to open position. Press and hold
button 'B' for 2 sec until it blinks. For controllers fitted with standard cam/spline
activated switches/sensors, drive the actuator to the first required indication position
and set the bottom switch by lifting and rotating the bottom cam (16). Secure the cam
by allowing it to fully re-engage with the spline (17).
Maintenance
The Type VSD requires no servicing during normal working life, if installed correctly.
However, it is advisable to check mounting screws/bolts, o-rings and terminal wiring
for signs of loosening or corrosion as part of the routine plant maintenance to ensure
continued operation. Ensure safety warnings are observed during maintenance.
Inspection & maintenance to ATEX/IECEx flameproof enclosures to be carried out by
suitably trained personnel with applicable code of practice
(eg IEC/EN60079-17). Repairs to Type SRX ATEX/IECEx
flameproof enclosures are not permitted. Please consult factory.
DRAWN
REV
DATE
TITLE:
DWG NO.
SHEET 2 OF 3
VSD-IOM-002
Installation, Operating & Maintenance
VSD - IECEx/ATEX
Imtex Controls Limited
CHK'D
ECO
Tel:+44(0)8700-340002
Website: www.imtex-controls.com
This private & confidential drawing is the property
of Imtex Controls Limited, Tonbridge, UK and cannot
be copied or reproduced without the express
written permission of the Company.
13-2019
28.2.13
PT
Product Markings
Further Setting Instructions
Cable Entries
Referenced Standards
The number and type of cable entry on the Controller can be determined by reference
to the 7th digit of the monitor part number. For example, in part number -
VSD16SYSR0-IOO
the seven digit is a 'Y' which corresponds to the monitor having 3 off M25 x 1.5 cable entry
and 3 off M20 x 1.5 cable entry. Refer to table below for details.
The following standards have been referred to in
these instructions and are applicable to the use
of this product when used in an environment
where an explosive atmosphere may be present:
IEC 60079-0:2017 7th Ed
IEC60079-1:2014 7th Ed
IEC60079-11:2011 6th Ed
IEC 60079-31:2014 2nd Ed
EN60079-0:2012
EN60079-1:2014
EN60079-11:2012
EN60079-31:2014
The label on the controller should be as below:
NPT Threads conform to ANSI/ASME B1.20.1 and shall be made up wrench tight
Metric Thread tolerance to ISO 965-1 and ISO 965-3
NOTE: The year of manufacture of the monitor can
be obtained from the last 2 digits of the serial number
STATUS
REV
R
B
17-2618
14.2.17
A
PT
18-2692
1.2.18
PT
B

CC
BOT SWITCH
TOP SWITCH
CONDUIT
ENTRIES
NO
NO
NC
NC
BOTTOM
or RIGHT
SENSOR
TOP or
LEFT
SENSOR
CONTROLLER - 2 x 2-Wire Prox Sensor
VSD42, 43
CONDUIT
ENTRIES
SENSOR 1
SENSOR 2
TOP/LEFT SENSOR
BOTTOM/RIGHT SENSOR
BU
-
A
+
BU
BK
BN
-
+
A
BN
CONTROLLER - 2 x 3-Wire Prox Sensor
VSD42, 43
SENSOR 1
CONDUIT
ENTRIES
BK
SENSOR 2
CONDUIT
ENTRIES
+
-
CONTROLLER - w/ 2 WIRE
TRANSMITTER - VSD70
TRANS
EMERGENCY SHUTDOWN OUTPUT (-)
EMERGENCY SHUTDOWN OUTPUT (+)
EMERGENCY SHUTDOWN INPUT (-)
EMERGENCY SHUTDOWN INPUT (+)
'-' ACTIVE ANALOGUE INPUT 2
'+' ACTIVE ANALOGUE INPUT 2
'-' ACTIVE ANALOGUE INPUT 1
'+' ACTIVE ANALOGUE INPUT 1
NOT USED
EXTERNAL. 24VDC POWER SUPPLY (-)
2412
11
14
23
22
21
13
ALLOCATION
TERMINAL
'-' PASSIVE ANALOGUE OUTPUT (OPTIONAL)
'+' PASSIVE ANALOGUE OUTPUT (OPTIONAL)
'-' PASSIVE ANALOGUE INPUT (OPTIONAL)
10
9
NOT USED
EXTERNAL POWER SUPPLY - GROUND
7
NOT USED
8
6
ALLOCATION
TERMINAL
2
5
EXTERNAL. 24VDC POWER SUPPLY (+)
4
'+' PASSIVE ANALOGUE INPUT (OPTIONAL)
3
1
ALLOCATION
TERMINAL
VALVE CONTROLLER BOARD - NOTE: TERMINAL 7 MUST BE CONNECTED TO GROUND. ALL OTHER GROUNDS ARE INTERNALLY CONNECTED
TERMINAL
ALLOCATION
27
29
28
30
31
'+' DIGITAL OUTPUT 1
'-' DIGITAL OUTPUT 1
32
GROUND
'+' DIGITAL OUTPUT 2
'-' DIGITAL OUTPUT 2
GROUND
'+' DIGITAL OUTPUT 3
'-' DIGITAL OUTPUT 3
TERMINAL
ALLOCATION
33
39
34
40
41
42
'+' DIGITAL INPUT 1
'-' DIGITAL INPUT 1
'+' DIGITAL INPUT 2
'-' DIGITAL INPUT 2
TERMINAL
ALLOCATION
43
39
44
40
41
42
'+' DIGITAL INPUT 3
'-' DIGITAL INPUT 3
SPECIAL NOTE:
Installation of Reed Switches (without Choke):
Where reed
switches (particularly low power, Rhodium contact versions) are
installed at the end of long cable runs, it is the responsibility of the
installer to ensure suitable precautions are taken to ensure cable
capacitance does not induce premature switch failure.
Consult Imtex for further information
VSD16 - Mechanical w/ Silver Contacts
Electrical Ratings: 10.0A @ 125/250VAC
0.5A @ 125 VDC
Temp Range: -40 to +60
C
Operating Life: 400,000 Cycles
Not recommended for circuits operating less than
20mA @24VDC
VSD17 - Mechanical w/ Gold Contacts
Electrical Ratings: 1.0A @ 125VAC
0.5A @ 30 VDC
Temp Range: -40 to +60
C
Operating Life: 100,000 Cycles
Recommended for use in 24VDC computer input circuits
VSD42 - NAMUR Proximity Sensor
Current Ratings: Target Present - Current < 1.0mA
Target Absent - Current > 3.0mA
Voltage Range: 5 to 25VDC (nominal 8VDC)
Temp. Range: -25 to +60
C (T6) or +72
C (T4)
Operating Life: Unlimited Cycles
Use with intrinsically safe repeater barrier. Namur
sensors fully conform to EN60947-5-6 (VDE0660
Part 212) standard.
CONTROLLER - 2 x SPST/SPDT Switch
VSD16,17,25 & 40
For SPST Switch NC contact is not available
BL(-)
BR(+) BR(+)
BL(-)
VSD70 - Analogue Transmitter -
Non-Contact Style
Supply Voltage: 12 to 24VDC
Load Impedance: R< (U - 9) / 0.02
Linearity: < 1% of FS
Repeatability: < 0.36
Op Temp Range: -40 to +85 Deg C
BASE BOARD
Supply Voltage: 24VDC
Max Dissipated
Power under Max
Load Conditions: 3.57 Watts
Op Temp Range: -40 to +85 Deg C
See Unit Title Plate
NOTE: Terminal 7 must be connected to Ground. All other
Electronic Board grounds are connected internally
NOTE 2:If VSD is fitted to actuator with 2 Solenoids but where only one is backwired into the
Controller, Terminals 21 to 24 would be for Power and Connections to the PST Solenoid.
VSD25 (A140077) - SPDT (Rhodium) Reed Switch
Electrical Ratings: 0.5A (Switching Current)
1.0A (Steady State Current)
120V Max (Voltage)
10W/VA Max (Power)
Temp. Range: -50 to +60
C (T6) or +85
C (T4)
Operating Life: 5,000,000 Cycles
VSD25 (A140077-SU) - SPDT(Hermetically Sealed
Reed)- w/ Choke
Electrical Ratings: 0.15A @ 125VAC / 30VDC
Inductance: 680 µH
Resistance: 10 Ohms
Temp. Range: -40 to +60
C (T6) or +85
C (T4)
Operating Life: 5,000,000 Cycles
VSD40 (A140077-SU) - SPST(Hermetically Sealed
Reed - w/ Choke)
Electrical Ratings: 0.15A @ 125VAC / 30VDC
Inductance: 680 µH
Resistance: 10 Ohms
Temp. Range: -40 to +60
C (T6) or +85
C (T4)
Operating Life: 5,000,000 Cycles
VSD25 (A140088) - High Power SPDT(Hermetically
Sealed Reed - Tungsten)
Electrical Ratings: Max Current: 3 Amps
Max Power: 100 Watts/VA
Min Power: 2 Watts
Temp. Range: -40 to +60
C (T6) or +85
C (T4)
Operating Life: 5,000,000 Cycles
Not recommended for use in 24VDC operating at <20mA
DRAWN
REV
DATE
TITLE:
DWG NO.
SHEET 3 OF 3
A4
VSD-IOM-002
Installation, Operating & Maintenance
VSD - IECEx/ATEX
Imtex Controls Limited
CHK'D
ECO
Tel:+44(0)8700-340002
Website: www.imtex-controls.com
This private & confidential drawing is the property
of Imtex Controls Limited, Tonbridge, UK and cannot
be copied or reproduced without the express
written permission of the Company.
B
13-2019
28.2.13
PT
A
STATUS
R
REV
B
1.2.18
18-2692
WIRING DIAGRAMS ('X' Indicates the applicable Diagram)
ELECTRICAL CHARACTERISTICS - NON-I.S. COMPONENTS ('X' Indicates the applicable Rating(s))
INTRINSICALLY SAFE PARAMETERS
17-2618
14.2.17
PT
PT
Popular Control Unit manuals by other brands

Unical
Unical PANEL BOARD MODULATING MASTER operating instructions

schmersal
schmersal PROTECT-IE Series operating instructions

Flowserve
Flowserve Edward 602Y Maintenance manual

Savant
Savant SKL-3040-00 Quick reference guide

Dickert Electronic
Dickert Electronic DCM31 manual

Behringer
Behringer 961 Interface quick start guide